City & Guilds 2391-51 Practice Test

City & Guilds Level 3 Award in Periodic Inspection, Testing and Certification of Electrical Installations (2391-51)

City & Guilds 2391-51 overview

  • 200 practice questions
  • 32 flashcards
  • 8 study guide topics
  • 38 key terms

What you'll study

  • Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing10%
  • Safe isolation, safety management and safe working practices on site12%
  • Preparation for periodic inspection and testing: documentation, extent, sampling and limitations10%
  • Visual inspection of electrical installations and identification of non-compliance and deterioration15%
  • Differences between initial verification and periodic inspection, and agreeing the scope of the report12%
  • Dead testing: continuity, ring final circuit, polarity and insulation resistance15%
  • Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing13%
  • Recording results, condition reporting, classification codes and recommendations13%

City & Guilds 2391-51 is the Level 3 Award in Periodic Inspection, Testing and Certification of Electrical Installations. It is a competence-style qualification for practising electricians who already install and maintain circuits and now need to inspect, test, certify and condition-report existing installations rather than newly commissioned ones. Candidates are typically experienced tradespeople moving into landlord, insurance, compliance or maintenance inspection work, or consolidating skills before registering with a competent person scheme.

The assessment blends a written knowledge paper with a practical task in which the candidate inspects and tests an installation, records results and produces a condition report with classification codes and recommendations. Subject matter spans the regulations and guidance that govern periodic inspection, safe isolation and site safety management, agreeing extent and limitations with the client, sampling, visual inspection and the recognition of deterioration, the distinction between initial verification and periodic reporting, dead tests (continuity, ring final circuit, polarity, insulation resistance), live tests (earth fault loop impedance, prospective fault current, RCD and functional testing), and the documentation that ties it all together.

Preparation should combine structured revision of test theory and expected values with hands-on practice on real boards, timed paperwork drills writing schedules and condition reports, and close reading of the current qualification handbook, which is the only authoritative source for assessment format, duration, pass criteria and fees. No official parameters could be verified at the time of writing; confirm them with City & Guilds or your approved centre before booking.

Common mistakes

Stating that BS 7671 is a statutory document or that the IET Guidance Notes have legal force, instead of identifying HASAWA, EAWR and ESQCR as the statutory framework.

Candidates memorise document titles but not their legal status, so they treat all publications as equally binding.

What to do instead

Build a two-column table: statutory (HASAWA, EAWR, ESQCR, CDM) and non-statutory (BS 7671, IET Guidance Note 3, HSE HSG107). For each, state its purpose and whether breach is an offence.

Describing safe isolation as 'switch off and test' without proving the tester on a known source before and after proving dead, without locking off, and without proving all conductors at the point of work.

The procedure is learned as a slogan rather than a sequence, and exam pressure causes steps to be omitted.

What to do instead

Write out the full sequence every time: identify circuit, isolate, lock off and retain key, prove tester on known source, prove dead on all conductors at the point of work, re-prove tester, prove dead again.

Beginning a periodic inspection without a written agreed extent and limitations, and without reviewing existing certificates, schedules and previous reports.

Candidates focus on test results and treat the report as the starting point rather than agreeing scope first.

What to do instead

State that the extent, limitations and sampling approach must be agreed with the client in writing before the inspection, and that existing documentation must be reviewed to inform sampling and identify changes.

Carrying out visual inspection only at the consumer unit and missing damaged cable sheaths, unsealed enclosure entries, missing grommets, absent circuit labels, inadequate IP protection and disconnected main protective bonding.

Testing is seen as the main task and visual inspection is treated as a quick look rather than a systematic examination.

What to do instead

Use the BS 7671 inspection schedule as a checklist and inspect by location: origin, distribution boards, accessible cable routes, accessories, equipment and special locations. Record what was and was not inspected.

Describing periodic inspection as requiring 100% inspection and testing, or as including design verification and the issue of an initial verification certificate.

The candidate has learned one procedure for initial verification and applies it unchanged to periodic inspection.

What to do instead

Compare the two in a table: initial verification confirms a new installation complies with BS 7671 and includes design verification; periodic inspection assesses condition, is sampled and limited by agreement, and results in an EICR with classifications and recommendations.

Testing a ring final circuit only by measuring end-to-end r1, rn and r2 at the board and never cross-connecting conductors to verify ring continuity and identify spurs or breaks.

The end-to-end readings alone appear to confirm continuity, so the three-stage method is not completed.

What to do instead

Perform the full sequence: stage 1 end-to-end r1, rn and r2; stage 2 cross-connect opposite legs; stage 3 confirm readings at each socket and compare with expected values. Investigate any socket that does not follow the expected pattern.

Carrying out insulation resistance testing with equipment, SPDs or electronics still connected, or testing only between line and earth rather than all conductor combinations.

Isolation and disconnection are rushed, and the test is remembered as a single L-E measurement.

What to do instead

Isolate and prove dead, disconnect sensitive equipment and electronics, then test L-N, L-E and N-E at 500 V DC (or 250 V DC where required for SELV/PELV), and record the lowest valid reading.

Measuring earth fault loop impedance only at the origin, or recording prospective fault current for only one fault type without stating whether it is line-neutral or line-earth.

Ze and Zs are confused, and PFC is treated as a single quantity.

What to do instead

Measure Ze at the origin and Zs at the relevant points of the circuit, including the furthest point. Record PFC for both line-neutral and line-earth, and state the point of measurement and supply characteristics used.

Testing an RCD only by pressing its integral test button and recording 'RCD tested', without instrument tests at half, one and five times rated residual operating current and without checking both polarities.

The test button is mistaken for a full verification of RCD performance.

What to do instead

State that the integral button is a mechanical/functional check only. Use an RCD tester at ½IΔn (no trip), IΔn and 5IΔn, on both positive and negative half-cycles, record operating times and compare with BS 7671 limits.

Assigning the wrong classification code, such as recording a missing RCD on a socket circuit as C3, using C3 for a dangerous exposed live part, or using FI without a specific reason why further investigation is needed.

The definitions of C1, C2, C3 and FI are memorised loosely and applied by impression rather than by risk.

What to do instead

Apply the definitions literally: C1 = danger present, C2 = potentially dangerous, C3 = improvement recommended, FI = further investigation required without delay. For each observation, state the risk and justify the code in the report.

Exam requirements can change. Confirm current details with the exam provider.

City & Guilds 2391-51 practice

200 questions. Each one lists the choices, the correct answer, and an explanation. With JavaScript, this list opens one question at a time. The checker at the top of this page saves progress in this browser when it is available.

  1. Question 1Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which of the following is a statutory document?

    1. IET Guidance Note 3
    2. The Electricity at Work Regulations 1989 Correct answer.
    3. The IET On-Site Guide
    4. BS 7671 Requirements for Electrical Installations

    Explanation

    Statutory documents are made under powers granted by an Act of Parliament and are enforceable in law. The Electricity at Work Regulations 1989 were made under the Health and Safety at Work etc. Act 1974 and impose legal duties on duty holders. BS 7671 and the IET publications are technical standards and guidance that carry no statutory force in themselves.

  2. Question 2Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    What is the legal status of BS 7671?

    1. A non-statutory standard used as evidence of legal compliance Correct answer.
    2. A code of practice given legal force by the Building Act 1984
    3. A statutory instrument that applies only to domestic premises
    4. A statutory instrument enforced by the Health and Safety Executive

    Explanation

    BS 7671 is not made by Parliament or a Minister, so it is not law. It is widely used, however, as a means of demonstrating that the statutory duties in the Electricity at Work Regulations 1989 and the Building Regulations have been met. Its requirements can therefore be used in evidence, but a departure from it is not in itself an offence.

  3. Question 3Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which of the following places general duties on employers to ensure, so far as is reasonably practicable, the health, safety and welfare at work of their employees?

    1. The Personal Protective Equipment at Work Regulations 1992
    2. The Health and Safety at Work etc. Act 1974 Correct answer.
    3. The Provision and Use of Work Equipment Regulations 1998
    4. The Control of Substances Hazardous to Health Regulations 2002

    Explanation

    Section 2 of the Health and Safety at Work etc. Act 1974 establishes the general duty of every employer to ensure, so far as is reasonably practicable, the health, safety and welfare at work of all employees. The other instruments listed are made under that Act and deal with specific hazards or equipment.

  4. Question 4Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Regulation 16 of the Electricity at Work Regulations 1989 deals with which of the following?

    1. The reporting of dangerous occurrences
    2. The notification of work to building control
    3. The earthing of exposed conductive parts
    4. Competence to prevent danger and injury Correct answer.

    Explanation

    Regulation 16 prohibits any person from being engaged in work where technical knowledge or experience is needed to prevent danger or injury unless that person has the necessary knowledge or experience or is adequately supervised. It is the main competence requirement in the Regulations.

  5. Question 5Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    IET Guidance Note 3 is primarily concerned with which activity?

    1. Earthing and bonding design
    2. Inspection and testing Correct answer.
    3. Selection of cables for voltage drop
    4. Protection against overcurrent

    Explanation

    Guidance Note 3 is the IET's guidance on the inspection and testing of electrical installations and supports the relevant parts of BS 7671. It covers initial verification, periodic inspection and the associated certification and reporting.

  6. Question 6Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    BS 7671 applies to electrical installations operating at voltages not exceeding which value?

    1. 11 kV ac between conductors
    2. 230 V ac between conductors
    3. 1500 V ac between conductors
    4. 1000 V ac between conductors Correct answer.

    Explanation

    The scope of BS 7671 covers installations with a nominal voltage up to and including 1000 V ac between conductors, or 1500 V dc between conductors. Installations above these levels fall outside the Regulations and are dealt with by other standards.

  7. Question 7Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Regulation 4 of the Electricity at Work Regulations 1989 requires electrical systems to be:

    1. Inspected and tested at intervals not exceeding five years
    2. Fitted with residual current devices at the origin
    3. Of such construction and maintained so as to prevent danger Correct answer.
    4. Certified by a registered third party before being energised

    Explanation

    Regulation 4 imposes a duty on persons with control of electrical systems to ensure that the systems are of such construction and are maintained so as to prevent danger. It is a general duty of construction and maintenance rather than a prescribed testing regime.

  8. Question 8Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Under the Electricity at Work Regulations 1989, work on or near a live conductor is permitted only where, among other conditions:

    1. Two competent persons are present for the whole of the work
    2. The circuit is protected by a 30 mA residual current device
    3. A permit to work has been issued and countersigned by the duty holder
    4. It is unreasonable in all the circumstances for it to be dead Correct answer.

    Explanation

    Regulation 14 permits live work only where it is unreasonable in all the circumstances for the conductor to be dead, and where it is reasonable for the work to be carried out live and suitable precautions are taken. All three conditions must be satisfied, so a permit, an RCD or a second person alone will not justify live working.

  9. Question 9Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Regulation 13 of the Electricity at Work Regulations 1989 requires that where conductors are made dead, precautions are taken to prevent them:

    1. Being worked on by more than one person
    2. Becoming live while the work is in progress Correct answer.
    3. Being earthed at the origin of the installation only
    4. Being inspected more than once a year

    Explanation

    Regulation 13 requires suitable precautions to prevent a conductor that has been made dead from becoming electrically charged during the work and, where applicable, when it is not being worked on. This normally involves secure isolation, proving dead and, where necessary, earthing.

  10. Question 10Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Under Part P of the Building Regulations, which of the following types of work in a dwelling in England is notifiable?

    1. Replacing a damaged light switch
    2. Replacing a broken ceiling rose
    3. Installing a complete new circuit for a garden shed Correct answer.
    4. Replacing a damaged socket outlet with an identical one

    Explanation

    In England, notifiable electrical work includes the installation of a new circuit, the replacement of a consumer unit or similar device, and certain work in special locations. Like-for-like replacement of accessories and repair or maintenance work are not notifiable.

  11. Question 11Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    The Electricity Safety, Quality and Continuity Regulations 2002 place duties primarily on which group?

    1. Electrical contractors carrying out periodic inspection
    2. Local authority building control bodies
    3. Distributors and suppliers of electricity Correct answer.
    4. Owners of domestic premises

    Explanation

    The ESQCR 2002 regulate the supply of electricity and impose duties on distributors and suppliers, covering such matters as voltage and frequency limits, earthing arrangements and continuity of supply. Duties on installers and premises owners derive from other legislation, chiefly the Electricity at Work Regulations 1989 and the Building Regulations.

  12. Question 12Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which of the following would be reportable as a dangerous occurrence under RIDDOR?

    1. A circuit breaker tripping due to overload with no damage
    2. An electrical short circuit causing a fire Correct answer.
    3. A 30 mA RCD operating during a test
    4. A luminous tube sign failing to strike

    Explanation

    RIDDOR lists certain electrical events as reportable dangerous occurrences, including an electrical short circuit or overload that causes a fire or explosion. Correct operation of protective devices and routine test operations are not reportable.

  13. Question 13Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which Regulations require an employer to make a suitable and sufficient assessment of the risks to health and safety arising from their work activities?

    1. Reporting of Injuries, Diseases and Dangerous Occurrences Regulations 2013
    2. Management of Health and Safety at Work Regulations 1999 Correct answer.
    3. Health and Safety (First-Aid) Regulations 1981
    4. Personal Protective Equipment at Work Regulations 1992

    Explanation

    The Management of Health and Safety at Work Regulations 1999 require employers to assess the risks to workers and others affected by their undertaking, and to record the significant findings where they employ five or more persons. Risk assessment underpins the selection of precautions taken during inspection and testing work.

  14. Question 14Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which statement correctly describes the relationship between Part P of the Building Regulations and BS 7671?

    1. Part P covers all the premises within the scope of BS 7671
    2. BS 7671 overrides Part P where the two conflict
    3. Compliance with BS 7671 guarantees compliance with Part P
    4. Adopting BS 7671 can demonstrate compliance with Part P Correct answer.

    Explanation

    Part P sets the legal requirement for reasonable provision for safety in electrical installations in dwellings, while BS 7671 provides the detailed technical rules. Approved Document P recognises that designing and installing to BS 7671 is a way of satisfying Part P, but it is not the only route and cannot guarantee compliance in every respect.

  15. Question 15Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Under the Electricity Safety, Quality and Continuity Regulations 2002, the declared low voltage single-phase supply of 230 V may vary within which limits?

    1. +6% / −10%
    2. +10% / −6% Correct answer.
    3. ±6%
    4. ±10%

    Explanation

    The ESQCR prescribe a declared voltage of 230 V with a permitted variation of +10% / −6%, giving a range of approximately 253 V to 216 V. This asymmetric tolerance reflects the historical harmonisation of UK and European supply voltages.

  16. Question 16Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which HSE publication gives guidance on voltage detectors and test lamps used by electricians?

    1. GS38 Electrical test equipment for use by electricians Correct answer.
    2. HSG85 Electricity at work: safe working practices
    3. HSR25 Memorandum of Guidance on the Electricity at Work Regulations
    4. INDG231 Electrical safety and you

    Explanation

    GS38 is the HSE guidance document covering the construction, selection and use of test equipment such as test lamps and voltage detectors, including the requirements for fused test leads and accessible probe tips. It is commonly referred to when selecting equipment for proving dead.

  17. Question 17Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Where the HSE Memorandum of Guidance on the Electricity at Work Regulations is not followed, what is the legal position?

    1. It does not create offences but can be used as evidence Correct answer.
    2. It replaces the Regulations in the premises where it is applied
    3. It has no legal standing and cannot be referred to in court
    4. It is a statutory code, so any departure from it is an offence

    Explanation

    The Memorandum is guidance, not legislation; only the Regulations themselves create offences. Failure to follow guidance is not in itself an offence, but a court may take the guidance into account when deciding whether a duty holder has failed to comply with the Regulations.

  18. Question 18Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which Regulations require work equipment to be maintained in an efficient state, in efficient working order and in good repair?

    1. The Building Regulations 2010
    2. The Management of Health and Safety at Work Regulations 1999
    3. The Electricity at Work Regulations 1989
    4. The Provision and Use of Work Equipment Regulations 1998 Correct answer.

    Explanation

    Regulation 5 of PUWER 1998 requires work equipment to be maintained in an efficient state, in efficient working order and in good repair, with any necessary log of maintenance kept. For electrical equipment this supports, and is supported by, the maintenance duty in regulation 4 of the Electricity at Work Regulations.

  19. Question 19Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Which IET publication gives practical guidance and standard circuit arrangements for domestic and similar installations?

    1. IET Guidance Note 5
    2. The IET On-Site Guide Correct answer.
    3. IET Guidance Note 3
    4. The IET Code of Practice for In-service Inspection and Testing

    Explanation

    The On-Site Guide is the IET's practical companion to BS 7671, presenting standard circuit arrangements, tables and worked guidance for typical domestic and similar installations. It is non-statutory guidance and does not replace the requirements of BS 7671.

  20. Question 20Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

    Under the Health and Safety at Work etc. Act 1974, which duty is placed on employees while at work?

    1. To take reasonable care of themselves and of others affected Correct answer.
    2. To ensure that the installation complies with BS 7671
    3. To provide a written risk assessment before every job is started
    4. To appoint a competent person to supervise all work

    Explanation

    Section 7 of the Act requires employees to take reasonable care for their own health and safety and that of others who may be affected by their acts or omissions, and to co-operate with their employer so far as is necessary to enable duties to be met. These duties apply alongside the employer's duties and are not transferred to the employee.

  21. Question 21Safe isolation, safety management and safe working practices on site

    What is the correct first step when carrying out safe isolation of a circuit?

    1. Fix a warning notice to the distribution board
    2. Test the voltage indicator on a proving unit
    3. Identify the circuit and its isolation device Correct answer.
    4. Operate the main switch at the origin of the installation

    Explanation

    Safe isolation starts with identifying exactly which circuit is to be worked on and which device isolates it, so that the correct point of isolation is used. Operating devices, fitting locks and notices, and proving the tester all follow once the correct isolation point is known.

  22. Question 22Safe isolation, safety management and safe working practices on site

    According to GS38, what is the maximum length of exposed metal permitted at the tip of a test probe?

    1. 6 mm
    2. 3 mm
    3. 2 mm
    4. 4 mm Correct answer.

    Explanation

    GS38 limits the exposed metal tip of test probes to no more than 4 mm, and recommends shorter tips where practicable, to reduce the chance of short circuits and contact with adjacent live parts. Finger guards and shrouded, fused leads complete the protection.

  23. Question 23Safe isolation, safety management and safe working practices on site

    After proving a circuit dead with an approved voltage indicator, what must be done before work begins?

    1. Re-prove the indicator on a known source or proving unit Correct answer.
    2. Switch the circuit breaker back on briefly
    3. Apply insulating tape over the conductors
    4. Record the readings in the site log

    Explanation

    The indicator must be proved before use and re-proved immediately afterwards, so that a tester that has failed during the test cannot give a false dead result. Only when the indicator still operates correctly can the dead test be relied upon.

  24. Question 24Safe isolation, safety management and safe working practices on site

    When a padlock has been fitted to secure an isolation, who should hold the key?

    1. The client's duty holder
    2. The person carrying out the work Correct answer.
    3. The site supervisor, whether or not they are working on the circuit
    4. Whoever is nearest to the distribution board

    Explanation

    The key must stay in the possession of the person working on the circuit, so that nobody else can restore the supply while the work is in progress. Where several people work on the same isolation, each fits a personal lock to a multi-lock hasp.

  25. Question 25Safe isolation, safety management and safe working practices on site

    Which notice should be fixed at the point of isolation while work is in progress?

    1. Do not switch on - men working Correct answer.
    2. Danger - high voltage
    3. Fire exit - keep clear
    4. Authorised persons only

    Explanation

    A warning notice stating that the circuit must not be switched on because people are working on it is fixed at the isolation point alongside the lock. It warns others who may not know the work is taking place not to re-energise the circuit.

  26. Question 26Safe isolation, safety management and safe working practices on site

    A colleague is gripping a live conductor and cannot let go. What should be done first?

    1. Isolate the supply before touching the casualty Correct answer.
    2. Start CPR immediately without moving them
    3. Throw water over the conductor to break contact
    4. Pull the casualty clear by their clothing

    Explanation

    The supply must be isolated before the casualty is touched, otherwise the rescuer becomes part of the circuit and may also be electrocuted. If isolation cannot be achieved quickly, an insulated object may be used to separate the casualty from the conductor.

  27. Question 27Safe isolation, safety management and safe working practices on site

    When proving a single-phase circuit dead at the point of work, which tests are required?

    1. Line to neutral only
    2. Between the lines of adjacent circuits
    3. Line to earth only
    4. All three combinations: L-N, L-E and N-E Correct answer.

    Explanation

    Dead testing must be carried out between every pair of conductors that could be at different potentials, which for a single-phase circuit means line to neutral, line to earth and neutral to earth. Testing only one pair could miss a conductor that is still live.

  28. Question 28Safe isolation, safety management and safe working practices on site

    Why should a short wait be allowed after isolating a circuit with long cable runs or large capacitors before proving dead?

    1. The breaker mechanism needs time to settle
    2. Stored charge may still be present after isolation Correct answer.
    3. The cable insulation needs time to cool
    4. The indicator needs time to self-calibrate

    Explanation

    Capacitance in long cables, capacitor banks and electronic equipment can hold a dangerous charge after the supply is removed. A suitable delay, or an approved discharge procedure, allows the charge to decay before the circuit is proved dead.

  29. Question 29Safe isolation, safety management and safe working practices on site

    Why is a non-contact voltage detector unsuitable as the sole means of proving a circuit dead?

    1. It is not permitted on domestic installations
    2. It can only be used on earthed systems
    3. It cannot detect alternating voltages
    4. It may fail to indicate a voltage, giving a false dead reading Correct answer.

    Explanation

    Non-contact detectors can be affected by screening, capacitative coupling and low battery condition, so they may fail to respond to a live conductor. An approved voltage indicator tested against a known source, or proving unit, is required to prove dead.

  30. Question 30Safe isolation, safety management and safe working practices on site

    Why must the neutral conductor of a single-phase circuit be proved dead as well as the line conductor?

    1. The RCD does not monitor the neutral
    2. Neutrals are always at earth potential
    3. It can become live if the neutral is disconnected Correct answer.
    4. The neutral carries no current when the load is off

    Explanation

    A neutral is a live conductor and can rise to a dangerous potential if it is disconnected, if the supply is reversed, or if it is fed from another source. It must therefore be isolated and proved dead like any other live conductor.

  31. Question 31Safe isolation, safety management and safe working practices on site

    Before isolating a final circuit in a building fitted with a rooftop PV array and a standby generator, what must be established?

    1. That the PV array has been cleaned recently
    2. That the inverter has been installed correctly
    3. Whether the circuit can be back-fed from another source Correct answer.
    4. That the installation has a valid EICR

    Explanation

    Alternative sources such as PV, generators, UPS units and standby supplies can keep a circuit energised after the mains isolator is opened. Each source must be identified and isolated, secured and proved dead before work begins.

  32. Question 32Safe isolation, safety management and safe working practices on site

    Two electricians are to work on the same isolated circuit. How should the isolation be secured?

    1. A warning notice alone is sufficient
    2. Each person fits their own padlock to a multi-lock hasp Correct answer.
    3. The supervisor holds a single padlock and key
    4. One padlock is shared and the key passed between them

    Explanation

    Each person must control their own lock so that the isolation cannot be removed until everyone has finished and removed their own lock. A multi-lock hasp allows several padlocks to secure a single isolation point.

  33. Question 33Safe isolation, safety management and safe working practices on site

    What is the main purpose of a permit-to-work system for electrical isolation?

    1. To remove the need for proving the circuit dead at the point of work
    2. To record the time and cost of the isolation for the client
    3. To formally confirm that the isolation is safe to work on Correct answer.
    4. To allow unskilled staff to work live under supervision

    Explanation

    A permit-to-work provides a recorded, authorised statement that the necessary isolations and precautions have been applied before work starts, and it is formally cancelled when work finishes. It supports, but never replaces, physical locking and proof of dead.

  34. Question 34Safe isolation, safety management and safe working practices on site

    Under what circumstances does BS 7671 permit work on or near live conductors?

    1. When the circuit voltage is below 230 V
    2. Whenever the circuit is protected by an RCD
    3. When the client accepts the risk in writing
    4. Only where it is unreasonable to work dead and precautions are taken Correct answer.

    Explanation

    Live work is permitted only where it is unreasonable for the work to be done dead and where suitable precautions, including a risk assessment, competent persons and appropriate PPE, are in place. Convenience or client preference is not sufficient justification.

  35. Question 35Safe isolation, safety management and safe working practices on site

    When applying the hierarchy of control to a hazard on site, what should be considered first?

    1. Eliminate the hazard altogether Correct answer.
    2. Write a method statement for the task
    3. Display warning signs around the area
    4. Provide personal protective equipment

    Explanation

    The hierarchy of control starts with eliminating the hazard, for example by arranging the work to be done dead rather than live. Only when elimination is not reasonably practicable should the risk be reduced, protected against or managed by administrative controls and PPE.

  36. Question 36Safe isolation, safety management and safe working practices on site

    What should happen before a method statement is used for a task on site?

    1. It should be prepared by the least experienced member of the team
    2. It should be issued to the client only after the work is finished
    3. Those carrying out the work should have it explained to them Correct answer.
    4. It should be filed in the site office without being discussed

    Explanation

    A method statement only controls risk if the people doing the work understand it, so it must be briefed to the team, with the opportunity to ask questions, before work starts. It is then followed, and revised if conditions change.

  37. Question 37Safe isolation, safety management and safe working practices on site

    Which of the following must be reported to the enforcing authority under RIDDOR?

    1. A damaged socket outlet that has been isolated
    2. A minor cut to a finger while stripping cable
    3. An electrical short circuit that caused a fire on site Correct answer.
    4. A worker arriving late for a shift

    Explanation

    RIDDOR requires the reporting of specified injuries, dangerous occurrences and certain ill health, and an electrical short circuit or overload causing a fire or explosion is a reportable dangerous occurrence. Minor first-aid injuries and equipment defects that have been made safe are recorded locally instead.

  38. Question 38Safe isolation, safety management and safe working practices on site

    Which type of portable fire extinguisher is suitable for a fire in live electrical equipment?

    1. Water
    2. Carbon dioxide Correct answer.
    3. Wet chemical
    4. Foam

    Explanation

    Carbon dioxide extinguishers are suitable for fires involving live electrical equipment because the gas is non-conductive and leaves no residue. Water, foam and wet chemical extinguishers are conductive and must not be used on live apparatus.

  39. Question 39Safe isolation, safety management and safe working practices on site

    When proving a three-phase and neutral distribution board dead at the point of work, which tests are required?

    1. Between each phase and neutral only
    2. Between each phase and earth only
    3. Between one phase and earth as a sample
    4. Between all conductors, in every combination Correct answer.

    Explanation

    Every pair of conductors that could be at different potentials must be tested, which means each phase to neutral, each phase to each other phase, each phase to earth and neutral to earth. Testing a sample combination could leave an energised conductor undetected.

  40. Question 40Safe isolation, safety management and safe working practices on site

    A circuit breaker has been switched off and locked. Why is this not, on its own, enough to make the circuit safe to work on?

    1. The breaker contacts may open too slowly
    2. It may still be live from another source and must be proved dead Correct answer.
    3. The lock may be removed by the client at any time
    4. A circuit breaker does not provide overload protection

    Explanation

    Switching off and locking does not guarantee the conductors are dead: the circuit may be back-fed, the device may be faulty, or the wrong device may have been operated. The conductors must always be proved dead at the point of work with an approved indicator.

  41. Question 41Safe isolation, safety management and safe working practices on site

    The main switch of a consumer unit has been locked off and the outgoing terminals proved dead. Why does work inside the unit remain hazardous?

    1. The incoming supply terminals upstream of the main switch remain live Correct answer.
    2. The neutral bar becomes live when the main switch is off
    3. Locking off causes the main switch to overheat
    4. The main switch can reclose automatically

    Explanation

    A main switch isolates only the outgoing side of the installation; the incoming meter tails and the supply terminals of the switch stay live. Work inside the enclosure must avoid those barriers and guards, or the supply must be isolated upstream by the distributor.

  42. Question 42Safe isolation, safety management and safe working practices on site

    Why does GS38 require test leads to incorporate a fuse or other protective device?

    1. To prevent use on three-phase systems
    2. To increase the sensitivity of the voltage indicator
    3. To reduce the cost of replacing damaged leads
    4. To limit the current if the leads short across a supply Correct answer.

    Explanation

    If the probes accidentally bridge live parts, the fuse limits the fault current and reduces the energy of the resulting arc, protecting the user from burns and blast. The leads must also be adequately rated and kept in good condition.

  43. Question 43Safe isolation, safety management and safe working practices on site

    Which PPE is appropriate when operating a large isolator that may produce an arc?

    1. A dust mask and ear defenders
    2. Arc-rated clothing and a face shield Correct answer.
    3. Ordinary spectacles and rubber gloves
    4. Cotton overalls and safety boots only

    Explanation

    Switching large isolators can produce an arc with intense heat, molten metal and blast, so arc-rated clothing and a face shield are worn, along with the correct gloves for the task. The risk assessment for the switching operation determines the specific PPE required.

  44. Question 44Safe isolation, safety management and safe working practices on site

    What does the CAT III marking on a voltage detector indicate?

    1. It is rated to withstand transient overvoltages expected in that location Correct answer.
    2. It is suitable only for domestic single-phase work
    3. It is able to measure currents up to 1000 A
    4. It is waterproof to IPX3

    Explanation

    Measurement category markings show the transient overvoltage environment the instrument is designed to withstand, with CAT III covering distribution level circuits such as distribution boards and fixed wiring. The instrument must be rated at least for the category and voltage of the point where it is used.

  45. Question 45Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Which document is issued to the person ordering a periodic inspection and test of an existing installation?

    1. A Minor Electrical Installation Works Certificate
    2. A Schedule of Inspections
    3. An Electrical Installation Certificate
    4. An Electrical Installation Condition Report Correct answer.

    Explanation

    Periodic inspection and testing of an existing installation is reported on an Electrical Installation Condition Report, the model form given in BS 7671. The report records the condition of the installation, the observations and classifications, and the recommended date of the next inspection.

  46. Question 46Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Which information should the inspector request from the client before starting a periodic inspection?

    1. The manufacturer's instructions for the supply transformer
    2. The previous inspection reports and certificates Correct answer.
    3. The building's public liability insurance policy
    4. The supplier's diagram of the local distribution network

    Explanation

    Existing documentation helps the inspector to establish the extent of the installation, plan the sample and compare earlier results with those obtained now. It should be requested at the preparation stage, before any work begins.

  47. Question 47Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    With whom must the extent of, and limitations to, a periodic inspection be agreed?

    1. The electricity distribution network operator
    2. The manufacturer of the protective devices
    3. The local authority building control body
    4. The person ordering the inspection Correct answer.

    Explanation

    BS 7671 requires the extent of the inspection and any limitations to be agreed with the person ordering the work before the inspection begins. What has been agreed is then recorded on the report so that readers know what it covers.

  48. Question 48Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    On an Electrical Installation Condition Report, where are parts of the installation that were not inspected or tested recorded?

    1. In the observations and recommendations
    2. In the schedule of test results
    3. In the extent and limitations section Correct answer.
    4. In the declaration on the report

    Explanation

    The report has a dedicated extent and limitations section describing the parts covered and, importantly, the parts not covered by the inspection. This allows the reader to judge how much of the installation the report actually relates to.

  49. Question 49Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    On a schedule of inspections, the abbreviation LIM indicates that the item:

    1. has a limited service life and must be replaced
    2. was not inspected or tested because of a limitation Correct answer.
    3. has a fault level that is limited and cannot be measured
    4. needs a low-current test instead of a full test

    Explanation

    LIM is entered against an item that fell within the agreed extent but could not be inspected or tested, for example because of lack of access or because the supply could not be isolated. The reason is described in the extent and limitations section of the report.

  50. Question 50Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Where a periodic inspection is to be based on a sample, what minimum proportion of the installation does GN3 recommend the sample should cover?

    1. 50%
    2. 25%
    3. 10% Correct answer.
    4. 5%

    Explanation

    GN3 recommends that a sampling inspection covers at least 10% of the items in the installation, including at least one example of each type of item. The sample is then extended if defects are found.

  51. Question 51Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    During a sampling inspection, several socket outlets on one circuit are found to have damaged shutters. What should the inspector do?

    1. Record the defects found and keep to the original sample size
    2. Issue a danger notice for the whole installation and stop work
    3. Extend the sample to cover similar items Correct answer.
    4. Reduce the extent so the remaining outlets are not covered

    Explanation

    Where a sample reveals defects that are likely to be repeated elsewhere, the sample must be increased so that the condition of similar items can be assessed. The extension is a matter of engineering judgement and will often cover all items of the affected type.

  52. Question 52Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    In the context of a periodic inspection, the term extent refers to:

    1. the total length of cable contained in the installation
    2. the time allowed to complete the inspection
    3. the parts of the installation to be covered Correct answer.
    4. the maximum demand of the installation in amperes

    Explanation

    Extent describes the scope of the work: which parts of the installation are to be inspected and tested and, by implication, which are excluded. It is agreed with the person ordering the work before the inspection starts.

  53. Question 53Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    A previous condition report and its schedules are available for an installation that shows no obvious signs of alteration. How should the inspector use these records?

    1. To disregard them because only freshly measured results are valid
    2. To copy the earlier results into the new report without carrying out tests
    3. To justify extending the period before the next inspection is due
    4. To help plan sampling and compare old and new results Correct answer.

    Explanation

    Historical records are a valuable aid when preparing for a periodic inspection because they show what was installed and tested previously. They inform the sample and provide a baseline, but the present condition must still be assessed by inspection and testing.

  54. Question 54Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    The schedule of inspections that accompanies a condition report is used to record:

    1. the measured insulation resistance and loop impedance values
    2. the signature and competence of the inspector
    3. the results of the visual inspection of each item checked Correct answer.
    4. the details of any limitations agreed with the client

    Explanation

    The schedule of inspections lists the items to be checked visually and records the outcome for each, such as satisfactory, not applicable or limited access. Measured values are recorded separately on the schedule of test results.

  55. Question 55Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Which of the following is recorded on the schedule of test results?

    1. The visual condition of each accessory inspected
    2. The date recommended for the next inspection
    3. The measured values for each circuit tested Correct answer.
    4. The reasons for any agreed limitations

    Explanation

    The schedule of test results has one row per circuit and records the values measured, such as continuity, insulation resistance, polarity, earth fault loop impedance, RCD operating times and prospective fault current. It is the quantitative record supporting the conclusions in the report.

  56. Question 56Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    On a condition report, a classification code C3 means that:

    1. the item needs further investigation by a specialist
    2. danger exists and immediate action is required
    3. the installation is potentially dangerous and urgent action is needed
    4. improvement is recommended as it does not meet the current edition Correct answer.

    Explanation

    C3 is used where an item does not comply with the current edition of BS 7671 but is not considered dangerous, so improvement is recommended rather than required urgently. C1 and C2 are reserved for danger present and potentially dangerous conditions respectively.

  57. Question 57Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Immediately after identifying a C1 condition during a periodic inspection, what should the inspector do?

    1. Continue the inspection and report the condition when the report is issued
    2. Reclassify it as C2 so the client can arrange work within 28 days
    3. Issue a danger notice and inform the person responsible without delay Correct answer.
    4. Record it as a limitation because only a sample was inspected

    Explanation

    A C1 classification means danger is present and immediate action is required, so the person responsible must be warned without waiting for the report. A danger notice is issued so the hazard is formally recorded and remedial action is prompted.

  58. Question 58Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Which items must be provided with a completed Electrical Installation Condition Report?

    1. An Electrical Installation Certificate and a Minor Works Certificate
    2. The client's written authorisation for the inspection
    3. Calibration certificates for the instruments used
    4. A schedule of inspections and a schedule of test results Correct answer.

    Explanation

    The condition report is issued together with its schedule of inspections and schedule of test results, which hold the detail behind the report. The three items together form the complete report package.

  59. Question 59Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    A building previously used as offices is converted for use as a restaurant with commercial cooking equipment. What effect should this have on periodic inspection?

    1. The next inspection may be deferred because the cooking appliances are plug-in
    2. None, because the fixed wiring has not been altered
    3. The installation automatically becomes industrial with a three-year interval
    4. The change of use should be reviewed and an earlier inspection considered Correct answer.

    Explanation

    The recommended interval depends on the use, environment and loading of the installation, and a change of use can alter these significantly. The inspector should review the change and may recommend an earlier inspection and a shorter interval in future.

  60. Question 60Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    When selecting items for a sampling inspection, the inspector should make sure that the sample:

    1. is taken entirely from the most recently installed section
    2. contains only items that are quick and easy to reach
    3. is restricted to the circuits listed on the original certificate
    4. is representative and covers each type of item across the site Correct answer.

    Explanation

    A sample is only valid if it fairly represents the installation as a whole, so it must include each type of circuit and equipment and be distributed across the premises. A sample drawn from one convenient area tells the inspector little about the rest.

  61. Question 61Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    A hotel commissions a periodic inspection, but six of its twenty guest bedrooms will be occupied throughout the visit. What is the most appropriate action?

    1. Inspect the occupied bedrooms while the guests are out of the room
    2. Agree and record the limitation, excluding those bedrooms from the extent Correct answer.
    3. Inspect 14 bedrooms and report that the whole hotel was inspected
    4. Postpone the whole inspection until every bedroom is vacant

    Explanation

    Where parts of the installation cannot be accessed, the exclusion must be agreed and recorded clearly as a limitation on the report. The report then honestly reflects what was and was not covered.

  62. Question 62Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    The interval recommended on a condition report before the next periodic inspection is based mainly on:

    1. the value of prospective fault current at the origin
    2. the rating of the main protective device
    3. the type and use of the premises, its environment and maintenance Correct answer.
    4. the number of circuits in the installation

    Explanation

    The recommended interval reflects how quickly an installation is likely to deteriorate, which depends on the type of premises, its use, the environment, the standard of maintenance and the condition found. It is not set by the size or fault level of the installation.

  63. Question 63Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    Since the last periodic inspection, new circuits have been added to an installation. How should the inspector treat them?

    1. Treat them as outside the extent until the next full inspection is due
    2. Include them in the extent and check that the associated certification exists Correct answer.
    3. Ignore them because they are covered by a separate certificate
    4. Reduce the sample size because the new circuits are known to be satisfactory

    Explanation

    The periodic inspection must cover the installation as it exists now, including additions made since the last report. The inspector should also confirm that the additions were properly certified so their design and construction can be relied on.

  64. Question 64Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

    During an inspection, a protective measure cannot be verified without disturbing fixed equipment that the client will not allow to be dismantled. No danger can be confirmed. Which classification should be recorded against this observation?

    1. FI Correct answer.
    2. C3
    3. LIM
    4. C1

    Explanation

    FI is used where the inspector has identified something needing further investigation before compliance or danger can be established. LIM records an item that was not inspected at all, whereas here a concern has been raised that cannot be resolved without more work.

  65. Question 65Visual inspection of electrical installations and identification of non-compliance and deterioration

    What is the main purpose of the visual inspection element of a periodic inspection and test?

    1. to confirm that the test instruments have a current calibration certificate
    2. to calculate the prospective fault current at the origin
    3. to establish the maximum demand of the installation
    4. to identify defects and deterioration that could cause danger Correct answer.

    Explanation

    Visual inspection is carried out before and during testing to detect damage, deterioration, defects, non-compliance and the effects of external influences that may give rise to danger. It is not a design exercise and does not replace instrument checks.

  66. Question 66Visual inspection of electrical installations and identification of non-compliance and deterioration

    The findings of a periodic inspection and test are recorded on which document?

    1. an electrical installation condition report Correct answer.
    2. a minor electrical installation works certificate
    3. a schedule of test results on its own
    4. an electrical installation certificate

    Explanation

    A periodic inspection and test results in an electrical installation condition report, supported by a schedule of inspections and a schedule of test results. Certificates are used to certify new work or alterations.

  67. Question 67Visual inspection of electrical installations and identification of non-compliance and deterioration

    In the IP rating IPX4, the second character relates to protection against:

    1. ingress of water Correct answer.
    2. ingress of solid foreign objects
    3. mechanical impact on the enclosure
    4. contact with live internal parts

    Explanation

    In the IP code the first character denotes protection against access to hazardous parts and ingress of solid objects, and the second character denotes protection against ingress of water. The X simply means the first characteristic is not specified.

  68. Question 68Visual inspection of electrical installations and identification of non-compliance and deterioration

    Which observation code is used where an inspection finds a defect that presents immediate danger?

    1. FI
    2. C3
    3. C1 Correct answer.
    4. C2

    Explanation

    C1 is reserved for defects that present immediate danger, where urgent action is required. C2 covers potentially dangerous conditions, C3 recommends improvement and FI indicates that further investigation is needed before a code can be given.

  69. Question 69Visual inspection of electrical installations and identification of non-compliance and deterioration

    Which colour identifies a protective conductor throughout its length?

    1. brown
    2. black
    3. green with a yellow stripe Correct answer.
    4. blue

    Explanation

    Protective conductors are identified by the combination of green and yellow, and this identification must run throughout the length of the conductor. Other colours must not be used to identify a protective conductor.

  70. Question 70Visual inspection of electrical installations and identification of non-compliance and deterioration

    Why is a missing blanking plate on a spare way of a consumer unit recorded as a defect?

    1. it prevents the main switch from being operated
    2. it leaves live parts accessible Correct answer.
    3. it reduces the current rating of the busbar
    4. it increases the earth fault loop impedance of the circuits

    Explanation

    Unused openings must be closed to maintain the degree of protection of the enclosure and to prevent contact with live parts. The blanking plate forms part of the enclosure and its absence is a breach of the requirements for protection against direct contact.

  71. Question 71Visual inspection of electrical installations and identification of non-compliance and deterioration

    Which of these is a typical visual indication that a cable termination has been overheating?

    1. a smell of solvent from the cable sheath
    2. a light green deposit on the brass terminal
    3. discoloured insulation and blackened strands Correct answer.
    4. a cable marker that has fallen off

    Explanation

    Overheating at a termination discolours the insulation and blackens the copper strands, usually because a loose or corroded connection has raised the resistance. Such a finding requires investigation and appropriate coding.

  72. Question 72Visual inspection of electrical installations and identification of non-compliance and deterioration

    A cable sheath that has become hard and brittle in an older installation is most likely to indicate:

    1. the circuit is protected by an RCBO
    2. age-related deterioration of the cable material Correct answer.
    3. the cable is installed in trunking
    4. the cable is larger than the recorded size

    Explanation

    Sheathing materials harden and become brittle with age and with exposure to heat and ultraviolet light. Cables in this condition crack easily and can lose insulation performance, so deterioration must be reported.

  73. Question 73Visual inspection of electrical installations and identification of non-compliance and deterioration

    In a TN-S domestic installation with 25 mm² line conductors, the minimum cross-sectional area of the main protective bonding conductor to the metallic water installation is:

    1. 10 mm² Correct answer.
    2. 16 mm²
    3. 25 mm²
    4. 6 mm²

    Explanation

    Table 54.8 requires a main protective bonding conductor of at least 10 mm² where the line conductors are 35 mm² or less. A smaller conductor may be acceptable for supplementary bonding but not for main protective bonding.

  74. Question 74Visual inspection of electrical installations and identification of non-compliance and deterioration

    Main protective bonding to the incoming metallic water pipe should be connected:

    1. within 600 mm of the meter outlet, before any branch Correct answer.
    2. at the point where the pipework leaves the building
    3. at the furthest accessible point on the pipe run
    4. to the body of the water meter using a strap

    Explanation

    Bonding is made to the consumer's pipework as close as practicable to the point of entry and, in any case, within 600 mm of the meter outlet or point of entry and before any branch. This ensures that all downstream metallic pipework is effectively bonded.

  75. Question 75Visual inspection of electrical installations and identification of non-compliance and deterioration

    What should the label fitted at each main protective bonding connection state?

    1. Do not paint – electrical connection
    2. Bonding point – minimum 10 mm²
    3. Earthing conductor – test annually
    4. Safety electrical connection – do not remove Correct answer.

    Explanation

    Each main protective bonding connection must carry a durable warning label reading 'Safety electrical connection – do not remove'. The label exists to prevent the connection being disconnected by others.

  76. Question 76Visual inspection of electrical installations and identification of non-compliance and deterioration

    Where a cable passes through a fire-resisting wall or ceiling, the opening should be:

    1. plugged with mineral wool only
    2. fitted with a plastic plate on each side
    3. left open so that heat from the cable can dissipate freely
    4. sealed to maintain the fire resistance of the structure Correct answer.

    Explanation

    Openings made for cables in fire-resisting elements must be sealed with a suitable fire-stopping system so that the fire resistance of the wall or floor is maintained. The sealing method must be appropriate to the element and the cable.

  77. Question 77Visual inspection of electrical installations and identification of non-compliance and deterioration

    During a periodic inspection of a dwelling, a 13 A socket outlet intended to supply portable equipment outdoors has no 30 mA RCD protection. The observation should be coded:

    1. C3
    2. C1
    3. C2 Correct answer.
    4. FI

    Explanation

    Absence of 30 mA RCD protection for socket outlets that may supply portable equipment outdoors is a potentially dangerous condition and is coded C2. C1 would be used only where danger is present now, such as accessible live parts.

  78. Question 78Visual inspection of electrical installations and identification of non-compliance and deterioration

    An RCD protecting a final circuit does not operate when its integral test button is pressed. This indicates that:

    1. the RCD is defective or requires investigation Correct answer.
    2. the circuit protective conductor is adequately sized
    3. the RCD is a time-delayed type that operates only on earth faults
    4. the test button is only used for a five-times test and the result may be ignored

    Explanation

    The integral test button checks the mechanical and electrical operation of the device. If the RCD fails to trip on the button test it is not functioning correctly and must be investigated and reported.

  79. Question 79Visual inspection of electrical installations and identification of non-compliance and deterioration

    A steel wire armoured cable is terminated into a metal enclosure using a plastic gland, and the armour is not otherwise connected. The main defect is that:

    1. the cable is not suitable for use on alternating current circuits
    2. the armour is not connected to the protective conductor Correct answer.
    3. the neutral conductor is incorrectly identified
    4. the cable rating must be de-rated for grouping

    Explanation

    Where the armour of an SWA cable is used as the circuit protective conductor it must be reliably connected at the termination, for example by a suitable gland and banjo. A plastic gland leaves the armour unearthed and the enclosure inadequately protected.

  80. Question 80Visual inspection of electrical installations and identification of non-compliance and deterioration

    Which of the following should be present at a distribution board so that the purpose of each way can be identified?

    1. a copy of the Electricity at Work Regulations 1989
    2. the last minor works certificate issued for the board
    3. the manufacturer's instruction leaflet for the board
    4. a durable chart or notice identifying each circuit Correct answer.

    Explanation

    A durable chart, schedule or notice identifying each circuit must be fixed at or near the distribution board. Its absence is a non-compliance because it prevents safe identification of circuits.

  81. Question 81Visual inspection of electrical installations and identification of non-compliance and deterioration

    A run of single-insulated conductors without an outer sheath is installed on a wall where it is exposed to mechanical damage. This does not comply because:

    1. the insulation resistance of the circuit will be too low
    2. the disconnection time for the circuit cannot be met
    3. the conductors are protected by basic insulation only Correct answer.
    4. the cable cores do not comply with the colour requirements

    Explanation

    Conductors without an outer sheath have only basic insulation, so they are not protected against mechanical damage or contact where they are exposed. The installation must provide protection against external influences appropriate to the location.

  82. Question 82Visual inspection of electrical installations and identification of non-compliance and deterioration

    A metallic water pipe is being used as the circuit protective conductor for a lighting circuit. This is:

    1. permitted, because copper pipework has a low resistance
    2. not permitted, as a water pipe is not a suitable protective conductor Correct answer.
    3. permitted, because the pipe is already bonded to the main earthing terminal
    4. not permitted, because a water pipe is always at earth potential

    Explanation

    Metallic service pipes are not recognised as protective conductors and must not be relied upon as part of the earthing arrangement. The circuit must include its own protective conductor, because pipework can be altered or removed.

  83. Question 83Visual inspection of electrical installations and identification of non-compliance and deterioration

    During inspection, the clamp connecting the earthing conductor to an earth electrode is found to be badly corroded. This is recorded because:

    1. the electrode is likely to be made from an unsuitable material such as galvanised steel
    2. the connection may have a high resistance Correct answer.
    3. the earth electrode resistance will become too low
    4. the depth of the electrode will no longer comply with the requirements

    Explanation

    Corrosion at the clamp or connection raises the resistance of the earthing path, which can impair disconnection and the operation of protective devices. The connection must be cleaned, remade or replaced.

  84. Question 84Visual inspection of electrical installations and identification of non-compliance and deterioration

    An outdoor enclosure in a wet location has a missing lid gasket, so that water can enter. The inspection finding is that:

    1. the circuit is no longer protected against overcurrent
    2. the cables inside must be increased in size
    3. the earth fault loop impedance will be too low
    4. the IP rating of the enclosure is no longer maintained Correct answer.

    Explanation

    Damaged or missing seals allow water to enter, so the degree of protection of the enclosure and its suitability for the location are no longer maintained. The enclosure must be repaired or replaced to restore its IP rating.

  85. Question 85Visual inspection of electrical installations and identification of non-compliance and deterioration

    A PVC-insulated cable is concealed at a depth of 40 mm in a wall, outside the permitted zones, with no earthed metallic covering and no 30 mA RCD protection. The appropriate observation is:

    1. C3, because the depth is less than 50 mm
    2. C1, because the cable is immediately dangerous
    3. no code, because the cable is protected by the plaster
    4. C2, because the cable may be damaged by a nail or screw Correct answer.

    Explanation

    A cable concealed at less than 50 mm outside the permitted zones without earthed metallic covering or 30 mA RCD protection is potentially dangerous because it may be penetrated by fixings, so C2 applies. C1 would require danger to be present at the time of inspection.

  86. Question 86Visual inspection of electrical installations and identification of non-compliance and deterioration

    Where the agreed extent of a periodic inspection covers only part of a large installation, the inspector should:

    1. issue an electrical installation certificate for the whole installation
    2. test every circuit in full regardless of the agreed extent
    3. assume that the parts not inspected comply
    4. record the extent and any limitations in the report Correct answer.

    Explanation

    The person ordering the report agrees the extent with the inspector, and the report must record that extent together with any limitations so that the reader understands what was and was not covered. Compliance of the uninspected parts cannot be assumed.

  87. Question 87Visual inspection of electrical installations and identification of non-compliance and deterioration

    Aluminium conductors at the terminals of an older distribution board are found to be loose and showing signs of creep. The main concern is that:

    1. aluminium conductors are not permitted in any installation
    2. loose aluminium terminations can overheat and cause fire Correct answer.
    3. the problem affects only the neutral, so the circuits can stay in use
    4. aluminium conductors have a lower current rating, so no action is needed

    Explanation

    Aluminium is prone to creep and surface oxidation, so terminations can loosen over time and overheat, presenting a fire risk. Loose terminations of any conductor require urgent attention and appropriate coding.

  88. Question 88Visual inspection of electrical installations and identification of non-compliance and deterioration

    A plastic-cased consumer unit is found in a domestic dwelling. There are no signs of thermal damage. Under BS 7671 a plastic enclosure in this location is:

    1. compliant, because plastic enclosures are permitted anywhere
    2. non-compliant, as the enclosure is not of non-combustible material Correct answer.
    3. compliant, provided the unit is mounted at least 1 m above floor level
    4. non-compliant, because consumer units must be metal-clad in all premises

    Explanation

    In domestic premises, consumer units and similar switchgear assemblies must have an enclosure of non-combustible material or be enclosed in a non-combustible cabinet. Where a plastic unit is found with no evidence of thermal damage it is normally recorded as a departure, typically C3.

  89. Question 89Visual inspection of electrical installations and identification of non-compliance and deterioration

    A 32 A ring final circuit in a dwelling supplies an unfused spur that feeds two double socket outlets, wired in 2.5 mm². What is the correct finding?

    1. record it as C1, because the sockets are immediately dangerous
    2. accept it, because the 32 A device protects the spur cable
    3. an unfused spur may supply only one socket outlet Correct answer.
    4. accept it, because the spur is wired in 2.5 mm² cable

    Explanation

    An unfused spur from a ring final circuit should supply only one socket outlet or one fused connection unit, so that the spur cable cannot be overloaded. Supplying two double sockets exceeds this arrangement and is potentially dangerous.

  90. Question 90Visual inspection of electrical installations and identification of non-compliance and deterioration

    During a visual inspection, a green-and-yellow insulated single-core conductor is found being used as a line conductor in a lighting circuit, with no other marking applied at its ends. Why is this a non-compliance?

    1. Single-core cables may not be used in lighting circuits unless they are installed in conduit
    2. Green-and-yellow is reserved for protective conductors only Correct answer.
    3. Green-and-yellow insulation has a lower temperature rating than line conductor insulation
    4. A line conductor must be brown throughout its length, so no other colour is permitted

    Explanation

    BS 7671 requires protective conductors to be identified by the green-and-yellow combination, and that combination must not be used to identify any other conductor. Where a single-core conductor is used as a line conductor it must be marked with the appropriate line colour at its terminations. Using an unmarked green-and-yellow core as a line conductor leaves the installation ambiguous and is a non-compliance to be recorded.

  91. Question 91Visual inspection of electrical installations and identification of non-compliance and deterioration

    A 13 A socket outlet in a dwelling is found to have a broken shutter, so that the line contact can be reached through the aperture with a thin object. Why is this recorded as a non-compliance?

    1. Socket outlets for use by ordinary persons must be shuttered Correct answer.
    2. Only metal-cased socket outlets are permitted to be installed in a dwelling
    3. Shutters are required only for socket outlets installed in bathrooms
    4. Any accessory showing signs of wear must be replaced regardless of its condition

    Explanation

    BS 7671 requires socket outlets intended for use by ordinary persons to be of the shuttered type, so that contact with live parts is prevented without the use of a tool. A broken shutter defeats that protection and leaves live metal accessible. The finding is a non-compliance and, because danger is present, would normally be given the most serious classification.

  92. Question 92Visual inspection of electrical installations and identification of non-compliance and deterioration

    A PVC-sheathed twin and earth cable in a loft is found lying directly on expanded polystyrene insulation boards. What is the main concern with this finding?

    1. Polystyrene releases a gas that corrodes the copper conductors of the cable
    2. The polystyrene will increase the current-carrying capacity of the cable, so the circuit is unsafe
    3. The insulation resistance of the cable will fall to zero wherever contact occurs
    4. The sheath may soften and deform because PVC and polystyrene are incompatible Correct answer.

    Explanation

    PVC in contact with expanded polystyrene suffers plasticiser migration, which softens and deforms the sheath and can impair its mechanical and insulating properties. BS 7671 requires cables to be selected and installed so that they are not in contact with materials liable to cause deterioration. A suitable barrier, or rerouting of the cable, is needed to restore compliance.

  93. Question 93Visual inspection of electrical installations and identification of non-compliance and deterioration

    During an inspection of a dwelling, a 13 A socket outlet is found on a bathroom wall 2.5 m from the boundary of zone 1, protected by a 30 mA RCD. What is the correct finding?

    1. Satisfactory, because the socket outlet is located outside zones 1 and 2
    2. Non-compliant: socket outlets must be at least 3 m from zone 1 Correct answer.
    3. Satisfactory, because the socket outlet is protected by a 30 mA RCD
    4. Non-compliant, because socket outlets are not permitted in a bathroom at all

    Explanation

    BS 7671 requires socket outlets in a bathroom to be located at least 3 m from the boundary of zone 1, the only exception being shaver supply units to the relevant product standard. RCD protection does not remove that distance requirement. At 2.5 m the socket outlet is therefore non-compliant and must be recorded.

  94. Question 94Visual inspection of electrical installations and identification of non-compliance and deterioration

    A group of PVC-insulated single-core conductors passes through an unprotected hole in a metal enclosure. At the hole the insulation is flattened and has a polished, thinned appearance, although no copper is visible. What is the most appropriate interpretation?

    1. The polished appearance is normal for PVC and no action is required
    2. The insulation has been abraded and may fail, so the entry needs protection Correct answer.
    3. The flattening shows the cables were over-bent, so only the bend radius is a problem
    4. The conductors have been overheated and the circuit must be derated

    Explanation

    A flattened, polished mark where a cable passes through metal is characteristic of chafing against a sharp edge, which progressively thins the insulation. BS 7671 requires cable entries through metalwork to be protected, for example by a grommet or bushing, so that the conductors are not damaged. The affected length should be assessed for repair or replacement as well as having the entry protected.

  95. Question 95Differences between initial verification and periodic inspection, and agreeing the scope of the report

    What is the main purpose of initial verification of a new electrical installation?

    1. To establish the interval that should be left before future periodic inspections
    2. To provide an energy efficiency rating for the whole building
    3. To record any deterioration that has occurred during service
    4. To confirm the installation complies with BS 7671 before use Correct answer.

    Explanation

    Initial verification is carried out on new work before the installation is energised and handed over, confirming that the design, construction and testing comply with BS 7671. In-service deterioration and condition are assessed later by periodic inspection.

  96. Question 96Differences between initial verification and periodic inspection, and agreeing the scope of the report

    For a periodic inspection, the extent of the inspection and any limitations should be agreed with:

    1. the manufacturer of the test instruments that will be used
    2. the person responsible for the installation or their representative Correct answer.
    3. the distribution network operator that supplies the premises
    4. the local building control body with responsibility for the area

    Explanation

    The scope of a periodic inspection is agreed between the contractor and the duty holder (the person responsible for the installation) or someone authorised to act for them, since they control access and know how the installation is used. Other bodies have no role in settling the extent of an EICR.

  97. Question 97Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Which document is produced after a periodic inspection of an existing installation?

    1. Building Regulations completion certificate
    2. Electrical Installation Condition Report Correct answer.
    3. Electrical Installation Certificate
    4. Minor Electrical Installation Works Certificate

    Explanation

    A periodic inspection results in an Electrical Installation Condition Report, which records the condition of the installation, the extent covered, any limitations and observations. Certificates such as the EIC and MEIWC are used to certify new work.

  98. Question 98Differences between initial verification and periodic inspection, and agreeing the scope of the report

    When carrying out initial verification of a new installation, the inspection and testing should cover:

    1. the whole installation, with all circuits tested Correct answer.
    2. a representative sample of circuits, as agreed with the client
    3. only the circuits supplying socket-outlets and lighting accessories
    4. at least 10 per cent of the circuits, selected at random by the inspector

    Explanation

    Initial verification is a complete process: every circuit of the new work must be inspected and tested, because the certificate declares the whole installation complies. Sampling is a technique associated with periodic inspection of large existing installations.

  99. Question 99Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Periodic inspection is primarily carried out to:

    1. certify that recently completed new work complies with BS 7671
    2. establish whether the installation remains satisfactory for continued use Correct answer.
    3. verify that the original design met BS 7671 at the time of construction
    4. confirm that the installation meets current energy efficiency standards

    Explanation

    A periodic inspection assesses the condition of an existing installation against the requirements of BS 7671, taking account of wear, deterioration, damage and changes in use. It identifies whether the installation is satisfactory for continued service.

  100. Question 100Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Which statement best describes the nature of an Electrical Installation Condition Report?

    1. It is a guarantee that the installation will remain safe until the next inspection
    2. It is a certificate issued by a regulator confirming legal compliance
    3. It transfers responsibility for the installation from the client to the inspector
    4. It is a report on the condition of the installation at the time of inspection Correct answer.

    Explanation

    An EICR records the condition of the installation and the observations found on the day of the inspection, together with the extent and limitations. It is not a regulator's certificate, it carries no guarantee of future safety and it does not transfer responsibility for the installation.

  101. Question 101Differences between initial verification and periodic inspection, and agreeing the scope of the report

    The interval recommended between periodic inspections is determined mainly by:

    1. the number of circuits in the installation
    2. the length of the longest final circuit
    3. the replacement value of the building
    4. the type of installation, its use and the conditions of use Correct answer.

    Explanation

    The recommended interval reflects the type of installation, the use to which it is put, the environment, the likelihood of damage and the standard of maintenance. Guidance tables give typical maximum intervals for different premises and conditions.

  102. Question 102Differences between initial verification and periodic inspection, and agreeing the scope of the report

    A client asks for a periodic inspection of the installation supplied from the main switchboard only, excluding the sub-mains and final circuits. What should the inspector do?

    1. Report the whole installation as satisfactory based on the main switchboard
    2. Refuse the work because an EICR must cover the whole installation
    3. Agree and record the limitation, then inspect the agreed extent Correct answer.
    4. Inspect the whole installation anyway, since safety overrides the client

    Explanation

    A periodic inspection may cover part of an installation provided the extent is agreed and clearly recorded, so that readers understand the assessment applies only to that part. The report then reflects the restricted scope honestly.

  103. Question 103Differences between initial verification and periodic inspection, and agreeing the scope of the report

    In general, a periodic inspection should be:

    1. restricted to visual inspection, with no electrical testing at all
    2. fully intrusive, with every accessory removed for inspection and testing
    3. carried out only with the whole installation isolated for the duration
    4. non-intrusive, with dismantling limited to what is necessary and agreed Correct answer.

    Explanation

    Periodic inspection is intended to establish condition with minimal disturbance to the installation and its users. Some dismantling and testing may be needed, but this should be limited to what is necessary and within the agreed extent.

  104. Question 104Differences between initial verification and periodic inspection, and agreeing the scope of the report

    What is the appropriate use of previous EICRs and records when carrying out a periodic inspection?

    1. They should be ignored, as only current conditions matter
    2. Their observations should be copied across without re-checking
    3. They should be withdrawn once the new report has been issued
    4. They should be reviewed and relevant details recorded in the new report Correct answer.

    Explanation

    Previous reports and records provide useful history, such as the date of the last inspection and earlier defects, and relevant details should be carried into the new report. Observations must still be verified afresh rather than copied.

  105. Question 105Differences between initial verification and periodic inspection, and agreeing the scope of the report

    During a periodic inspection an existing departure from BS 7671 is found that is not, in the inspector's judgement, dangerous. How should it be dealt with?

    1. It should be recorded as an observation in the report Correct answer.
    2. An Electrical Installation Certificate should be issued for the departure
    3. The installation must be reported unsatisfactory regardless of risk
    4. It should be ignored, because BS 7671 applies only to new work

    Explanation

    A departure found during a periodic inspection is recorded so the reader is aware of it, and it is classified according to the risk it presents. It does not automatically make the installation unsatisfactory.

  106. Question 106Differences between initial verification and periodic inspection, and agreeing the scope of the report

    What does the overall assessment on an EICR indicate?

    1. That the client must appoint the inspecting contractor to carry out remedial work
    2. Whether the installation is satisfactory or unsatisfactory for continued use Correct answer.
    3. The number of years the installation can be used without further inspection
    4. Whether the installation complies with the current edition of BS 7671 in every respect

    Explanation

    The overall assessment states whether, in the inspector's opinion, the installation is satisfactory or unsatisfactory for continued use, based on the observations and their classifications. It does not certify full compliance with the current edition.

  107. Question 107Differences between initial verification and periodic inspection, and agreeing the scope of the report

    How does the schedule of inspections in an EICR differ from that in an EIC?

    1. It is replaced by the schedule of test results in the report
    2. It is not required for a periodic inspection of an existing installation
    3. It records only the items actually inspected within the agreed extent Correct answer.
    4. It must list every item as inspected regardless of the extent agreed

    Explanation

    In a periodic inspection the schedule reflects what was actually examined within the agreed extent and limitations. In an EIC it records that the complete new work has been inspected.

  108. Question 108Differences between initial verification and periodic inspection, and agreeing the scope of the report

    New circuits installed in an existing building are to be covered at the same time as a periodic inspection of the existing installation. How should the new work be dealt with?

    1. It should be included in the EICR as part of the existing installation
    2. The EICR should be replaced by an Electrical Installation Certificate for the building
    3. It should be left until the next periodic inspection is due
    4. It should be certified separately with an EIC or MEIWC as appropriate Correct answer.

    Explanation

    New work must be certified for compliance at the time it is completed, using an EIC or, where appropriate, a MEIWC. The EICR reports on the condition of the existing installation and does not certify new work.

  109. Question 109Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Under the private rented sector rules in England, a landlord must have an EICR carried out:

    1. at intervals not exceeding five years, with a copy given to the tenant Correct answer.
    2. only when a tenant raises a complaint about the electrics with the landlord
    3. only when the property is sold or re-mortgaged by the current owner
    4. at least every ten years, or whenever the property changes hands

    Explanation

    The private rented sector regulations require an EICR at intervals not exceeding five years, and a copy must be supplied to the tenant and, on request, to the local authority. The report must be satisfactory or remedial work carried out.

  110. Question 110Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Who normally commissions and is responsible for arranging a periodic inspection?

    1. The distribution network operator for the area
    2. The electrical contractor, as a statutory duty placed on contractors
    3. The local authority, for all commercial premises
    4. The duty holder or person responsible for the installation Correct answer.

    Explanation

    The duty holder, such as the owner or occupier responsible for the installation, commissions the inspection and is responsible for acting on the findings. Contractors and other bodies do not carry that statutory responsibility for the premises.

  111. Question 111Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Why must the extent of the installation covered and any limitations be clearly stated in an EICR?

    1. To list the test instruments used and their calibration dates
    2. To justify the time charged for the inspection and any travel
    3. So that the reader knows what the overall assessment does and does not cover Correct answer.
    4. To satisfy the requirements of the electricity supplier for the premises

    Explanation

    The declared extent and limitations define the boundaries of the inspection, so the overall assessment and observations are understood to apply only to what was actually covered. Without this the report could mislead the reader.

  112. Question 112Differences between initial verification and periodic inspection, and agreeing the scope of the report

    During a periodic inspection, access to several flats in a block is not available. What should the inspector do?

    1. Abandon the inspection and refuse to issue any report to the client
    2. Record the inaccessible areas as limitations and reflect them in the extent Correct answer.
    3. Assume the inaccessible parts are satisfactory because nothing was reported
    4. Classify the inaccessible areas as an immediate danger to users

    Explanation

    Items that cannot be inspected must be recorded as limitations, and the stated extent adjusted accordingly, so the reader understands the report does not cover them. No assumption of satisfactory condition can be made.

  113. Question 113Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Which activity forms part of initial verification but not of a periodic inspection?

    1. Verifying that the design of the new work complies with BS 7671 Correct answer.
    2. Confirming the operation of residual current devices
    3. Verifying the polarity of connections at accessories
    4. Confirming the continuity of protective conductors in the circuits

    Explanation

    Initial verification includes verification of the design as well as construction and testing of the new work. Periodic inspection assesses the in-service condition of an existing installation and does not re-verify the original design.

  114. Question 114Differences between initial verification and periodic inspection, and agreeing the scope of the report

    A periodic inspection of a large installation uses a sample of socket-outlets. Several in the sample are found to have damaged circuit protective conductors. What is the most appropriate action?

    1. Extend the sample to establish how widespread the defect is Correct answer.
    2. Reduce the sample size to limit the amount of remedial work identified
    3. Classify the whole installation as immediate danger and stop work
    4. Record the sample results and complete the rest of the inspection as planned

    Explanation

    Sampling must be representative of the installation; where defects are found the sample should be increased to establish the extent of the problem. The findings then inform the observations and the overall assessment.

  115. Question 115Differences between initial verification and periodic inspection, and agreeing the scope of the report

    An office building is to be converted into a restaurant with commercial cooking equipment. What is the correct position regarding periodic inspection?

    1. A change of use has no effect on the need for or scope of an inspection
    2. The installation must be completely rewired before any inspection is carried out
    3. The change of use is a trigger for a periodic inspection of the installation Correct answer.
    4. Only the electricity supplier can require an inspection after a change of use

    Explanation

    Changes of use, changes in load, and changes in the environment are recognised triggers for a periodic inspection, because the existing installation may no longer be suitable for the new conditions. The inspection assesses suitability for continued use in the new circumstances.

  116. Question 116Differences between initial verification and periodic inspection, and agreeing the scope of the report

    Which statement best describes what a periodic inspection verifies?

    1. That all portable appliances used in the building have been tested
    2. That the installation is in a satisfactory condition for continued use Correct answer.
    3. That the original design and construction fully satisfy the requirements of the time
    4. That the installation complies fully with the current edition of BS 7671

    Explanation

    Periodic inspection is a condition assessment: it judges whether the installation remains satisfactory for continued service, allowing for deterioration, damage and changes in use. Full compliance with every requirement of the current edition is not the test applied.

  117. Question 117Differences between initial verification and periodic inspection, and agreeing the scope of the report

    An inspector considers that a particular installation should be inspected more often than the statutory maximum applying to the premises. What should be done?

    1. Record no recommended interval and leave the decision to the client
    2. Record the statutory maximum, because statute overrides engineering judgement
    3. Record the statutory maximum and note that it cannot be varied
    4. Record the shorter interval recommended on the basis of condition and use Correct answer.

    Explanation

    Statutory intervals are maximum periods, not targets. The report should recommend the interval judged appropriate from the condition, use and environment, which may be shorter than the statutory maximum.

  118. Question 118Differences between initial verification and periodic inspection, and agreeing the scope of the report

    During a periodic inspection a dangerous condition giving immediate risk of injury is found within the agreed scope. What action takes priority?

    1. Isolating the entire installation without first informing the duty holder
    2. Informing the duty holder without delay and recommending immediate action Correct answer.
    3. Completing the report first, so that the findings are properly documented
    4. Recording the observation and posting the report to the client in the usual way

    Explanation

    A condition coded as immediate danger requires urgent action: the person responsible must be told without delay and immediate remedial action recommended, which may include isolation. Documentation follows, but it does not take priority over removing the danger.

  119. Question 119Dead testing: continuity, ring final circuit, polarity and insulation resistance

    In the recommended sequence of dead tests on a new installation, which test is carried out first?

    1. Polarity at each socket outlet
    2. Insulation resistance of each final circuit
    3. Continuity of ring final circuit conductors
    4. Continuity of protective conductors and protective bonding Correct answer.

    Explanation

    Dead testing starts with the continuity of protective conductors, including main and supplementary bonding, because every later test and every protective measure depends on a sound earth path.

  120. Question 120Dead testing: continuity, ring final circuit, polarity and insulation resistance

    What is the minimum acceptable insulation resistance for a 230 V single-phase final circuit when tested with a 500 V d.c. tester?

    1. 1 MΩ Correct answer.
    2. 2 MΩ
    3. 0.5 MΩ
    4. 5 MΩ

    Explanation

    For circuits rated up to and including 500 V, the minimum insulation resistance measured at 500 V d.c. is 1 MΩ; lower values are not acceptable regardless of circuit type.

  121. Question 121Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Which test voltage is applied when measuring the insulation resistance of a 400 V three-phase installation?

    1. 2500 V d.c.
    2. 250 V d.c.
    3. 1000 V a.c.
    4. 500 V d.c. Correct answer.

    Explanation

    Circuits operating at voltages up to 500 V are tested at 500 V d.c.; the 250 V setting is reserved for SELV and PELV, and 1000 V or more is used only for higher-voltage systems.

  122. Question 122Dead testing: continuity, ring final circuit, polarity and insulation resistance

    A ring final circuit is wired with 2.5 mm² line and neutral conductors and a 1.5 mm² protective conductor. If the end-to-end line resistance r1 is 0.40 Ω, what is the expected value of r2?

    1. 0.40 Ω
    2. 0.24 Ω
    3. 0.67 Ω Correct answer.
    4. 0.55 Ω

    Explanation

    Resistance is inversely proportional to cross-sectional area, so the 1.5 mm² conductor has 2.5/1.5 times the resistance of the 2.5 mm² conductor: 0.40 × 1.67 = 0.67 Ω.

  123. Question 123Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Which instrument is used to verify the continuity of a circuit protective conductor?

    1. A low-resistance ohmmeter Correct answer.
    2. A loop impedance tester
    3. An insulation resistance tester
    4. An earth electrode resistance tester

    Explanation

    A low-resistance ohmmeter passes a test current of at least 200 mA and gives the milliohm-level resolution needed to prove protective conductor continuity.

  124. Question 124Dead testing: continuity, ring final circuit, polarity and insulation resistance

    With the two ends of a ring final circuit separated at the consumer unit, a resistance reading is taken between the two line conductor ends. What does this reading represent?

    1. The resistance of the complete ring with all ends joined together
    2. The end-to-end resistance of the protective conductor
    3. The end-to-end resistance of the line conductor Correct answer.
    4. The combined resistance of the line and neutral conductors

    Explanation

    With the ends separated, an ohmmeter placed across the two line ends measures the line conductor taken all the way around the ring, recorded as r1.

  125. Question 125Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Which terminal of an Edison screw (ES) lampholder must be connected to the line conductor?

    1. The centre contact Correct answer.
    2. The metal body of the luminaire
    3. The outer screw thread
    4. Either terminal, provided the switch is single-pole

    Explanation

    Correct polarity requires the centre contact to be the line terminal so that the outer screw thread, which is easier to touch when changing a lamp, remains at neutral potential.

  126. Question 126Dead testing: continuity, ring final circuit, polarity and insulation resistance

    What test voltage and minimum insulation resistance apply to a SELV circuit?

    1. 500 V d.c. and 1 MΩ
    2. 500 V d.c. and 0.5 MΩ
    3. 250 V d.c. and 1 MΩ
    4. 250 V d.c. and 0.5 MΩ Correct answer.

    Explanation

    SELV and PELV circuits are tested at 250 V d.c. with a minimum acceptable insulation resistance of 0.5 MΩ, because the lower operating voltage permits a reduced test level.

  127. Question 127Dead testing: continuity, ring final circuit, polarity and insulation resistance

    End-to-end readings on a ring final circuit give r1 = 0.40 Ω and r2 = 0.67 Ω. What value of R1 + R2 is expected at each socket outlet after the ring is cross-connected?

    1. 0.53 Ω
    2. 1.07 Ω
    3. 0.27 Ω Correct answer.
    4. 0.40 Ω

    Explanation

    With line and protective conductors cross-connected, the resistance measured at any socket is approximately one quarter of the sum of the end-to-end readings: (0.40 + 0.67) ÷ 4 = 0.27 Ω.

  128. Question 128Dead testing: continuity, ring final circuit, polarity and insulation resistance

    After the ring final circuit conductors have been cross-connected, what pattern of R1 + R2 readings is expected at the socket outlets?

    1. Lowest at the socket furthest from the consumer unit
    2. Approximately equal at every socket on the ring Correct answer.
    3. Equal to r1 plus r2 at every socket
    4. Highest at the socket nearest the consumer unit

    Explanation

    The cross-connection creates two parallel paths between the test points, so the measured resistance is substantially the same at every socket on a healthy ring regardless of its position.

  129. Question 129Dead testing: continuity, ring final circuit, polarity and insulation resistance

    What is the purpose of the figure-of-eight test on a ring final circuit?

    1. To measure the earth fault loop impedance of the ring
    2. To locate a break in the ring conductors Correct answer.
    3. To check the polarity of each socket outlet
    4. To confirm the insulation resistance of the ring

    Explanation

    Linking one line end to the opposite protective conductor end splits the ring into two loops whose resistances change as the test point passes the break, allowing the fault position to be located.

  130. Question 130Dead testing: continuity, ring final circuit, polarity and insulation resistance

    A lighting circuit contains a dimmer module and electronic transformers. What should be done before an insulation resistance test?

    1. Test with the dimmer set to maximum brightness
    2. Carry out the test at 250 V d.c. instead
    3. Disconnect the equipment before testing Correct answer.
    4. Record the result and note it as a limitation

    Explanation

    Electronic devices can be damaged by the 500 V test voltage and can also drag the reading down, so they are removed or isolated, with the omission recorded as a limitation of the test.

  131. Question 131Dead testing: continuity, ring final circuit, polarity and insulation resistance

    An insulation resistance test on a domestic lighting circuit gives 0.5 MΩ at 500 V d.c. What is the correct course of action?

    1. Re-test at 250 V d.c. and record the higher of the two results
    2. Record the result as satisfactory because it exceeds 0.5 MΩ
    3. Energise the circuit and confirm with a live loop test
    4. Investigate and rectify the cause before energising the circuit Correct answer.

    Explanation

    The minimum acceptable value for a 230 V circuit is 1 MΩ, so a reading of 0.5 MΩ is a failure that must be traced and corrected before the circuit is put into service.

  132. Question 132Dead testing: continuity, ring final circuit, polarity and insulation resistance

    When the continuity of a main protective bonding conductor is checked with a wander lead, the instrument is connected between the main earthing terminal and:

    1. the earth electrode serving the installation
    2. the far end of the bonding conductor at the extraneous part Correct answer.
    3. the line conductor at the origin of the installation
    4. two adjacent points on the equipotential bonding bar

    Explanation

    The wander lead provides one long test path so the ohmmeter can measure the whole bonding conductor from the main earthing terminal to its clamp on the extraneous-conductive-part.

  133. Question 133Dead testing: continuity, ring final circuit, polarity and insulation resistance

    How is the polarity of a socket outlet verified during dead testing?

    1. By carrying out a loop impedance test at the socket
    2. By a continuity test from the origin to the socket terminals Correct answer.
    3. By visual inspection of the conductor colours only
    4. By measuring insulation resistance between line and neutral

    Explanation

    Dead polarity testing uses a low-resistance ohmmeter to confirm that the line conductor at the origin is continuous with the line terminal of the socket and that the neutral goes to the neutral terminal.

  134. Question 134Dead testing: continuity, ring final circuit, polarity and insulation resistance

    What must be done to the test leads of a low-resistance ohmmeter before measuring the resistance of a protective conductor?

    1. They must be at least 10 m in length
    2. Their resistance must be nulled out Correct answer.
    3. They must be tested at 500 V d.c.
    4. They must be disconnected from the instrument

    Explanation

    The resistance of the leads is significant when readings are in the order of tenths of an ohm, so the instrument is zeroed with the leads joined, or the lead resistance is deducted from each result.

  135. Question 135Dead testing: continuity, ring final circuit, polarity and insulation resistance

    For a global insulation resistance test on a single-phase installation, how is the test instrument connected?

    1. Between line and neutral joined together, and earth Correct answer.
    2. Between the neutral conductor and the main earthing terminal only
    3. Between the line conductor and the main earthing terminal only
    4. Between the line conductor and the neutral conductor only

    Explanation

    The global test links line and neutral so that all live conductors are tested together against the earthed enclosure and protective conductors in a single measurement.

  136. Question 136Dead testing: continuity, ring final circuit, polarity and insulation resistance

    What is the minimum test current that should be used when verifying the continuity of a protective conductor?

    1. 20 mA
    2. 2 A
    3. 20 A
    4. 200 mA Correct answer.

    Explanation

    A low-resistance ohmmeter must deliver a test current of at least 200 mA from a low-voltage source so that a poor joint is revealed rather than being bridged by a low-current measurement.

  137. Question 137Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Why should the polarity of the incoming supply at the origin be confirmed before dead testing begins?

    1. To verify that the neutral is isolated from earth at the origin
    2. To check that the main switch is of the double-pole type
    3. To obtain the value of the external earth fault loop impedance
    4. To ensure the incoming line and neutral are correctly identified Correct answer.

    Explanation

    If the incoming line and neutral are transposed, every downstream polarity check and every single-pole device would be based on a false assumption, so the supply polarity is proved first.

  138. Question 138Dead testing: continuity, ring final circuit, polarity and insulation resistance

    On a ring final circuit the measured r1 and rn values should be approximately equal. A substantially higher rn value indicates:

    1. that the neutral is deliberately smaller in area
    2. a poor connection in the neutral conductor Correct answer.
    3. a short circuit between line and neutral
    4. an open circuit in the protective conductor

    Explanation

    Line and neutral of a ring are the same conductor size and follow the same route, so a higher end-to-end reading on the neutral points to a loose terminal or damaged neutral.

  139. Question 139Dead testing: continuity, ring final circuit, polarity and insulation resistance

    On a ring final circuit, r1 is 0.50 Ω and r2 is 0.83 Ω, but every socket gives about 0.15 Ω in the cross-connection test instead of the expected 0.33 Ω. What is the most likely reason?

    1. The ring has an open circuit in the line conductor
    2. Parallel earth paths are reducing the reading Correct answer.
    3. The neutral has a larger cross-section than the line
    4. The test leads have not been nulled correctly

    Explanation

    Readings lower than the calculated value indicate that the protective conductor is being shunted by an alternative earth return, such as metal conduit, trunking or supplementary bonding, so the measured value is not the true R1 + R2 of the circuit.

  140. Question 140Dead testing: continuity, ring final circuit, polarity and insulation resistance

    A global insulation resistance test gives 3 MΩ, but an individual lighting circuit gives only 0.6 MΩ while all other circuits exceed 100 MΩ. How should this be interpreted?

    1. The result is acceptable because lighting needs only 0.5 MΩ
    2. The global test should be repeated at 250 V d.c. to confirm
    3. The installation is satisfactory because the global result exceeds 1 MΩ
    4. The lighting circuit fails to meet the 1 MΩ minimum Correct answer.

    Explanation

    Each circuit must achieve at least 1 MΩ in its own right; a global reading is a parallel combination and can look healthy while one circuit is defective, so the low circuit must be investigated.

  141. Question 141Dead testing: continuity, ring final circuit, polarity and insulation resistance

    A ring final circuit is wired in 4.0 mm² line and neutral with a 1.5 mm² protective conductor. If r1 is 0.24 Ω, what is the expected value of r2?

    1. 0.09 Ω
    2. 0.96 Ω
    3. 0.64 Ω Correct answer.
    4. 0.36 Ω

    Explanation

    The resistance ratio follows the inverse of the cross-sectional areas: 4.0 ÷ 1.5 = 2.67, so the expected r2 is 0.24 × 2.67 = 0.64 Ω.

  142. Question 142Dead testing: continuity, ring final circuit, polarity and insulation resistance

    A measured R1 + R2 value is significantly lower than the figure calculated from the cable length and tabulated resistance. What does this suggest?

    1. An earth path exists in parallel with the CPC Correct answer.
    2. The circuit is longer than the recorded route
    3. The protective conductor terminal is loose
    4. The line conductor is open circuit

    Explanation

    A parallel earth path, such as metal conduit, trunking or supplementary bonding connected to the circuit, reduces the measured resistance below the value expected from the protective conductor alone.

  143. Question 143Dead testing: continuity, ring final circuit, polarity and insulation resistance

    An insulation resistance test on a distribution board containing a surge protective device gives an unexpectedly low reading. What is the correct action?

    1. Test line to neutral only and record it
    2. Disconnect the device and repeat the test Correct answer.
    3. Reduce the test voltage to 250 V d.c.
    4. Record the low reading as a limitation

    Explanation

    Surge protective devices and similar electronics present a low impedance to the test voltage and can be damaged by it, so they are disconnected and the test repeated on the remainder of the installation.

  144. Question 144Dead testing: continuity, ring final circuit, polarity and insulation resistance

    For a 230 V final circuit tested at 500 V d.c., what is the minimum acceptable insulation resistance?

    1. 1.0 MΩ Correct answer.
    2. 0.5 MΩ
    3. 0.25 MΩ
    4. 2.0 MΩ

    Explanation

    BS 7671 requires a minimum insulation resistance of 1 MΩ for circuits rated up to 500 V when tested at 500 V d.c. with loads and sensitive equipment disconnected. Any reading below this value must be investigated before the circuit is put back into service.

  145. Question 145Dead testing: continuity, ring final circuit, polarity and insulation resistance

    In a BS 1363 socket outlet, which terminal must the line conductor be connected to when viewed facing the socket?

    1. Either terminal, because polarity is not defined for socket outlets
    2. The left-hand terminal
    3. The right-hand terminal Correct answer.
    4. The earth terminal at the top

    Explanation

    For a BS 1363 socket outlet the line conductor is connected to the right-hand terminal, the neutral to the left-hand terminal and the protective conductor to the top terminal. Correct terminal selection is what allows a plug-top fuse and single-pole switching to operate in the line conductor.

  146. Question 146Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Which procedure correctly measures R1 + R2 for a radial socket-outlet circuit?

    1. Measure between line and neutral at each socket outlet with the circuit energised and the loads connected.
    2. With the circuit isolated and the far end left open, measure between the line and protective conductors at the origin.
    3. Link the line and neutral conductors at the far end, then measure between line and neutral at the origin.
    4. Link the line and protective conductors at the far end, then measure between them at the origin. Correct answer.

    Explanation

    The R1 + R2 method joins the line and protective conductors together at the far end of the circuit so that the instrument at the origin reads the sum of both conductor resistances. The result confirms continuity of the protective conductor and provides the resistance value used for earth fault loop path verification.

  147. Question 147Dead testing: continuity, ring final circuit, polarity and insulation resistance

    Why should the switches of a two-way lighting circuit be operated through each position during an insulation resistance test?

    1. To discharge the capacitance of the strapper conductors between tests.
    2. To ensure every strapper conductor is tested. Correct answer.
    3. To confirm that the switch contacts are not welded together.
    4. To prevent the lamp from being illuminated during the test.

    Explanation

    With two-way and intermediate switching, some strapper conductors are only connected through to the line side of the test when the switches are in particular positions. Operating the switches through each position during the insulation resistance test ensures every strapper is stressed at the test voltage and included in the measured result.

  148. Question 148Dead testing: continuity, ring final circuit, polarity and insulation resistance

    During the cross-connected stage of a ring final circuit test, readings at socket outlets are not all identical. Which socket is expected to give the highest R1 + R2 reading?

    1. The socket nearest the consumer unit.
    2. Every socket on the ring should give an identical reading.
    3. The socket at the electrical midpoint of the ring. Correct answer.
    4. The last socket to be tested on the ring.

    Explanation

    With the line and protective conductors cross-connected at the origin, the test current divides between the two legs of the ring and the measured resistance rises from almost zero near the origin to a maximum where the two paths are equal. That point is the electrical midpoint of the ring, where the reading is approximately (r1 + r2)/4.

  149. Question 149Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    What is the main purpose of measuring earth fault loop impedance on a final circuit?

    1. To establish the current-carrying capacity of the cable
    2. To confirm the insulation resistance is satisfactory
    3. To prove the polarity of the socket outlets
    4. To confirm disconnection within the required time Correct answer.

    Explanation

    Earth fault loop impedance limits the current that can flow during an earth fault, and the measured value must be low enough for the protective device to operate within the disconnection time required by BS 7671. It is not a substitute for any other test.

  150. Question 150Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    When a 30 mA RCD is tested at five times its rated residual operating current, what test current is applied?

    1. 150 mA Correct answer.
    2. 30 mA
    3. 300 mA
    4. 500 mA

    Explanation

    The 5 times test applies five times the rated residual operating current, so 5 × 30 mA = 150 mA. This check confirms fast operation at a current well above the residual operating current.

  151. Question 151Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    What does the integral test button on an RCD allow the user to check?

    1. The residual operating current of the device
    2. The mechanical operation of the device Correct answer.
    3. The operating time of the device
    4. The resistance of the installation earth electrode

    Explanation

    The test button passes a simulated imbalance through the device to confirm that its mechanism operates and the contacts open. It gives no measured result and is not a substitute for instrument testing.

  152. Question 152Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Where is the prospective fault current of an installation normally measured?

    1. At the furthest socket outlet of each final circuit
    2. At the terminals of each item of equipment
    3. At the mid-point of every ring final circuit
    4. At the origin of the installation Correct answer.

    Explanation

    Prospective fault current is at its highest at the origin of the installation, so this is where it is measured and recorded. The value is then used to confirm the short-circuit ratings of the equipment installed there.

  153. Question 153Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Test leads used for live testing must comply with GS38. Which of the following meets that requirement?

    1. Probes with 50 mm of exposed metal
    2. Leads of unrestricted length with no fuse
    3. Fused shrouded probes with short tips Correct answer.
    4. Unfused probes with long exposed tips

    Explanation

    GS38 requires test leads to be fused, to have finger barriers or shrouds, and to have only a short length of metal exposed at the tip. This reduces the risk of short circuits and electric shock during live testing.

  154. Question 154Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    An RCD should remain closed when it is tested at which multiple of its rated residual operating current?

    1. 1 × IΔn
    2. 2 × IΔn
    3. 0.5 × IΔn Correct answer.
    4. 5 × IΔn

    Explanation

    At half the rated residual operating current the device must not trip, which confirms it is not over-sensitive. Tripping at this level indicates a defective or unsuitable device.

  155. Question 155Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Operating the main switch and several circuit breakers by hand during an inspection is an example of:

    1. a continuity test
    2. a polarity test
    3. an insulation resistance test
    4. a functional test Correct answer.

    Explanation

    Functional testing confirms that equipment such as switches, isolators and protective devices operates correctly when operated. It is carried out in addition to the instrument-based tests.

  156. Question 156Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    For a 230 V final circuit rated at 32 A in a TN system, what is the maximum permitted disconnection time?

    1. 1 s
    2. 0.1 s
    3. 0.4 s Correct answer.
    4. 5 s

    Explanation

    BS 7671 requires a disconnection time of 0.4 s for final circuits not exceeding 32 A in TN systems. Distribution circuits are permitted 5 s.

  157. Question 157Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    The tabulated maximum earth fault loop impedance for a circuit is 1.1 Ω. Applying the rule of thumb, what is the highest measured value that would normally be accepted?

    1. 1.10 Ω
    2. 0.88 Ω Correct answer.
    3. 1.38 Ω
    4. 1.32 Ω

    Explanation

    The rule of thumb multiplies the tabulated value by 0.8 to allow for conductors being at their operating temperature, giving 1.1 × 0.8 = 0.88 Ω. A measured value at or below this confirms compliance.

  158. Question 158Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    What is the maximum operating time for a general (non-delayed) RCD tested at 1 × IΔn?

    1. 500 ms
    2. 300 ms Correct answer.
    3. 40 ms
    4. 1000 ms

    Explanation

    BS EN 61008 and BS EN 61009 require a general RCD to operate within 300 ms at its rated residual operating current. The 40 ms limit applies to the 5 times IΔn test.

  159. Question 159Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    What is the maximum operating time for a general (non-delayed) RCD tested at 5 × IΔn?

    1. 150 ms
    2. 40 ms Correct answer.
    3. 500 ms
    4. 300 ms

    Explanation

    At five times the rated residual operating current a general RCD must operate within 40 ms. This confirms rapid operation at fault current levels.

  160. Question 160Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    The prospective fault current at the origin of an installation is measured so that the installer can confirm:

    1. the rated residual current of the RCD
    2. the earth electrode resistance
    3. the short-circuit rating of the equipment Correct answer.
    4. the size of the protective conductor

    Explanation

    Equipment at the origin, such as the main switch and protective devices, must have a short-circuit breaking or conditional rating at least equal to the prospective fault current. The other items are established by different calculations or tests.

  161. Question 161Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Which of the following is good practice immediately before an RCD is tested in a live installation?

    1. Switching off and removing the loads Correct answer.
    2. Applying 10 × IΔn to reduce test time
    3. Disconnecting the main earthing conductor
    4. Linking out the RCD to protect it

    Explanation

    Loads should be switched off or removed before testing so that they are not disturbed by the interruption of supply, and so that their leakage current does not influence the result. The RCD must remain in circuit and the earthing must stay connected.

  162. Question 162Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    An RCD tester is used at both 0° and 180°. Why is this done?

    1. To check operation on both half-cycles Correct answer.
    2. Because the RCD only operates on one half-cycle
    3. Because the test leads must be reversed between tests
    4. To double the applied test current

    Explanation

    The two tests apply the residual current at opposite points on the alternating waveform. The longer of the two measured times is then compared with the standard limit.

  163. Question 163Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Why is a low test current sometimes selected on a loop impedance tester?

    1. It measures only the external loop impedance
    2. It avoids tripping an RCD in the circuit Correct answer.
    3. It always gives a more accurate result
    4. It removes the need for a neutral connection

    Explanation

    A low-current, no-trip loop test is used on circuits protected by an RCD so that the test current does not operate the device and interrupt the supply. The high-current test can trip the RCD.

  164. Question 164Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    Which of the following would most likely make a measured earth fault loop impedance lower than the true value of the circuit's own loop?

    1. A loose test lead connection
    2. Testing at the far end of a long circuit
    3. A break in the protective conductor
    4. Parallel paths through bonded metalwork Correct answer.

    Explanation

    Bonding to other metallic services creates parallel return paths, so some of the test current bypasses the circuit protective conductor and the indicated impedance is lower. This can give a false pass if it is not recognised.

  165. Question 165Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    The external earth fault loop impedance (Ze) of a TN-S installation is measured with the main switch off. Which connection arrangement is correct?

    1. Between the earthing terminal and a temporary earth rod
    2. Between line and neutral with all final circuits left connected
    3. Between incoming line and incoming neutral with the main earth connected
    4. Between line and the disconnected main earthing conductor Correct answer.

    Explanation

    For Ze only the external supply loop must be measured, so the main earthing conductor is disconnected from the earthing terminal and the tester is connected between the incoming line and that conductor with the main switch off. This excludes the installation's own earth path.

  166. Question 166Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    What is the maximum permitted disconnection time for a 400 V distribution circuit in a TN system?

    1. 0.2 s
    2. 0.4 s
    3. 0.1 s
    4. 5 s Correct answer.

    Explanation

    BS 7671 allows 5 s for distribution circuits in TN systems, because the risk is reduced compared with a final circuit supplying portable equipment. The 0.4 s limit applies to final circuits not exceeding 32 A.

  167. Question 167Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    A 30 mA RCD trips in 45 ms at 0° and 280 ms at 180° when tested at 1 × IΔn. What is the correct interpretation?

    1. It passes because one test is below 300 ms
    2. It fails because the 0° result is too fast
    3. It fails because the average of the two times exceeds 40 ms
    4. It passes because the longer time is within 300 ms Correct answer.

    Explanation

    The longer of the two measured times is compared with the 300 ms limit for a general RCD at 1 times IΔn. 280 ms is within that limit, so the device complies.

  168. Question 168Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    An RCD tester is connected to a socket outlet to test the 30 mA RCD protecting the circuit. Which connections must the tester make?

    1. Neutral and protective earth only
    2. Line and neutral only
    3. Line and protective earth only
    4. Line, neutral and protective earth Correct answer.

    Explanation

    An RCD tester uses all three conductors: it draws current between line and protective earth to create the residual current while the neutral provides the supply reference. Without the earth connection no test current can flow.

  169. Question 169Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    The 0.8 factor commonly used when comparing measured Zs with tabulated values allows for:

    1. the rise in resistance of hot conductors Correct answer.
    2. the effect of parallel earth return paths
    3. the accuracy tolerance of the test instrument
    4. the reduction in supply voltage during a fault

    Explanation

    Tabulated values are based on conductors at 20 °C, but during a fault the conductors are near their operating temperature and have a higher resistance. Multiplying by 0.8 gives a measured value that will still comply when the conductors are hot.

  170. Question 170Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    In which situation is a Type B RCD required?

    1. Where the circuit is a three-phase motor circuit
    2. Where the circuit supplies fluorescent luminaires
    3. Where the RCD is used as a main isolator
    4. Where a smooth d.c. residual current may occur Correct answer.

    Explanation

    Type B devices respond to smooth d.c. residual currents as well as alternating ones, and are needed for equipment such as certain variable-speed drives and chargers. Type AC and Type A devices may not detect a smooth d.c. component.

  171. Question 171Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    A TT installation is protected by a 30 mA RCD. What is the maximum earth electrode resistance permitted by BS 7671?

    1. 1667 Ω Correct answer.
    2. 100 Ω
    3. 500 Ω
    4. 200 Ω

    Explanation

    For a TT system the resistance of the earth electrode and protective conductor must not exceed 50 divided by IΔn, so 50 ÷ 0.03 = 1667 Ω. This keeps the touch voltage during a fault to 50 V or less.

  172. Question 172Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    For a three-phase installation, which measured value is recorded as the prospective fault current?

    1. The highest line-line or line-neutral value Correct answer.
    2. The sum of the three line-neutral values
    3. The average of the three line-line values
    4. The line-neutral value of a single phase

    Explanation

    The highest prospective current that could flow, whether from a line-to-line or a line-to-neutral fault, is the value that the equipment must withstand. Averaging or using a single phase would understate the duty on the equipment.

  173. Question 173Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    A measured Zs on a final circuit is higher than the maximum permitted value. What is the most appropriate action?

    1. Reduce the test current of the loop tester and repeat the test
    2. Record the value and take no further action
    3. Investigate for poor connections and conductor size Correct answer.
    4. Increase the rating of the protective device to speed disconnection

    Explanation

    The usual causes are a loose connection, an undersized or damaged protective conductor, or an unexpectedly long circuit, and these must be investigated and corrected. Changing the device rating is not appropriate because the device is selected for the load and cable, and a lower test current does not change the true impedance.

  174. Question 174Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

    During a periodic inspection, the inspector presses the integral test button on a 30 mA RCD and the device trips. What does this result establish?

    1. It confirms the device trips within 300 ms at rated current.
    2. It proves the device is the correct type for the loads.
    3. It confirms the mechanism works but not the operating time. Correct answer.
    4. It verifies the earth fault loop impedance of the circuit.

    Explanation

    The integral test button passes a current through an internal resistor that simulates a residual current, so it demonstrates that the sensing and tripping mechanism functions. It does not measure the disconnection time, and because the test current does not flow through the installation's protective conductors it gives no information about earth fault loop impedance. Instrument-based testing at the prescribed multiples of IΔn is therefore still required to confirm compliance.

  175. Question 175Recording results, condition reporting, classification codes and recommendations

    What does classification code C1 indicate on an electrical installation condition report?

    1. Potentially dangerous, with urgent remedial action required
    2. Further investigation required before a classification can be given
    3. Danger present, with immediate action required Correct answer.
    4. Improvement recommended, as the installation does not meet current standards

    Explanation

    C1 is used where an observation shows a danger that is present and creates a risk of injury, so immediate action is needed to remove it. The inspector must also take action at the time, such as isolation, and warn the user.

  176. Question 176Recording results, condition reporting, classification codes and recommendations

    Which description applies to an observation classified as C2?

    1. No action required, but the item should be monitored at the next inspection
    2. Potentially dangerous, with urgent remedial action required Correct answer.
    3. Improvement recommended because the item does not comply with current standards
    4. Danger present, with immediate action required

    Explanation

    C2 is applied where the observation shows a potential danger and remedial work is needed urgently, though the risk is not so immediate as to require action on the spot. The report is unsatisfactory whenever a C2 is recorded.

  177. Question 177Recording results, condition reporting, classification codes and recommendations

    Which description applies to an observation classified as C3?

    1. Further investigation required, as the full extent of the defect is not known
    2. Improvement recommended, as the item does not comply Correct answer.
    3. Danger present, and immediate action is required to remove the risk of injury
    4. Potentially dangerous, and urgent remedial action is required to make it safe

    Explanation

    C3 is used where the item does not comply with BS 7671 but is not considered to present a danger, so improvement is recommended rather than required. A C3 on its own does not make the report unsatisfactory.

  178. Question 178Recording results, condition reporting, classification codes and recommendations

    What does the classification code FI tell the person receiving the report?

    1. Potentially dangerous, requiring urgent remedial action
    2. Improvement recommended, as the item does not comply with current standards
    3. Danger present, requiring immediate action to remove the risk
    4. Further investigation required without delay Correct answer.

    Explanation

    FI is used where the inspector has identified something that may be a defect but cannot establish the full facts without further investigation, which must be carried out without delay. Recording an FI makes the report unsatisfactory.

  179. Question 179Recording results, condition reporting, classification codes and recommendations

    An EICR records three observations, all classified C3, and no other entries. What is the overall condition of the installation?

    1. Unsatisfactory until the C3 items are corrected
    2. Satisfactory Correct answer.
    3. Satisfactory only if the client accepts the C3 items in writing
    4. Unsatisfactory, because any observation makes the report unsatisfactory

    Explanation

    A report is satisfactory where the only observations are coded C3, or where there are no observations at all. C3 means improvement is recommended, not that the installation is unsafe.

  180. Question 180Recording results, condition reporting, classification codes and recommendations

    During an inspection, a broken accessory is found exposing live conductors at a socket outlet in a shop. What must the inspector do first?

    1. Code it C2 and list it for urgent remedial work within 28 days
    2. Record the observation and include it in the report issued a week later
    3. Take immediate action to remove the danger and warn the user Correct answer.
    4. Code it C3 and recommend improvement at the next inspection

    Explanation

    Exposed live parts accessible to touch are a danger present, so they are coded C1. The inspector must take immediate action, such as isolation or another suitable measure, and warn the person responsible.

  181. Question 181Recording results, condition reporting, classification codes and recommendations

    How is each observation in the observations section of an EICR identified?

    1. By the measured test value that shows the defect exists
    2. By the classification code alone, without any other reference
    3. By the date on which the defect was first noticed by the inspector
    4. By an item number that cross-refers to the schedule of inspections Correct answer.

    Explanation

    Each observation carries an item number matching the relevant heading in the schedule of inspections, together with its location and classification code. This lets the reader trace exactly which part of the installation was examined.

  182. Question 182Recording results, condition reporting, classification codes and recommendations

    What should be agreed with the client before a periodic inspection begins?

    1. The extent of the installation to be inspected and any limitations Correct answer.
    2. The date on which the next EICR will be carried out
    3. The classification code to be applied to any observations found
    4. The name of the contractor who will carry out the remedial works

    Explanation

    The extent of the inspection and any agreed limitations must be established with the client and recorded on the report. This protects both parties by making clear what was and was not covered.

  183. Question 183Recording results, condition reporting, classification codes and recommendations

    A socket circuit in a locked tenant's flat cannot be accessed on the day of the inspection. How is this best recorded?

    1. As a limitation, with the circuit marked LIM in the schedule Correct answer.
    2. As a C2 observation, because the circuit has not been inspected
    3. By leaving the circuit out of the schedule of test results entirely
    4. As a C3 observation, because no defect has actually been found

    Explanation

    Where part of the installation cannot be examined, it is recorded as a limitation and the relevant entries are marked LIM rather than being given a classification code. Omitting the circuit entirely would misrepresent the scope of the report.

  184. Question 184Recording results, condition reporting, classification codes and recommendations

    An insulation resistance test on a 230 V circuit gives a reading above the top of the instrument's range. What should be entered in the schedule of test results?

    1. The highest value on the instrument scale, as a measured result
    2. 0.00, because no value was displayed by the instrument
    3. Greater than the instrument's maximum, for example >200 MΩ Correct answer.
    4. NV, because the test could not be completed successfully

    Explanation

    Where the reading exceeds the instrument's range, the result is recorded as a value greater than that range, such as >200 MΩ. Recording the scale maximum as a measurement would state a result the instrument did not actually produce.

  185. Question 185Recording results, condition reporting, classification codes and recommendations

    In what unit are RCD operating times recorded in the schedule of test results?

    1. Cycles at 50 Hz
    2. Milliseconds Correct answer.
    3. Seconds, to two decimal places
    4. Microseconds, to three decimal places

    Explanation

    The schedule of test results provides a column for RCD operating time in milliseconds. This unit suits the short operating times expected at the rated and five-times rated residual operating currents.

  186. Question 186Recording results, condition reporting, classification codes and recommendations

    The measured Zs of a circuit is 1.42 Ω, which exceeds the maximum permitted value for the protective device. How is this recorded?

    1. The measured value is entered as a pass because the circuit trips on fault
    2. The measured 1.42 Ω is entered, with a C2 observation Correct answer.
    3. The maximum permitted value is entered, with a note of the measurement
    4. The value is not entered, since the circuit is non-compliant

    Explanation

    The schedule of test results must record the actual measured value, and the failure to meet the maximum permitted earth fault loop impedance is then reported as an observation. An excessive Zs can prevent the protective device disconnecting within the required time, so it is coded C2.

  187. Question 187Recording results, condition reporting, classification codes and recommendations

    What is recorded for polarity in the schedule of test results?

    1. The length of each final circuit measured in metres
    2. Confirmation that polarity was correct at each point tested Correct answer.
    3. The resistance of the line conductor measured in ohms
    4. The date on which the polarity was last checked by the DNO

    Explanation

    Polarity is confirmed as correct at the points tested, including accessories, distribution boards and the supply intake. The schedule records the confirmation rather than a numeric measurement.

  188. Question 188Recording results, condition reporting, classification codes and recommendations

    Under the older coding system, code 4 meant that an item did not comply with BS 7671. Which current code covers this situation?

    1. C2
    2. FI
    3. C3 Correct answer.
    4. C1

    Explanation

    The old code 4 has been replaced by C3, which is used where the item does not comply with the current standard but is not considered dangerous. C3 means improvement is recommended.

  189. Question 189Recording results, condition reporting, classification codes and recommendations

    How is the date for the next inspection and test decided?

    1. It reflects the installation's use, condition and previous records Correct answer.
    2. It is fixed at 10 years for every installation, regardless of condition
    3. It is always set at 12 months after the report is issued
    4. It is set by the local authority for all commercial premises

    Explanation

    The inspector recommends the next inspection date after considering the type and use of the installation, its condition, external influences and the records available. There is no single interval that applies to every installation.

  190. Question 190Recording results, condition reporting, classification codes and recommendations

    Which recommendation accompanies a C2 observation?

    1. No action is needed until the next scheduled inspection
    2. The item should be improved when the installation is next rewired
    3. The item should be monitored at each subsequent inspection
    4. Urgent remedial action is required Correct answer.

    Explanation

    C2 means the condition is potentially dangerous, so urgent remedial action is required to make the installation safe. The report is unsatisfactory until that work is done.

  191. Question 191Recording results, condition reporting, classification codes and recommendations

    Who must sign the declaration on an electrical installation condition report?

    1. An electrical duty holder employed at the premises being inspected
    2. The client who ordered the report
    3. The person who will carry out the remedial works
    4. The competent person who did the inspection and testing Correct answer.

    Explanation

    The declaration is signed by the competent person who carried out the inspection and testing, confirming the extent of the work and the observations made. The signature identifies who is accountable for the report.

  192. Question 192Recording results, condition reporting, classification codes and recommendations

    Why does an EICR state that the inspection was carried out on a sampling basis?

    1. Because test instruments can only measure a limited number of circuits per day
    2. Because the client is allowed to choose which circuits are inspected
    3. Because only the circuits with the highest load need to be tested
    4. Because the report cannot confirm that no other defects exist outside the sample Correct answer.

    Explanation

    A periodic inspection examines a sample of the installation rather than every accessory and every length of cable. The report therefore records the condition of what was inspected and cannot guarantee that no defects exist elsewhere.

  193. Question 193Recording results, condition reporting, classification codes and recommendations

    A test could not be carried out because a circuit could not be isolated. How should the corresponding entry in the schedule of test results be handled?

    1. Enter the value from the previous report for that circuit
    2. Leave the entry blank and note the limitation on the report Correct answer.
    3. Enter a zero so that the column is complete for every circuit
    4. Enter the tabulated maximum value for the protective device

    Explanation

    Where a test could not be performed, the entry is left blank and the reason is recorded as a limitation. Entering an invented or copied value would misrepresent the results obtained.

  194. Question 194Recording results, condition reporting, classification codes and recommendations

    An installation contains a departure from BS 7671 that is nevertheless considered safe. How is this dealt with on the EICR?

    1. The departure and the reason it is considered safe are recorded Correct answer.
    2. It is omitted, as only non-compliances need to be recorded
    3. It is coded C1, since any departure is a danger
    4. It is coded FI, since its safety cannot be confirmed

    Explanation

    Where a departure from BS 7671 is identified, the report records the departure and the reason the installation is still considered safe. This gives the reader the information needed to judge the decision.

  195. Question 195Recording results, condition reporting, classification codes and recommendations

    An inspector finds four separate defects during an inspection. How are they recorded in the observations section?

    1. As four separate entries, each with its own location and code Correct answer.
    2. As one entry listing all four defects under a single code
    3. As two entries, grouped by the circuits affected
    4. As a single entry, provided the defects are all on one floor

    Explanation

    Each observation is listed separately with its location, the item number from the schedule of inspections and its own classification code. This allows each defect to be tracked and remedied individually.

  196. Question 196Recording results, condition reporting, classification codes and recommendations

    Which information is recorded in the schedule of test results?

    1. The date of the last EICR and the name of the previous inspector
    2. The agreed extent of the inspection and any limitations
    3. The classification codes for every observation on the report
    4. The circuit details and the measured test results for each circuit Correct answer.

    Explanation

    The schedule of test results sets out the circuit details, such as protective device type and rating, cable size and the measured results of the tests carried out. It complements the schedule of inspections and the observations.

  197. Question 197Recording results, condition reporting, classification codes and recommendations

    What must be done with an EICR that records a C2 observation?

    1. It may be issued only after the client has agreed to the remedial work
    2. It must be withheld until the remedial work has been completed
    3. It must still be issued, with the client advised of the action required Correct answer.
    4. It should be re-coded as C3 so that the report can be issued as satisfactory

    Explanation

    An unsatisfactory report must still be issued so that the person responsible knows about the condition of the installation and can act. The report records the C2 and the urgent remedial action needed.

  198. Question 198Recording results, condition reporting, classification codes and recommendations

    In a dwelling, 13 A socket outlets are protected by a 32 A MCB with no 30 mA RCD. Which code applies?

    1. C3, because RCD protection is only a recommendation
    2. C2, because additional protection is required for these sockets Correct answer.
    3. FI, because the presence of an RCD cannot be confirmed
    4. C1, because the socket outlets are live

    Explanation

    Additional protection by a 30 mA RCD is required for socket outlets used by ordinary persons in a dwelling, and its absence in an existing installation is a potential danger. The observation is therefore coded C2 and the report is unsatisfactory.

  199. Question 199Recording results, condition reporting, classification codes and recommendations

    An FI is recorded for a distribution board that could not be opened. What is the effect on the overall assessment?

    1. Satisfactory, because no defect has been confirmed
    2. Satisfactory if all other observations are coded C3
    3. Satisfactory once the client agrees to further investigation
    4. Unsatisfactory, until the investigation is completed Correct answer.

    Explanation

    A report containing any FI is unsatisfactory, because the condition of that part of the installation is unknown and must be investigated without delay. The outcome is revisited once the investigation establishes the facts.

  200. Question 200Recording results, condition reporting, classification codes and recommendations

    An inspector carrying out an EICR finds a distribution board in which the circuit protective conductors of several final circuits are bare copper with no green/yellow identification. The conductors are securely connected and the installation is otherwise in good order. Which classification code applies to this observation?

    1. FI, because the identification of protective conductors can only be confirmed by further investigation
    2. C3, because the conductors do not comply with BS 7671 but give rise to no immediate or potential danger Correct answer.
    3. No code, because the circuit protective conductors are correctly connected and continuity has been verified
    4. C2, because any departure concerning earthing and bonding conductors is treated as potentially dangerous

    Explanation

    A C3 code is used where an observation does not comply with BS 7671 but does not give rise to immediate or potential danger, and improvement is recommended rather than required. Missing green/yellow identification on otherwise sound, correctly connected protective conductors is a typical example of such a non-compliance. Codes C1 and C2 are reserved for items where danger or potential danger exists.

City & Guilds 2391-51 flashcards

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

BS 7671 legal status
BS 7671 is the national wiring standard; it is non-statutory, but compliance is commonly accepted as evidence that statutory duties under the Electricity at Work Regulations have been met.
EAWR Regulation 14
Prohibits work on or near live conductors unless it is unreasonable for the equipment to be dead and suitable precautions, including a written risk assessment, have been taken.
Part P Building Regulations
Applies to electrical installations in dwellings in England and Wales; certain work is notifiable to building control and the work must comply with Part P requirements.
GS38 test lead requirements
Test probes to GS38 have no more than 4 mm exposed metal tip, finger guards, fused leads and adequate voltage category rating, protecting the user during live testing.
Prove dead procedure
Identify and isolate the circuit, lock off, prove the voltage detector on a known source, test the conductors, then re-prove the detector to confirm it still works.
Lock off and warning notice
The isolation device is padlocked with the key retained by the person working, and a warning notice is fixed so others cannot inadvertently restore the supply.
Two-pole voltage detector
An approved two-pole device to GS38 is used to prove conductors dead; non-contact or single-pole voltage indicators are not acceptable for proving dead.
Competence under EAWR
Regulation 16 requires that no person works on electrical systems unless competent to do so, or is supervised by someone who is competent, preventing unsafe working.
Sampling in periodic inspection
Periodic inspection may examine a sample of the installation where justified; the sample is increased if defects are found and the approach is recorded as a limitation.
Recording limitations
Items not inspected or tested, such as inaccessible areas or circuits omitted from the sample, must be listed on the condition report so the reader knows the extent covered.
Previous documentation review
Prior certificates, schedules of test results, drawings and records of alterations are reviewed before a periodic inspection to plan sampling and identify changes.
Agreeing extent with client
Before starting, the client and inspector agree in writing which parts of the installation and which circuits are covered, and what limitations apply.
Main protective bonding size
The main protective bonding conductor size is determined from the supply neutral conductor size using BS 7671 Table 54.8, typically 10 mm2 for a 25 mm2 neutral.
Safe zones for buried cables
Cables buried in walls must run within defined safe zones, typically within 150 mm of a corner or ceiling or aligned with an accessory, otherwise extra protection is required.
Signs of heat damage
Discoloured or brittle insulation, melted plastic, blackened terminals and a burning smell indicate overheating from loose connections or overload and require investigation.
Consumer unit enclosure checks
The enclosure should be sound, correctly IP rated for its location, with no unused open knockouts, intact barriers and a legible and accurate circuit chart.
EIC versus EICR
An Electrical Installation Certificate is issued after initial verification of new work; an Electrical Installation Condition Report records the condition of an existing installation after periodic inspection.
Initial verification coverage
Initial verification covers the whole new installation or alteration, comparing it with the design, and requires full inspection and testing without any sampling.
Purpose of periodic inspection
Periodic inspection determines whether an existing installation is safe for continued use, identifying deterioration, damage, defects and non-compliance with the current standard.
Domestic EICR interval
Guidance suggests a maximum of ten years between periodic inspections for a domestic installation, or at a change of occupancy or change of use.
Ring final continuity readings
End-to-end resistances r1, rn and r2 are measured; r1 should equal rn, and r2 is approximately 1.67 times r1 for 2.5 mm2 line and 1.5 mm2 CPC.
Ring final R1+R2 value
After cross-connecting line and neutral at the board, the expected R1+R2 at each socket is (r1+r2)/4, with readings increasing towards the mid-point of the ring.
Insulation resistance minimum
For circuits up to 500 V the test is at 500 V DC and the minimum acceptable insulation resistance is 1 Mohm; SELV and PELV require 250 V DC and 0.5 Mohm.
Main bonding continuity value
Continuity of main protective bonding is measured between the main earthing terminal and the bonding clamp, with a typical acceptable result of 0.05 ohm or less.
External earth loop impedance
Ze is measured at the origin with the installation isolated, the main switch off and the main earthing conductor disconnected, using a suitable earth fault loop impedance tester.
Zs 0.8 rule
Measured Zs should not exceed 0.8 times the tabulated maximum Zs, because tabulated values apply at 20 degrees C while conductors run hotter in service.
RCD five-times tripping time
A general non-delay RCD should trip within 40 ms when tested at five times its rated residual operating current, and the test is repeated on both half-cycles.
Prospective fault current measurement
Prospective short-circuit current between line and neutral and prospective earth fault current between line and earth are both measured at the origin, and the higher is recorded.
C1 classification code
C1 means danger is present, there is a risk of injury, and immediate remedial action is required, usually involving isolation of the affected circuit or installation.
C2 classification code
C2 means a potentially dangerous condition exists and urgent remedial action is required; a report containing any C2 observation cannot be recorded as satisfactory.
C3 classification code
C3 means improvement is recommended; the condition is not dangerous but would benefit from improvement, and no immediate action is required.
FI classification code
FI means further investigation is required because a defect or departure is suspected but cannot be confirmed without additional access, testing or dismantling.

City & Guilds 2391-51 study guide

Statutory and non-statutory regulations, standards and guidance

The hierarchy

Inspection and testing sits inside a legal framework, and questions test whether you can separate law from standard from guidance.

Statute. The Health and Safety at Work etc. Act 1974 creates the general duty. The Electricity at Work Regulations 1989 are the key set for electrical work: regulation 4(1) requires electrical systems to be constructed and maintained so as to prevent danger, regulation 5 covers strength and capability, regulation 6 adverse environments, and regulation 29 permits work on or near live conductors only in limited circumstances. PUWER 1998 covers your test instruments and probes, MHSWR 1999 requires risk assessment, ESQCR 2002 governs distributors, and Part P of the Building Regulations applies to domestic work in England and Wales.

Non-statutory. BS 7671 (the IET Wiring Regulations), IET Guidance Note 3, the On-Site Guide and HSE guidance HSG85 and GS38 are not law, but a court may treat them as evidence of good practice. Non-compliance does not automatically create liability, and compliance does not automatically discharge the EAWR duty.

Traps. BS 7671 is often described as a legal requirement in distractors - it is not. BS 7671 is also not retrospective: an installation to an earlier edition is not automatically non-compliant. Conversely, EAWR and PUWER apply to every installation regardless of age.

Rule of thumb. A cheap multimeter with long unshrouded probes offends GS38 and PUWER: GS38 expects fused or current-limited leads, finger guards and roughly 4 mm maximum exposed tip.

Safe isolation, safety management and safe working practices

Making dead safe

Safe isolation is a sequence, not a single action, and the sequence is examined closely.

  1. Identify every source of supply to the part to be worked on - parallel supplies, a second consumer unit, PV inverters, generators, UPS, emergency lighting, control circuits and shared or borrowed neutrals.
  2. Notify affected persons and agree a shutdown.
  3. Isolate. Remember the consumer unit main switch does not isolate the meter tails or the distributor's cut-out.
  4. Secure the isolation with a lock and caution notice, and keep the key.
  5. Prove the voltage indicator before use (proving unit or known live source), prove dead at the point of work on every conductor, line-to-line and line-to-earth, then re-prove the indicator - the prove-test-prove routine.
  6. Only then apply portable earths or dismantle.

Traps. Fitting a lock-off and then testing at the board rather than at the actual point of work; using an untested indicator; forgetting that a single-pole device can leave a conductor at a dangerous potential; assuming that switching off proves dead. On a TN-C-S supply the neutral is a PEN conductor and must be treated as live.

Safety management. A risk assessment and method statement, suitable PPE, arc-flash awareness, barriers and permits to work are expected. Live testing must be justified and carried out with instruments of the correct overvoltage category.

Rule of thumb. If you cannot prove your voltage indicator on a proving unit, you have not proved dead - stop.

Preparation for periodic inspection: documentation, extent, sampling and limitations

Before you start

The period before the inspection determines whether the report is defensible. Gather previous certificates and reports (EIC, EICR, minor works certificates, schedules of test results), distribution board charts, drawings and as-fitted layouts, design data, maintenance records including alterations and repairs, and details of how the installation is used and why the inspection has been requested.

Agree the scope with the client: the purpose, the extent (the whole installation or a named part) and the limitations. Limitations are recorded where access is not possible, where a shutdown is not permitted, or where equipment cannot be isolated. Everything outside the agreed extent is excluded, and the report must say so.

Sampling. You cannot dismantle every accessory. Guidance permits a sample - commonly at least 10% of items - spread across each distribution board and a range of circuit types, with a representative number of accessories and joints. If a sampled item shows a defect, the sample is enlarged, up to 100%.

Traps. Reusing the previous report's results as though they were current; failing to record limitations, since a report is only valid within its stated extent; assuming the client's requested extent is adequate, when the inspector may recommend a wider one; and using test equipment without a current calibration certificate, typically within 12 months.

Rule of thumb. Sample 10%; find a fault and expand the sample; a report without recorded limitations is a report you cannot defend.

Visual inspection and identifying non-compliance and deterioration

Look before you test

Visual inspection is the highest-yield part of a periodic inspection: most defects found in service are visible. Inspect with the installation isolated and safe, working systematically from origin to final circuit.

Check the origin and distributor's equipment; consumer units and distribution boards - device ratings and types, enclosure condition, blanking, labelling; main protective bonding of incoming metallic services (water, gas, oil, structural steel) with the correct conductor size, a sound connection, and on a PME supply within about 600 mm of the point of entry; circuit protective conductors present and connected; cable types, routes, support and protection; accessories - cracked, damaged, missing lids, wrong IP rating, thermal damage, scorching, loose terminations; fire sealing of penetrations; danger and warning notices, RCD notices, the periodic inspection label and the notice at the origin.

Deterioration includes discoloured insulation, verdigris, corrosion, water ingress, rodent damage, chafed sheaths and loose terminations.

Traps. Missing or undersized main protective bonding is a common high-code observation, often C2. Bonding applies to extraneous conductive parts, not to every pipe. Exposed live parts are C1 and must be made safe immediately, with the client's authority.

Worked example. A 6 mm2 bonding conductor is fitted to the incoming gas pipe with a loose clamp and a corroded connection 2 m from the meter: bonding is present but not secure and may be undersized for a PME supply - record it and code C2.

Initial verification versus periodic inspection and agreeing scope

Two different jobs

Initial verification and periodic inspection answer different questions.

Initial verification asks: does this new work comply with the design and with BS 7671? It is done before the installation is energised or put into service, covers 100% of the installation, requires design data, and the results are recorded on an Electrical Installation Certificate with schedules of inspections and test results.

Periodic inspection asks: is this existing installation in a satisfactory condition for continued service? It is done with the installation in use as far as possible, samples rather than covers everything, works from limited documentation, records observations on an Electrical Installation Condition Report, and recommends the next inspection interval.

Three consequences that questions test: BS 7671 is not retrospective, so departures from an earlier edition are not automatically non-compliant; an EICR cannot confirm that the design was ever correct, only whether the installation is in a satisfactory condition within the extent inspected; and a satisfactory report is not a guarantee that every circuit has been tested.

Agreeing the scope. Before testing, confirm with the client in writing the purpose, the extent and the limitations, and put them on the report. Where the requested extent is inadequate for the purpose, say so and recommend a wider extent.

Traps. Statements such as a periodic inspection confirms compliance with the current edition of BS 7671 are wrong, as is a satisfactory EICR means the installation is safe - it means no C1, C2 or FI was found within the stated extent.

Dead testing: continuity, ring final circuits, polarity and insulation resistance

Dead testing

Dead tests are carried out with the supply isolated, in a set order, because later tests depend on earlier ones.

Continuity of protective conductors. Either the R1+R2 method (temporary link between line and CPC at the board, measure at each point) or a long wander lead. Readings should be consistent with expected conductor resistance and circuit length.

Ring final circuit continuity. Measure end-to-end r1, rn and r2 at the board. Cross-connect the line of one leg to the neutral of the other and measure at each socket; readings should be roughly equal, around (r1+rn)/4. Repeat with line to CPC, expecting about (r1+r2)/4. A reading much higher than its neighbours indicates a spur; no reading indicates a break.

Polarity. Confirm line to the centre contact of ES lampholders, line to the protective device and not the neutral, correct socket polarity, and that all single-pole switches are in the line.

Insulation resistance. With the main switch off, lamps removed and sensitive equipment and SPDs disconnected, test at 500 V DC between line/neutral, line/earth and neutral/earth. The minimum for a 500 V test is 1 M ohm; a healthy installation typically reads hundreds of megohms.

Traps. Testing through connected equipment, RCDs, neon indicators or surge protection gives misleadingly low readings. Never infer polarity from cable colours alone. R1+R2 is not the same as end-to-end r1+r2.

Rule of thumb. Any insulation resistance below 1 M ohm is a failure and must be investigated, not recorded and forgotten.

Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

Live testing

Live tests confirm that protective devices will operate within the required disconnection time and that residual current devices work.

Earth fault loop impedance. Ze is measured at the origin with the installation isolated and the means of earthing disconnected, or obtained by enquiry. Zs is measured at the furthest point of each circuit, or calculated as Ze + R1+R2. Compare Zs with the maximum in BS 7671 Table 41.3 or 41.4, or with manufacturer's data. Because those tables assume conductors at maximum operating temperature, a healthy circuit typically measures around 80% of the tabulated maximum; a reading at or near the maximum warrants investigation.

Prospective fault current. Measure at the origin and at circuit ends, record the higher of prospective short-circuit current and prospective earth fault current, and compare with the breaking capacity of the devices.

RCD testing. Use the test button as a functional check, then an instrument: half rated residual current for no trip, rated current for operation within 300 ms, and five times rated current for operation within 40 ms. Test at the device and at a socket outlet so the circuit is included.

Functional testing also covers isolators, switches, interlocks and, where within scope, emergency lighting.

Traps. Recording only PSCC when PEFC is higher, which is typical of TT systems; testing RCDs without checking supply polarity; and taking a Zs on a circuit with an open CPC.

Worked example. A 32 A Type B MCB on a ring final measures Zs 0.58 ohm against a tabulated maximum of 1.37 ohm - acceptable and well below the limit.

Recording results, condition reporting, classification codes and recommendations

Recording and reporting

The output of a periodic inspection is the Electrical Installation Condition Report. Its sections are: details of the client and installation, the date of the previous inspection, the extent and limitations, a summary of condition, observations with classification codes, the schedule of items inspected, the schedule of test results, a recommendation for the next inspection interval, and the declaration and signature.

Classification codes.

  • C1 - danger present: risk of injury, immediate remedial action required. With the client's authority, make safe or isolate.
  • C2 - potentially dangerous: urgent remedial action required.
  • C3 - improvement recommended: not dangerous, but would improve safety.
  • FI - further investigation required: without delay, because the inspector could not establish whether the item is safe. Observations may also be recorded with no code where an item departs from the current edition but does not warrant one.

Satisfactory or unsatisfactory. Any C1, C2 or FI makes the report unsatisfactory; C3 items alone do not.

Recommendations. Give a next inspection interval based on installation type, use, environment and maintenance regime - commonly 10 years for domestic and 5 years for commercial or industrial, with change of occupancy prompting a new inspection.

Traps. Coding an item C3 and then declaring the installation unsatisfactory; omitting the extent and limitations; failing to record an FI because it is only a guess; and wording observations so vaguely that the client cannot act on them.

Rule of thumb. C1 make safe now, C2 urgent, C3 improve, FI investigate - any of the first, second or fourth makes the report unsatisfactory.

City & Guilds 2391-51 cheat sheet

Quick reference

Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

  • BS 7671 (IET Wiring Regulations) is non-statutory, but enforcement bodies and courts accept compliance as evidence of reasonable practicability under the Electricity at Work Regulations 1989.

  • Electricity at Work Regulations 1989: Reg 4 (systems and protective equipment), Reg 12 (isolation), Reg 13 (work on dead equipment), Reg 14 (live working), Reg 16 (competence).

  • Health and Safety at Work etc. Act 1974 places duties on employers and self-employed persons to ensure safety so far as is reasonably practicable, including contractors on site.

  • Part P of the Building Regulations 2010 applies to fixed electrical installations in dwellings in England and Wales; notifiable work requires building control notification.

  • IET Guidance Note 3 gives the recognised practical guidance on inspection and testing to BS 7671 Part 6 (Chapters 61 to 64).

  • HSE GS38 specifies test probe and lead requirements: maximum 4 mm exposed tip, finger guards, fused leads and adequate voltage category rating.

  • The Electricity Safety, Quality and Continuity Regulations 2002 govern the supply and distribution network, not the consumer's installation.

  • The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 require a five-yearly EICR by a competent person, with remedial action within 28 days.

  • Non-statutory documents (BS 7671, guidance notes, codes of practice) create no legal duty by themselves; duties arise from statute and statutory instruments.

Quick reference

Safe isolation, safety management and safe working practices on site

  • Safe isolation sequence: identify the circuit and all sources, isolate, lock off and retain the key, post a warning notice, prove dead with an approved two-pole detector, then re-prove the detector.

  • The voltage detector must be proved on a known live source or proving unit before and after testing the isolated conductors.

  • Non-contact voltage sticks and single-pole testers are not acceptable for proving dead; only an approved two-pole device to GS38 is used.

  • Parallel supplies must be isolated: standby generators, UPS, PV inverters, dual supplies, control circuits and signal circuits.

  • EAWR Reg 13: equipment made dead must be isolated, secured against reconnection where practicable, and proven dead at the point of work.

  • Live working is permitted only where it is unreasonable to work dead and suitable precautions, including a written risk assessment, are taken under EAWR Reg 14.

  • EAWR Reg 16 makes competence a legal requirement; work must be supervised where the person is not competent to carry it out unaided.

  • Test leads to GS38 are fused, fitted with finger guards, have 4 mm maximum exposed tips, and are inspected for damage before every use.

Quick reference

Preparation for periodic inspection and testing: documentation, extent, sampling and limitations

  • Collect previous EICRs, EICs, schedules of test results, drawings and records of alterations before attending site.

  • Agree the extent, limitations and sampling approach with the client in writing before the inspection starts.

  • Sampling may be used on existing installations, but the sample must be increased where defects or non-compliance are found.

  • Record every limitation on the report: inaccessible areas, circuits not sampled, equipment not energised, buried cables not inspected.

  • Confirm the earthing system (TN-S, TN-C-S, TT), nominal voltage, supply capacity and any special locations before testing.

  • Check that test instruments have a valid calibration certificate and correct category rating, and prove leads and battery condition.

  • Plan shutdowns, permits to work, access arrangements and safe isolation with the duty holder before energised testing.

  • Identify special installations and locations (bathrooms, swimming pools, agriculture, fire alarm and emergency lighting systems) requiring specific inspection.

Quick reference

Visual inspection of electrical installations and identification of non-compliance and deterioration

  • Check the origin: intake condition, meter, main switch or isolator, distributor's earthing facility and presence of a main protective bonding conductor.

  • Verify main protective bonding to metallic services (water, gas, oil, structural steel) is present, correctly sized to Table 54.8 and securely clamped.

  • Check distribution boards: enclosure condition, IP rating, unused open knockouts, barriers and shrouds, labelling and circuit chart accuracy.

  • Look for heat damage: discoloured insulation, blackened or melted terminations, burnt smells and arcing marks at connections.

  • Check cables for sheath damage, correct support, mechanical protection, routing within safe zones and fire barrier penetration.

  • Check accessories for cracks, missing screws, correct IP rating, bathroom zoning compliance, damaged sockets and signs of overheating.

  • Check protective device rating against cable capacity (Ib <= In <= Iz) and correct device type for the earthing arrangement and disconnection time.

  • Confirm RCD protection where required and notices such as the RCD test notice, SPD notice and danger or dual supply labels.

  • Record deterioration such as corrosion, water ingress, rodent damage, loose connections and unauthorised DIY alterations as coded observations.

Quick reference

Differences between initial verification and periodic inspection, and agreeing the scope of the report

  • Initial verification applies to new installations and to alterations or additions, and is carried out before the installation is put into service.

  • Periodic inspection applies to existing installations already in service and determines fitness for continued use.

  • Initial verification requires full inspection and testing of the work with no sampling; periodic inspection may use sampling with recorded limitations.

  • Initial verification produces an Electrical Installation Certificate (EIC); periodic inspection produces an Electrical Installation Condition Report (EICR).

  • The EICR is a report on condition, not a certificate of compliance with the current edition of BS 7671.

  • Periodic inspection considers age, use, wear, environment, previous records and any change of use or occupancy.

  • Guidance intervals: domestic about 10 years, rented domestic 5 years, commercial 5 years, industrial 3 years, and at change of occupancy.

  • The scope agreement defines circuits included and excluded, the sampling level, limitations, and whether remedial work is to be quoted.

  • Both activities follow the same test sequence, but periodic testing is proportionate to the agreed sample and the available records.

Quick reference

Dead testing: continuity, ring final circuit, polarity and insulation resistance

  • Continuity of circuit protective conductors is measured with a low-resistance ohmmeter with leads nulled, giving R1+R2 for each circuit.

  • Main protective bonding continuity is measured between the main earthing terminal and the bonding clamp; a value of 0.05 ohm or less is typical evidence of a sound connection.

  • Ring final circuit: measure r1, rn and r2 end to end; r1 should equal rn and r2/r1 is about 1.67 for 2.5 mm2 line with 1.5 mm2 CPC.

  • Ring cross-connection: expected R1+R2 at a socket is (r1+r2)/4, while (r1+rn)/4 gives the expected loop reading at each socket.

  • A ring with a broken conductor or an unintended spur shows socket readings that do not follow the expected progression from the board.

  • Insulation resistance: 500 V DC with a minimum of 1 Mohm for circuits up to 500 V; 250 V DC and 0.5 Mohm for SELV and PELV.

  • Test insulation between live conductors and earth, i.e. line and neutral connected together to the protective conductor, to protect connected electronic equipment.

  • Isolate and disconnect loads, SPDs, dimmers, electronic ballasts and controls before the insulation test, and discharge after testing.

  • Polarity by dead testing confirms line is connected to the centre pin or line terminal and that all single-pole devices are in the line conductor.

Quick reference

Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

  • Ze is measured at the origin with the installation isolated, main switch off and main earthing conductor disconnected, using an earth fault loop impedance tester.

  • Zs is measured at the furthest point of each circuit, or calculated from Ze + R1+R2, and compared with the maximum tabulated value.

  • Measured Zs should not exceed 0.8 times the tabulated maximum Zs from BS 7671 to allow for conductor operating temperature.

  • Prospective fault current: measure PSCC (line to neutral) and PEFC (line to earth) at the origin and record the higher of the two.

  • The recorded prospective fault current must not exceed the short-circuit rating (Icn) of the protective devices installed.

  • RCD test sequence: half rated current must not trip; rated current within 300 ms; five times rated current within 40 ms for general non-delay RCDs.

  • Test RCDs on both half-cycles of the waveform and at each outlet protected by the device, particularly 30 mA additional protection.

  • Functional testing confirms correct operation of isolators, switches, RCD test buttons, timers, indicators and interlocked equipment.

  • Energised testing requires a risk assessment, insulated tools and PPE, protection from adjacent live parts, and adequate working space and lighting.

Quick reference

Recording results, condition reporting, classification codes and recommendations

  • The EICR records installation details, extent and limitations, summary of condition, coded observations, schedules of inspection and test results, and the next inspection date.

  • C1 = danger present, risk of injury, immediate action required, usually isolation of the affected part of the installation.

  • C2 = potentially dangerous condition, urgent remedial action required.

  • C3 = improvement recommended; not dangerous but the installation would benefit from improvement.

  • FI = further investigation required without delay because a suspected defect cannot be confirmed with the access or information available.

  • No code is recorded for items that comply, are not applicable, or where a limitation was agreed with the client.

  • The overall assessment is recorded as satisfactory only where no C1 or C2 observations are present.

  • The next inspection interval is recommended from the installation type, use, environment, condition and duty holder requirements.

  • Test results are recorded on the schedule of test results with circuit references, and the signed report is issued to the person ordering the work.

City & Guilds 2391-51 key terms

Electricity at Work Regulations 1989

Statutory regulations in Great Britain placing duties on those responsible for electrical systems at work to keep them safe, properly maintained and worked on by competent people. Breaching them is a criminal offence.

Related: BS 7671 (IET Wiring Regulations), Competent person
BS 7671 (IET Wiring Regulations)

The British Standard covering the design, erection, inspection and testing of electrical installations. Following it is the accepted way of showing that legal duties, such as those in the Electricity at Work Regulations, have been met.

Related: Electricity at Work Regulations 1989, Guidance Note 3 (GN3)
Guidance Note 3 (GN3)

An IET publication explaining in detail how to inspect, test and certify installations to BS 7671. It is the standard reference for inspection and testing practice and for completing certificates and reports.

Related: BS 7671 (IET Wiring Regulations)
Part P

The Building Regulations requirement, applying in England and Wales, that electrical installation work in dwellings is safe. Notifiable work must be certified by a registered competent person or by building control.

Related: Competent person
Competent person

Someone with enough technical knowledge, skill and experience to carry out the work safely and prevent danger or injury. Their competence must be appropriate to the particular task being done.

Related: Safe isolation
Safe isolation

A formal sequence of identifying the circuit, switching off, isolating, locking off and proving dead, then confirming the correct circuit was isolated. It protects the worker from electric shock and arc flash.

Related: Prove dead, Lock-off device and caution notice
Prove dead

Using a proven voltage indicator to confirm zero voltage between all live conductors, and between each live conductor and earth, immediately before touching the isolated conductors.

Related: Proving unit, Safe isolation
Proving unit

A known voltage source used to check that a voltage indicator is working correctly before and after proving a circuit dead. Some indicators have a built-in self-test instead.

Related: Prove dead
Lock-off device and caution notice

A lock and warning label fitted to an isolator or protective device so that an isolated circuit cannot be re-energised by someone else while work is in progress.

Related: Safe isolation, Permit to work
Permit to work

A formal written document authorising specific work under stated safety conditions. It is used for high-risk tasks such as live working or work on complex or hazardous installations.

Related: Safe isolation
Periodic inspection and testing

Scheduled inspection and testing of an existing installation at intervals during its life, to assess its condition and compliance with BS 7671. The findings are recorded in an Electrical Installation Condition Report.

Related: Electrical Installation Condition Report (EICR), Sampling
Extent and limitations

The agreed description of which parts of an installation will be inspected and tested and what will be left out, recorded so readers know exactly what the report does and does not cover.

Related: Sampling, Agreed scope of report
Sampling

Inspecting and testing a representative selection of the installation rather than every item, chosen to give reasonable confidence in the condition of the whole. Any parts not sampled must be recorded as limitations.

Related: Extent and limitations
Visual inspection

A careful examination of the installation, without dismantling beyond what is needed, to find damage, deterioration, overheating, incorrect identification, poor workmanship and departures from BS 7671.

Related: Deterioration, Non-compliance
Non-compliance

A departure from BS 7671 or another applicable standard found during inspection. It must be recorded as an observation and classified according to the risk it presents.

Related: Classification code C2, Deterioration
Deterioration

The decline in condition of installation parts through ageing, wear, corrosion, heat or damage, such as cracked insulation or loose connections, which increases the chance of fault or danger.

Related: Visual inspection
Initial verification

Inspection and testing of a new installation, or of new work, carried out before it is put into service, to confirm that it matches its design and complies with BS 7671.

Related: Electrical Installation Certificate (EIC), Periodic inspection and testing
Electrical Installation Certificate (EIC)

The certificate issued after initial verification of a new installation or major alteration, declaring that the work has been designed, constructed, inspected and tested in accordance with BS 7671.

Related: Initial verification, Minor Electrical Installation Works Certificate
Minor Electrical Installation Works Certificate

A certificate used for small additions or alterations that do not add a new circuit, covering the design, construction, inspection and testing of that particular piece of work.

Related: Electrical Installation Certificate (EIC)
Agreed scope of report

The purpose and coverage of the report, agreed with the client before work starts, including the extent, limitations, sampling and any special requirements such as a change of occupancy.

Related: Extent and limitations, Sampling
Continuity testing

Measuring the resistance of protective, bonding and circuit conductors to show they are continuous and correctly connected. Results are compared with expected values calculated from conductor size and length.

Related: R1+R2, Insulation resistance test
R1+R2

The measured resistance of a circuit's line conductor plus its circuit protective conductor, taken with the supply isolated. It is added to the external loop impedance to give the earth fault loop impedance.

Related: Continuity testing, Earth fault loop impedance (Zs)
Ring final circuit test

A test of a ring final circuit using end-to-end resistance readings of line, neutral and protective conductors, then a cross-connected reading. The cross-connected value should be roughly a quarter of the end-to-end line-to-neutral value.

Related: Polarity test
Polarity test

Confirming that line, neutral and protective conductors are connected to the correct terminals throughout, so that switches and single-pole devices are in the line conductor and earthing remains effective.

Related: Ring final circuit test
Insulation resistance test

A dead test applying a DC voltage, usually 500 V for 230/400 V circuits, between live conductors and earth and between live conductors, to confirm the insulation is sound. Results must meet the minimum values in BS 7671.

Related: Continuity testing
Earth fault loop impedance (Zs)

The total impedance of the path taken by fault current from the point of fault, through the protective conductor and back to the supply source. It determines whether the protective device disconnects within the required time.

Related: External earth fault loop impedance (Ze), Prospective fault current (PFC)
External earth fault loop impedance (Ze)

The impedance of the fault path outside the installation, measured at the origin with the main switch off. It is used together with a circuit's R1+R2 to calculate Zs.

Related: Earth fault loop impedance (Zs)
Prospective fault current (PFC)

The current that would flow if a short circuit or earth fault occurred at a particular point, measured or calculated at the origin. It is used to check that protective devices and equipment can withstand it.

Related: Earth fault loop impedance (Zs)
RCD operating time test

Using an RCD tester to confirm that a residual current device trips within the required time at its rated residual operating current and at five times that current.

Related: Functional testing
Functional testing

Operating switches, isolators, RCD test buttons, interlocks, emergency lighting and similar equipment to confirm they work as intended as part of the inspection and testing process.

Related: RCD operating time test
Classification code C1

The observation code for a danger present with risk of injury, where immediate remedial action is required and the installation, or the affected part, must be made safe or isolated straight away.

Related: Classification code C2, Satisfactory or unsatisfactory
Classification code C2

The observation code for a potentially dangerous condition: a defect that could become dangerous and that needs urgent remedial action.

Related: Classification code C1, Classification code C3
Classification code C3

The observation code for an improvement recommended: a departure or non-compliance that is not dangerous but would improve safety if it were put right.

Related: Classification code C2
FI (further investigation)

A code used where a problem has been found but cannot be fully assessed without further investigation, for example where part of the installation is hidden or badly deteriorated.

Related: Classification code C2
Observations

The findings from the inspection and testing, each written up with its location and given a classification code. They form the main body of the condition report and drive the recommendations.

Related: Classification code C2, Electrical Installation Condition Report (EICR)
Electrical Installation Condition Report (EICR)

The report produced after a periodic inspection, recording the extent, limitations, test results and observations, with an overall assessment and the date by which the next inspection is due.

Related: Periodic inspection and testing, Satisfactory or unsatisfactory
Satisfactory or unsatisfactory

The overall assessment on a condition report: satisfactory where no C1 or C2 observations are recorded, and unsatisfactory where any C1 or C2, or an unresolved further investigation, is present.

Related: Classification code C1, Classification code C2
Schedule of Test Results

The form, part of a certificate or condition report, on which measured results such as continuity, insulation resistance, Zs, prospective fault current and RCD operating times are recorded circuit by circuit.

Related: Electrical Installation Condition Report (EICR)

City & Guilds 2391-51 study plan

8 weeks · About 7 hours per week

Week 1

Visual inspection of electrical installations and identification of non-compliance and deterioration & Statutory and non-statutory regulations, standards and guidance applicable to inspection and testing

  • List the statutory and non-statutory documents that govern inspection and testing and state the legal status of each

  • Identify, from written descriptions of installed equipment, at least 30 examples of non-compliance or deterioration

  • Match each identified defect to the relevant requirement in BS 7671 or the associated guidance

  • Distinguish between departures that require improvement and those that are immediately dangerous

  • Rank identified defects in order of severity without yet assigning classification codes

Your checkpoint

A 30-item visual inspection defect log with a regulation or guidance reference and a severity ranking for every entry

Week 2

Safe isolation, safety management and safe working practices on site & Dead testing: continuity, ring final circuit, polarity and insulation resistance

  • Write out, from memory, a full safe isolation procedure including proving the tester before and after use

  • Justify the selection and inspection requirements for test instruments and leads under the relevant guidance

  • Perform and record protective conductor continuity and main bonding continuity results on a practice installation

  • Carry out ring final circuit end-to-end and cross-connected readings and interpret the resulting r1, rn, r2 values

  • Confirm polarity at every relevant point of a practice circuit and record the outcome

Your checkpoint

A completed dead-test record sheet for continuity, ring final circuit and polarity on a practice board, with calculated expected values alongside measured values

Week 3

Dead testing: continuity, ring final circuit, polarity and insulation resistance

  • Select the correct insulation resistance test voltages and minimum acceptable values for different circuit types

  • Explain how to prepare an installation for insulation resistance testing and which items must be disconnected

  • Calculate expected insulation resistance values for a given set of parallel circuits

  • Describe how to interpret an unexpectedly low insulation resistance reading and state the next action

  • Sequence the full dead testing regime in the correct order and justify that order

Your checkpoint

A written dead-test sequence for a specified installation, including test voltages, expected values, tolerances and the action to take on each unsatisfactory result

Week 4

Live testing: earth fault loop impedance, prospective fault current, RCD and functional testing

  • Describe the methods for measuring earth fault loop impedance at the origin and at the furthest point of a circuit

  • Calculate expected loop impedance values from protective device characteristics and compare them with measured results

  • Distinguish between prospective fault current measurement and calculation, and state where each is appropriate

  • Carry out and record the full set of RCD tests, including the half-rated current, tripping time and operating time checks

  • Justify the functional testing required for a completed installation and list what must be verified

Your checkpoint

A live test results table for a practice installation showing measured and calculated earth fault loop impedance, prospective fault current and all RCD test results, with each result judged as compliant or non-compliant

Milestones

Week 2: Reproduce the safe isolation procedure and the dead-test sequence unaided, scoring at least 80% on a self-marked written check

Week 4: Complete a full set of dead and live test results for one practice installation within a two-hour time limit, with no missing readings

Week 6: Correctly assign observation codes to 20 written scenarios, with a written justification for each code that references the relevant requirement

Week 8: Achieve at least 80% on two timed mixed-topic mock papers covering all eight domains

City & Guilds 2391-51 exam day

Your checklist

Photo ID

Bring current photographic ID (e.g. passport or photocard driving licence). Confirm with the provider which forms of ID it accepts before the day - requirements vary between centres.

Appointment / joining instructions

Bring your booking confirmation and candidate/registration number, and read the centre's joining instructions in full (arrival time, site address, parking, what is and is not supplied).

Current edition of BS 7671

Many centres supply the regulations and guidance documents on the day, but confirm with the provider what reference material you may bring in and what will be provided.

On-Site Guide / Guidance Note 3

Useful for inspection, testing and EICR work, but confirm with the provider whether personal copies are permitted in the assessment area - some centres restrict materials to those they issue.

Scientific calculator

Non-programmable, with fresh batteries. Confirm with the provider whether a calculator is supplied and whether programmable or stored-data models are prohibited.

Stationery

Pens (including a spare), pencil, eraser, ruler and highlighter for recording results and completing documentation.

Personal protective equipment

Bring safety footwear as a minimum and wear suitable clothing for practical work. Confirm with the provider whether it supplies PPE such as gloves, eye protection or coveralls, and what its dress code requires.

Safe isolation equipment

Familiarise yourself with the lock-off/proving procedure. Confirm with the provider whether you must bring your own padlock and lock-off device or whether these, and the proving unit, are supplied.

Test instruments

Assume the centre supplies calibrated instruments and test leads, but confirm with the provider in advance - do not arrive expecting to use your own unless you have written confirmation.

EICR / model forms

You will typically complete an Electrical Installation Condition Report for the assessment installation. Confirm with the provider whether forms are supplied or whether you should bring your own current model forms.

Refresh safe isolation and GS38 practice

Rehearse the full safe isolation sequence (identify, isolate, lock off, prove the tester, prove dead, prove the tester again) and the correct use of test leads and probes to GS38 - unsafe practice is directly assessed.

Refresh inspection and testing knowledge

Revise Part 6 and Part 7 of BS 7671, the standard test sequence, expected results, and the condition-reporting codes (C1, C2, C3, FI) together with recording limitations and extent of sampling.

Plan the day

Final 72 hours

Re-read the assessment outcomes and your centre's joining instructions; confirm arrival time, site address and travel plan. Check that your ID is in date and pack your kit early. Spend revision time on the inspection checklist, test sequence, expected values and EICR coding rather than on new material. Protect sleep in the last two nights.

Final 72 hours

Confirm with the provider any open questions: what reference documents and instruments are supplied, whether PPE is provided, and whether you may bring your own forms or calculator. Get the answers in writing if possible.

24 hours before

Pack and check everything on the checklist; charge or replace batteries in any personal items; lay out clothing and safety footwear. Rehearse the safe isolation sequence and the dead-then-live test order out loud. Review the difference between C1, C2, C3 and FI and how to record limitations and agreed sampling. Have an early night.

Morning of the assessment

Eat properly and allow generous travel time - aim to arrive well before the stated time so you can sign in, store belongings and settle. Switch your phone off and stow it as instructed. Use the wait to mentally rehearse the safe isolation procedure rather than to cram new facts.

During the assessment - briefing

Listen carefully to the assessor's briefing, note the scope of the installation, the extent of inspection and testing expected, and any agreed limitations. Ask clarifying questions at the start rather than mid-task. Confirm where you may and may not work.

During the assessment - inspection

Work systematically, area by area, using a consistent inspection routine. Record what you observe as you go rather than relying on memory, and note any limitations and their reasons.

During the assessment - testing

Carry out safe isolation and prove dead before working on circuits. Follow the standard sequence: continuity of protective conductors, continuity of ring final circuit conductors, insulation resistance, polarity, then live tests (earth fault loop impedance, prospective fault current, RCD operation) last. Record results as you obtain them and compare with expected values.

During the assessment - reporting and discussion

Complete the condition report accurately and legibly, assign condition codes with a clear justification, state the overall assessment and any limitations. Be ready for the assessor's questions: explain your reasoning, the effect of your findings and your recommended actions. If you make an error, say so and correct it rather than covering it up.

Rules to check

  • Bring current photographic ID; the provider will refuse entry without it. Confirm accepted ID types with the provider in advance.

  • Mobile phones and smart devices must be switched off and stored as directed. Do not photograph, record or remove any assessment materials, and do not discuss the assessment content with other candidates.

  • Comply with the centre's health and safety rules at all times. Safe isolation and safe working practice are assessed in their own right, and the assessor may stop you if your practice is unsafe - confirm with the provider how a stoppage affects the outcome.

  • Confirm with the provider what reference material, notes and pre-completed forms you may bring into the assessment area; assuming you may use your own documents when you may not can invalidate your result.

  • Breaks and movement around the site are at the assessor's discretion. Ask permission before leaving the assessment area; confirm with the provider how breaks are handled and whether they count towards the assessment time.

  • The work must be your own. The assessor will observe you and ask questions to confirm your understanding; you must be able to explain and justify what you have done.

  • Assessment outcomes and feedback are issued through the centre's own process, and resit or appeal arrangements vary. Confirm with the provider how and when results are released and what the appeals route is.

City & Guilds 2391-51 FAQ

How many City & Guilds 2391-51 practice questions are available?

The practice set has 200 City & Guilds 2391-51 questions. Each one includes the choices, the correct answer, and an explanation, and the set is free to read with no signup.

How many City & Guilds 2391-51 flashcards are available?

The flashcard set has 32 City & Guilds 2391-51 cards. Each card shows the term and its definition.

Which topics does the City & Guilds 2391-51 study material cover?

The City & Guilds 2391-51 study material has 8 sections, including Statutory and non-statutory regulations, standards and guidance, Safe isolation, safety management and safe working practices, and Preparation for periodic inspection: documentation, extent, sampling and limitations.

What format facts does the catalog list for the City & Guilds 2391-51 exam?

The catalog lists these item types: multiple choice and practical assessment for the City & Guilds 2391-51 exam.