EPA 608 Universal Practice Test

EPA Section 608 Universal Technician Certification

EPA 608 Universal overview

  • 200 practice questions
  • 32 flashcards
  • 4 study guide topics
  • 40 key terms

What you'll study

  • Type I - small appliances25%
  • Type II - high- or very high-pressure appliances, except small appliances and MVACs25%
  • Type III - low-pressure appliances25%
  • Universal - all types of equipment25%

Section 608 Technician Certification is the credential required by EPA regulations (40 CFR Part 82, Subpart F) under Section 608 of the Clean Air Act for technicians who maintain, service, repair, or dispose of equipment that could release refrigerants into the atmosphere. The credential comes in four forms, each matched to the equipment a technician intends to work on: Type I for small appliances, Type II for high- or very high-pressure appliances other than small appliances and MVACs, Type III for low-pressure appliances, and Universal for all types of equipment. The tests for each certification type cover different topics, so the exams are not interchangeable. Candidates must pass an EPA-approved test administered by an EPA-approved certifying organization; the core test must be taken as a proctored exam to attain Universal certification, and a core test taken open-book cannot be used for Universal. Certification credentials do not expire. Preparation means studying the equipment category you will actually work on, checking test topics published by EPA, choosing an approved program (many offer on-site, remote, or online testing and some publish training manuals), and confirming proctoring arrangements in advance for Universal.

Common mistakes

Uses the same recovery cylinder for whatever refrigerant is recovered and does not label the cylinder with the refrigerant name before starting.

Recovery is rushed, cylinders look identical, and the technician assumes mixing small amounts is acceptable.

What to do instead

Use a dedicated, DOT-approved recovery cylinder for each refrigerant; label the cylinder with the refrigerant type and date before recovery; never mix refrigerants.

Stops recovery as soon as the system gauge reads 0 psig and declares the appliance empty.

The technician confuses no positive pressure with no refrigerant remaining; vapor can still be in the system at atmospheric pressure.

What to do instead

Follow the required recovery/evacuation level for the appliance category and refrigerant, and continue with the recovery machine until that level is reached, not just 0 psig.

Applies familiar high-pressure recovery rules to a low-pressure chiller and pulls it down only to 0 psig.

Low-pressure equipment operates differently and the technician uses the procedure learned for high-pressure systems.

What to do instead

Use Type III low-pressure procedures and equipment; recover to the required deep vacuum level for low-pressure appliances, such as 25 in Hg where applicable.

Uses a recovery machine or cylinder without checking that it is rated for the refrigerant and pressure involved.

The technician assumes all recovery equipment is universal, but very high-pressure refrigerants such as R-410A require higher-rated equipment.

What to do instead

Verify the recovery machine, hoses, and DOT recovery cylinder are rated for the specific refrigerant and pressure; use a scale and appropriate cylinder.

Vents refrigerant from a small appliance such as a household refrigerator or window unit because the charge is small.

The technician believes a small charge is exempt or harmless and does not treat it as regulated refrigerant.

What to do instead

Recover the refrigerant with certified small-appliance recovery equipment; intentional venting is prohibited regardless of charge size.

Overfills a recovery cylinder by filling it until it feels full or by volume rather than by weight.

Liquid refrigerant expands, and the technician ignores the cylinder fill limit or does not use a scale.

What to do instead

Weigh the recovery cylinder during filling and stop at no more than 80% of its capacity by weight.

Pressure-tests a refrigerant system with oxygen or compressed air.

Oxygen or air is readily available and seems like a convenient dry gas, but the technician does not recognize the ignition and contamination hazards.

What to do instead

Use dry nitrogen with a pressure regulator for pressure testing; never use oxygen or compressed air in a refrigerant system.

Confuses recovery, recycling, and reclaiming, such as calling refrigerant cleaned on site 'reclaimed.'

The terms sound similar and the technician has not memorized the regulatory definitions.

What to do instead

Remember: recovery means removing refrigerant; recycling means cleaning it for reuse on site; reclaiming means reprocessing to new-product specification by an EPA-certified reclaimer.

Adds refrigerant to a low-pressure chiller to fix low suction without checking the purge unit or finding the leak.

Low-pressure systems run in vacuum and can draw in air and moisture; the technician misreads low performance as simply low charge.

What to do instead

Leak-check the chiller, verify purge unit operation, check for air/moisture in the refrigerant, and repair the leak before charging.

Identifies refrigerant by gauge pressure alone and charges a system with the assumed refrigerant.

Pressure changes with temperature, and blends or mixed refrigerants make pressure-only identification unreliable.

What to do instead

Use the equipment nameplate, a refrigerant identifier, and a pressure-temperature chart with a measured temperature; never guess the refrigerant.

Exam requirements can change. Confirm current details with the exam provider.

EPA 608 Universal practice

200 questions. Each one lists the choices, the correct answer, and an explanation. With JavaScript, this list opens one question at a time. The checker at the top of this page saves progress in this browser when it is available.

  1. Question 1Type I - small appliances

    Under EPA Section 608, a small appliance is defined as an appliance charged with no more than how much refrigerant?

    1. 5 pounds Correct answer.
    2. 15 pounds
    3. 2 pounds
    4. 50 pounds

    Explanation

    Type I certification covers small appliances, which EPA defines as appliances containing 5 pounds or less of refrigerant. Appliances with larger charges fall under the Type II or Type III rules.

  2. Question 2Type I - small appliances

    A technician finishes servicing a household refrigerator and finds refrigerant left in the service hoses. What is the proper action?

    1. Recover it into a recovery cylinder Correct answer.
    2. Vent it slowly to the outdoors through a hose
    3. Release it into a plastic recovery bag
    4. Discharge it through a filter-drier to the room

    Explanation

    Section 608 prohibits knowingly venting refrigerant to the atmosphere during service, maintenance, repair, or disposal. Refrigerant trapped in hoses must be recovered or routed back into a cylinder rather than released.

  3. Question 3Type I - small appliances

    Recovery equipment that relies on the compressor inside the appliance to move refrigerant out of the system is called:

    1. system-dependent Correct answer.
    2. self-contained
    3. reclaiming
    4. passive

    Explanation

    System-dependent recovery equipment has no compressor of its own and uses the appliance's compressor and internal pressure to drive refrigerant into the recovery cylinder. Self-contained equipment carries its own compressor.

  4. Question 4Type I - small appliances

    A recovery cylinder may be filled to what maximum level?

    1. 80 percent by weight Correct answer.
    2. 85 percent by weight
    3. 100 percent by weight
    4. 90 percent by weight

    Explanation

    Recovery cylinders must be filled to no more than 80 percent of capacity by weight. The remaining 20 percent provides vapor space so liquid refrigerant can expand as it warms without overpressurizing or rupturing the cylinder.

  5. Question 5Type I - small appliances

    Which of the following is classified as a small appliance under EPA regulations?

    1. A household dehumidifier Correct answer.
    2. A centrifugal chiller holding 900 pounds
    3. An industrial freezer holding 60 pounds
    4. A supermarket rack system holding 400 pounds

    Explanation

    Small appliances include refrigerators, freezers, dehumidifiers, under-the-counter ice makers, vending machines, drinking water coolers, and room air conditioners that contain 5 pounds or less of refrigerant. Equipment with larger charges is regulated under other appliance categories.

  6. Question 6Type I - small appliances

    Before cutting into the sealed system of a small appliance, a technician must first:

    1. install a new filter-drier
    2. recover the refrigerant Correct answer.
    3. evacuate the system with a vacuum pump
    4. purge the system with nitrogen

    Explanation

    Refrigerant must be recovered from the system before any line or joint is opened, because releasing it would violate the venting prohibition. Evacuation and filter-drier replacement happen later, after the repair is complete and the system is closed again.

  7. Question 7Type I - small appliances

    How should refrigerant cylinders be stored?

    1. Upright and secured against tipping Correct answer.
    2. In a heated cabinet to maintain pressure
    3. Lying flat on a shelf
    4. In a closed vehicle for security

    Explanation

    Cylinders should be kept upright and secured so they cannot fall, which keeps liquid away from the valve outlet and protects the valve from damage. They must also be kept away from heat and out of enclosed spaces that can overheat.

  8. Question 8Type I - small appliances

    A technician adds refrigerant to a small appliance that has a known leak and no leak-repair obligation under Section 608. What should be done before or during the charge?

    1. The appliance may be charged with any refrigerant on hand
    2. The leak may be ignored because small appliances are unregulated
    3. Refrigerant may be vented until the leak is located
    4. The leak should be located and repaired before charging Correct answer.

    Explanation

    Even though the leak-rate repair and reporting rules do not apply to small appliances, good practice and the venting prohibition mean the leak should be found and corrected before recharging. Adding refrigerant to a known leak simply repeats the release.

  9. Question 9Type I - small appliances

    When recovering refrigerant from a small appliance manufactured after November 15, 1993, the recovery equipment must be capable of removing what percentage of the charge?

    1. 95 percent
    2. 70 percent
    3. 90 percent Correct answer.
    4. 80 percent

    Explanation

    Recovery equipment used on small appliances manufactured on or after November 15, 1993 must be able to remove 90 percent of the refrigerant charge. Appliances built before that date carry a lower 80 percent requirement.

  10. Question 10Type I - small appliances

    A system-dependent recovery device is used on a small appliance whose compressor will not run. What percentage of the charge must be recovered?

    1. 80 percent
    2. 100 percent
    3. 90 percent Correct answer.
    4. 50 percent

    Explanation

    With system-dependent equipment, recovery from a small appliance must reach 80 percent of the charge when the appliance compressor is operating and 90 percent when it is not.

  11. Question 11Type I - small appliances

    The Section 608 leak inspection, repair, and reporting requirements apply to appliances containing how much refrigerant?

    1. More than 15 pounds
    2. Any amount at all
    3. 50 or more pounds Correct answer.
    4. More than 5 pounds

    Explanation

    Leak-rate calculation, repair, and reporting obligations attach to appliances with a charge of 50 pounds or more. Small appliances fall below that threshold, although venting refrigerant from them remains illegal.

  12. Question 12Type I - small appliances

    What is the most accurate way to charge a small appliance with refrigerant?

    1. Watching the sight glass for bubbles
    2. Reading the suction gauge only
    3. Weighing the refrigerant into the system on a scale Correct answer.
    4. Filling until the high-side pressure matches the nameplate

    Explanation

    Small systems are critically charged, so the charge must be measured by weight with a scale according to the manufacturer's specification. Gauges and sight glasses are indirect indicators that can mislead on equipment with a small charge.

  13. Question 13Type I - small appliances

    A recovery cylinder used for small appliance refrigerant must be:

    1. a cylinder rated to 1000 psi and painted gray
    2. a pressure vessel with the relief valve removed
    3. a DOT-approved cylinder with a current test date Correct answer.
    4. a stainless steel tank labeled with the owner's name

    Explanation

    Refrigerant must be recovered into a DOT-approved recovery cylinder whose hydrostatic test date has not expired. The cylinder must also be in good condition and never filled above 80 percent by weight.

  14. Question 14Type I - small appliances

    Why should recovered refrigerant from different appliances never be mixed in one recovery cylinder?

    1. Mixing drives the cylinder pressure below atmospheric
    2. It cannot be identified or reclaimed to specification Correct answer.
    3. Mixed refrigerant will freeze and destroy the recovery machine
    4. Mixing two refrigerants always causes an immediate explosion

    Explanation

    A mixture of refrigerants cannot be identified or separated, so a reclaimer cannot restore it to specification and it may have to be destroyed. Mixing also contaminates the cylinder and any equipment the refrigerant is later run through.

  15. Question 15Type I - small appliances

    Which practice speeds recovery when a system-dependent device is used on a small appliance?

    1. Opening the appliance suction line to the atmosphere
    2. Sealing the appliance inside an insulated box
    3. Warming the recovery cylinder with an open flame
    4. Chilling the recovery cylinder in a cooler Correct answer.

    Explanation

    Cooling the recovery cylinder lowers its internal pressure, which increases the pressure difference driving refrigerant out of the appliance and into the cylinder. Heating the appliance slightly can also help, but an open flame must never be used.

  16. Question 16Type I - small appliances

    A refrigerant identifier is used to:

    1. locate small leaks in the evaporator coil
    2. confirm the refrigerant type and its purity Correct answer.
    3. measure the moisture content of the compressor oil
    4. weigh the total refrigerant charge in the system

    Explanation

    An identifier analyzes refrigerant vapor to determine which refrigerant is present and whether it is contaminated. This prevents mixing incompatible refrigerants and helps detect counterfeit or contaminated refrigerant before recovery.

  17. Question 17Type I - small appliances

    Refrigerant that has been recovered and cleaned of oil, moisture, and other contaminants so it can be reused is called:

    1. virgin refrigerant
    2. recycled refrigerant Correct answer.
    3. azeotropic refrigerant
    4. reclaimed refrigerant

    Explanation

    Recycling removes contaminants such as oil and moisture from recovered refrigerant so it can be put back into the same system or another system of the same owner. Reclaiming goes further, reprocessing the refrigerant to the purity of new product at a certified facility.

  18. Question 18Type I - small appliances

    To calculate how much refrigerant has been recovered into a cylinder, a technician needs the cylinder's:

    1. relief valve setting
    2. internal volume in cubic feet
    3. hydrostatic test pressure
    4. tare weight Correct answer.

    Explanation

    Tare weight is the weight of the empty cylinder. Subtracting it from the gross weight on the scale gives the weight of refrigerant inside, which is how fill level and recovered amount are determined.

  19. Question 19Type I - small appliances

    On a small appliance with no service valves, refrigerant is recovered by:

    1. installing a piercing-type access valve on the process tube Correct answer.
    2. opening the capillary tube and catching refrigerant in a bag
    3. cutting the process tube with a tubing cutter while the system runs
    4. heating the compressor sump until the charge boils off

    Explanation

    Sealed systems without service ports are accessed with a clamp-on piercing valve installed on the process stub, and refrigerant is recovered through that valve before the system is opened. Cutting lines while a charge is present would release refrigerant.

  20. Question 20Type I - small appliances

    A small appliance must have its refrigerant recovered, but its compressor will not run. What should the technician do?

    1. Vent the charge, since the appliance is being scrapped
    2. Bypass the compressor overload to force it to run
    3. Use a self-contained recovery machine Correct answer.
    4. Seal the lines and send the appliance to a landfill

    Explanation

    System-dependent recovery cannot work when the appliance compressor is inoperative, so a self-contained recovery machine must be used to pull the charge out. Applying power to a failed compressor or venting the charge is never acceptable.

  21. Question 21Type I - small appliances

    A household refrigerator is being scrapped. What must happen to its refrigerant?

    1. It may be vented to the atmosphere because the appliance is being destroyed.
    2. Only the compressor oil must be drained; the refrigerant may be released.
    3. It must be recovered before the appliance is dismantled. Correct answer.
    4. It may be vented to the atmosphere if the charge is under one pound.

    Explanation

    Section 608 requires refrigerant to be recovered from appliances before they are dismantled or discarded, and the venting prohibition applies even to equipment being destroyed. Draining oil does not remove refrigerant from the sealed circuit.

  22. Question 22Type I - small appliances

    Recovery and recycling equipment used on small appliances must be:

    1. rebuilt from components listed by the appliance maker
    2. certified to EPA standards by an independent lab Correct answer.
    3. registered with the local fire marshal before each use
    4. inspected annually by a state environmental agency

    Explanation

    EPA requires recovery and recycling equipment to be certified by an independent testing organization, such as UL, as meeting the recovery efficiency standard for the type of appliance being serviced. Certification applies to equipment designed for small appliances as well as other categories.

  23. Question 23Type I - small appliances

    A technician uses a system-dependent recovery device on a small appliance whose compressor runs normally. Recovery is considered complete when:

    1. the recovery cylinder stops gaining weight on the scale
    2. the appliance has been pulled down to a 500-micron vacuum
    3. 80 percent of the charge has been recovered Correct answer.
    4. the suction line feels warm and the low-side gauge reads zero

    Explanation

    For system-dependent recovery from a small appliance, the required endpoint is 80 percent of the refrigerant charge when the appliance compressor is operating. When the compressor is not operating, 90 percent must be recovered and a self-contained machine is normally needed.

  24. Question 24Type I - small appliances

    After a repair has been completed on a small appliance, air and moisture are removed from the system by:

    1. flushing the system with CFC-12 vapor
    2. adding nitrogen and leaving it in the system
    3. opening the suction line to room air
    4. evacuating the system with a vacuum pump Correct answer.

    Explanation

    Evacuation with a vacuum pump lowers the system pressure so that non-condensables are drawn out and trapped moisture boils off. Refrigerant must never be used to purge or blow out a system, because that practice releases refrigerant to the atmosphere.

  25. Question 25Type I - small appliances

    A technician certified only as Type I may legally perform service that involves which of the following?

    1. A centrifugal chiller using R-123
    2. A household refrigerator containing 4 pounds of R-134a Correct answer.
    3. A commercial rooftop unit containing 30 pounds of R-410A
    4. An automobile air-conditioning system using R-134a

    Explanation

    Type I certification covers small appliances, which are hermetically sealed, factory-charged appliances containing 5 pounds or less of refrigerant. A household refrigerator with 4 pounds falls within that category. Rooftop units and chillers require Type II or Type III certification, and motor vehicle air conditioning is covered under Section 609.

  26. Question 26Type I - small appliances

    What must be done with refrigerant removed from a small appliance that is being repaired?

    1. It may be vented only if the appliance is being scrapped.
    2. It may be vented if the charge is less than 5 pounds.
    3. It may be discharged into a sealed container of water.
    4. It must be recovered and not released to the atmosphere. Correct answer.

    Explanation

    Section 608 prohibits venting refrigerant to the atmosphere, so refrigerant removed during service must be recovered. The 5-pound small-appliance charge size does not create an exception that allows venting. Releasing refrigerant into water or venting it because the appliance is being scrapped is also prohibited.

  27. Question 27Type I - small appliances

    Why should a recovery cylinder never be filled completely with liquid refrigerant?

    1. Refrigerant will change color when compressed.
    2. The cylinder becomes too heavy to move safely.
    3. Liquid refrigerant expands with temperature and can overpressurize the cylinder. Correct answer.
    4. The recovery machine cannot pump into a full cylinder.

    Explanation

    Recovery cylinders must be filled by weight and left with vapor space because liquid refrigerant expands as it warms. Overfilling can cause hydrostatic pressure high enough to rupture the cylinder. Standard practice limits filling to about 80 percent of the cylinder capacity.

  28. Question 28Type I - small appliances

    What is the standard color marking for a DOT refrigerant recovery cylinder?

    1. Gray body with a yellow top Correct answer.
    2. White body with a blue stripe
    3. Solid red with a black top
    4. Solid green with a white band

    Explanation

    DOT recovery cylinders are commonly gray with a yellow top so they can be identified as recovery containers. The color marking helps prevent recovered refrigerant from being confused with virgin refrigerant cylinders.

  29. Question 29Type I - small appliances

    Which method is appropriate for locating a refrigerant leak on a small appliance?

    1. Smelling the refrigerant at the service port
    2. Using an electronic leak detector Correct answer.
    3. Pressurizing with oxygen and watching for bubbles
    4. Holding an open flame near the tubing

    Explanation

    Electronic leak detectors and soap-bubble solutions are safe and effective ways to locate refrigerant leaks. Open flames and oxygen must never be used because they create fire and contamination hazards. Refrigerant odor is not a reliable or safe leak-detection method.

  30. Question 30Type I - small appliances

    Which gas should be used to pressurize a small appliance for leak testing?

    1. Acetylene
    2. Compressed air from a shop compressor
    3. Dry nitrogen Correct answer.
    4. Oxygen

    Explanation

    Dry nitrogen is inert and does not introduce moisture into the refrigeration system, making it the preferred leak-testing gas. Compressed air can contain moisture and oil, while oxygen and acetylene create serious fire or explosion hazards.

  31. Question 31Type I - small appliances

    Why is a vacuum pump used instead of the appliance's own compressor to evacuate a small appliance?

    1. The vacuum pump automatically recharges the system.
    2. The appliance compressor cannot run without a refrigerant charge.
    3. The appliance compressor is not designed to pull a deep vacuum. Correct answer.
    4. A vacuum pump heats the refrigerant for reuse.

    Explanation

    A refrigeration compressor is designed to pump refrigerant, not to evacuate a system to a deep vacuum. Using it as a vacuum pump can overheat it and damage the compressor. A dedicated vacuum pump is required to remove air and moisture properly.

  32. Question 32Type I - small appliances

    Which instrument is used to measure the vacuum level during evacuation of a small appliance?

    1. A refrigerant scale
    2. A micron gauge Correct answer.
    3. An electronic leak detector
    4. A manifold gauge set high-side gauge

    Explanation

    A micron gauge measures deep vacuum accurately, which is necessary to confirm that air and moisture have been removed. Standard manifold gauges are not precise enough at the low absolute pressures used during evacuation.

  33. Question 33Type I - small appliances

    What distinguishes a self-contained recovery machine from a system-dependent recovery device?

    1. It works only on appliances with no service valves.
    2. It uses the appliance's compressor to move refrigerant.
    3. It has its own compressor to move refrigerant. Correct answer.
    4. It does not require a recovery cylinder.

    Explanation

    A self-contained, or system-independent, recovery machine has its own compressor and can recover refrigerant even if the appliance compressor is not operating. A system-dependent device relies on the appliance's compressor to move refrigerant.

  34. Question 34Type I - small appliances

    Which process produces refrigerant that has been analyzed and certified to meet AHRI Standard 700?

    1. Reclaiming Correct answer.
    2. Recycling
    3. Evacuating
    4. Recovering

    Explanation

    Reclaiming requires chemical analysis and processing to restore refrigerant to AHRI Standard 700 purity. Recycling is a simpler cleaning process and does not include the laboratory certification required for reclaimed refrigerant.

  35. Question 35Type I - small appliances

    Which heat source is acceptable for warming a small appliance during refrigerant recovery?

    1. An open torch flame
    2. A heat gun set to maximum
    3. Warm water Correct answer.
    4. A space heater placed directly against the cabinet

    Explanation

    Warm water or another gentle heat source can be used to help move refrigerant out of a small appliance without creating a fire hazard. Open flames and excessive heat can damage the appliance or overpressurize the system.

  36. Question 36Type I - small appliances

    Which refrigerant state is generally recovered faster from a small appliance?

    1. Liquid refrigerant Correct answer.
    2. Superheated vapor
    3. A mixture of air and vapor
    4. Refrigerant vapor at low pressure

    Explanation

    Liquid refrigerant contains much more mass per unit volume than vapor, so recovering it as a liquid is generally faster. Vapor recovery is slower because the recovery machine must compress a low-density gas.

  37. Question 37Type I - small appliances

    When charging a small appliance with a zeotropic refrigerant blend, the refrigerant should be withdrawn from the cylinder as:

    1. A superheated gas
    2. A vapor
    3. A liquid Correct answer.
    4. A mixture of liquid and vapor

    Explanation

    Zeotropic blends fractionate, meaning their components can separate when vapor is withdrawn. Charging as a liquid helps maintain the correct refrigerant composition.

  38. Question 38Type I - small appliances

    What is the purpose of low-loss fittings on recovery hoses?

    1. They allow the cylinder to be filled to 100 percent.
    2. They increase the recovery rate by heating the refrigerant.
    3. They filter moisture from the refrigerant.
    4. They reduce refrigerant release when hoses are disconnected. Correct answer.

    Explanation

    Low-loss fittings are designed to minimize refrigerant released when hoses are connected or disconnected. They do not heat refrigerant, filter moisture, or permit overfilling of the recovery cylinder.

  39. Question 39Type I - small appliances

    How should used compressor oil removed from a small appliance be handled?

    1. Spread on the ground outdoors to evaporate
    2. Poured into a floor drain with plenty of water
    3. Mixed with the recovered refrigerant in the recovery cylinder
    4. Collected and disposed of according to local and federal regulations Correct answer.

    Explanation

    Used compressor oil is a regulated waste and must be collected and disposed of properly. It must not be poured down drains, spread outdoors, or mixed with recovered refrigerant.

  40. Question 40Type I - small appliances

    After evacuating a small appliance, the technician isolates the vacuum pump and the micron gauge rises quickly from 500 to 2000 microns. What does this most likely indicate?

    1. The vacuum pump oil is new.
    2. A leak or moisture is present in the system. Correct answer.
    3. The system is fully dehydrated and ready to charge.
    4. The micron gauge is out of calibration.

    Explanation

    A rapid rise in pressure after isolation indicates that air is entering through a leak or that moisture is vaporizing in the system. A fully dehydrated system should hold a low vacuum without a fast rise. The technician should find and correct the cause before charging.

  41. Question 41Type I - small appliances

    A small refrigerator has a heavy frost pattern on the suction line at the evaporator outlet. Which condition is most likely?

    1. Low refrigerant charge or a restriction Correct answer.
    2. Too much compressor oil
    3. Overcharge of refrigerant
    4. A disconnected defrost heater

    Explanation

    A low charge or a restriction lowers suction pressure and temperature, which can cause heavy frost or ice to form on the suction line. An overcharge would typically raise pressures rather than create this low-pressure frost pattern.

  42. Question 42Type I - small appliances

    Following a compressor burnout in a small appliance, which test helps determine whether acid remains in the system?

    1. An acid test of the compressor oil Correct answer.
    2. A soap-bubble leak check
    3. A nitrogen pressure test
    4. A micron gauge reading

    Explanation

    Compressor burnout can produce acids in the system, and an acid test of the oil helps determine whether contamination remains. Pressure, vacuum, and leak tests do not measure acid levels.

  43. Question 43Type I - small appliances

    Why should a refrigerant cylinder never be heated with an open flame?

    1. The pressure can rise enough to rupture the cylinder. Correct answer.
    2. The cylinder label will become unreadable.
    3. The flame will change the refrigerant's boiling point.
    4. The refrigerant will leak through the valve stem.

    Explanation

    Heating a refrigerant cylinder raises its internal pressure, and an open flame can cause dangerous overpressurization or rupture. Warm water is the acceptable gentle heat source when heating is needed.

  44. Question 44Type I - small appliances

    What information should be marked on a cylinder containing recovered refrigerant?

    1. The type of refrigerant and the date of recovery Correct answer.
    2. The EPA certification exam score
    3. The technician's home address
    4. The date the appliance was manufactured

    Explanation

    Recovered refrigerant cylinders should be labeled with the refrigerant type and recovery date so the contents are not misidentified or mixed. Proper labeling helps ensure the refrigerant is handled and reused or reclaimed correctly.

  45. Question 45Type I - small appliances

    Under EPA Section 608, who may purchase refrigerant for servicing small appliances?

    1. A properly certified technician Correct answer.
    2. Only the appliance owner
    3. Any hardware store employee
    4. Any person with a valid driver's license

    Explanation

    Section 608 requires technicians who service refrigeration equipment to be certified, and refrigerant sales to service technicians are restricted to certified persons. A driver's license, appliance ownership, or retail employment does not satisfy the certification requirement.

  46. Question 46Type I - small appliances

    Why should a technician ventilate the work area when recovering refrigerant from a small appliance?

    1. To keep the vacuum pump oil cool
    2. To avoid inhaling refrigerant vapors Correct answer.
    3. To prevent the recovery cylinder from rusting
    4. To increase the recovery speed

    Explanation

    Refrigerant vapors can displace oxygen and cause dizziness or other health effects, so the work area should be well ventilated. Ventilation does not speed recovery, prevent cylinder rust, or cool vacuum pump oil.

  47. Question 47Type I - small appliances

    Why should liquid refrigerant be prevented from entering the compressor of a small appliance during system-dependent recovery?

    1. Liquid refrigerant cannot be recovered.
    2. Liquid refrigerant will freeze the recovery cylinder.
    3. Liquid refrigerant turns into air.
    4. Liquid can damage the compressor valves. Correct answer.

    Explanation

    Liquid refrigerant entering a running compressor can cause slugging, which may bend or break compressor valves. System-dependent recovery should control the rate so refrigerant returns to the compressor as vapor.

  48. Question 48Type I - small appliances

    The oil in a vacuum pump turns milky after evacuating a small appliance. What does this indicate?

    1. The pump is operating at peak efficiency.
    2. Moisture has contaminated the pump oil. Correct answer.
    3. The micron gauge is reading inaccurately.
    4. The system has a refrigerant overcharge.

    Explanation

    Milky vacuum-pump oil usually indicates that the pump has absorbed moisture from the system. The oil should be changed, and the evacuation may need to be repeated to remove remaining moisture.

  49. Question 49Type I - small appliances

    A technician recovers refrigerant from a small appliance and cannot verify its purity. What is the proper disposition of the refrigerant?

    1. Install it in another appliance of the same type.
    2. Mix it with new refrigerant to dilute impurities.
    3. Vent it slowly outdoors.
    4. Send it to a reclaiming facility for analysis. Correct answer.

    Explanation

    Refrigerant of unknown purity must be sent to a reclaiming facility for analysis and processing before reuse. It cannot be installed in another appliance, vented, or diluted with new refrigerant.

  50. Question 50Type I - small appliances

    A technician is recovering refrigerant from several small appliances into an empty DOT-approved recovery cylinder. Which filling practice is required?

    1. Stop filling when the cylinder reaches 80 percent of its capacity by weight Correct answer.
    2. Stop filling when the cylinder reaches 90 percent of its capacity by weight
    3. Stop filling when the cylinder's gross weight equals its tare weight
    4. Fill the cylinder completely, since recovery cylinders are built for liquid-full storage

    Explanation

    Recovery cylinders must be limited to 80 percent of their capacity by weight so that headspace remains for liquid expansion as the cylinder warms. Overfilling can hydrostatically stress the cylinder and cause it to rupture or relieve refrigerant through the safety device.

  51. Question 51Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A technician recovers refrigerant from a residential split system built in 1998 that holds 12 pounds of R-22. What is the minimum percentage of the charge that must be recovered?

    1. 70 percent of the charge
    2. 80 percent of the charge
    3. 90 percent of the charge Correct answer.
    4. 100 percent of the charge

    Explanation

    High-pressure appliances manufactured after November 15, 1993 must have at least 90 percent of their refrigerant recovered before the system is opened. The 80 percent figure applies to appliances built before that date. Evacuating the appliance to the required vacuum level is an alternative way to comply.

  52. Question 52Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A high-pressure appliance manufactured after November 15, 1993 contains 250 pounds of R-134a. To what vacuum level must it be evacuated before it is opened?

    1. 10 inches of mercury
    2. 0 inches of mercury
    3. 15 inches of mercury Correct answer.
    4. 4 inches of mercury

    Explanation

    Appliances manufactured after November 15, 1993 that hold 200 pounds or more must be evacuated to 15 inches of mercury vacuum. Appliances under 200 pounds built after that date need only 10 inches of mercury. The 4 inch level applies to small appliances.

  53. Question 53Type II - high- or very high-pressure appliances, except small appliances and MVACs

    In Section 608 terminology, what does recovering refrigerant mean?

    1. Processing refrigerant to remove oil and moisture
    2. Testing refrigerant against ARI-700 specifications
    3. Transferring refrigerant into an external container Correct answer.
    4. Reusing refrigerant in the same appliance

    Explanation

    Recovery is the act of removing refrigerant from an appliance and storing it in an external container, whether or not it is later cleaned or tested. Recycling means cleaning the refrigerant for reuse, and reclamation means processing it to ARI-700 purity.

  54. Question 54Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A technician needs a container for refrigerant just removed from a rooftop unit. Which container is acceptable?

    1. A DOT-approved recovery cylinder Correct answer.
    2. A container approved only for compressed air
    3. A refillable cylinder labeled for a different refrigerant
    4. The disposable cylinder the virgin refrigerant came in

    Explanation

    Recovered refrigerant must be stored in DOT-approved recovery cylinders built for reuse. Disposable cylinders are not designed to be refilled and can rupture, and putting refrigerant into a cylinder labeled for another refrigerant creates a mixture that cannot be reclaimed.

  55. Question 55Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which is the correct way to pressure test a repaired high-pressure system for leaks?

    1. Refrigerant vapor from a supply cylinder
    2. Oxygen from a welding regulator
    3. Dry nitrogen through a pressure regulator Correct answer.
    4. Shop compressed air

    Explanation

    Dry nitrogen is inert, non-flammable, and free of moisture, which makes it safe for pressure testing. Oxygen can explode when combined with compressor oil, and compressed air carries moisture and oil that contaminate the system.

  56. Question 56Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Why is dry nitrogen flowed through the tubing while brazing joints?

    1. To prevent oxidation inside the tubing Correct answer.
    2. To detect leaks as the joint is heated
    3. To speed the cooling of the joint
    4. To raise the internal pressure for leak checks

    Explanation

    Oxygen in the air inside open tubing forms scale when heated by a torch, and that scale travels through the system and damages compressors and metering devices. A low flow of dry nitrogen displaces the air during brazing.

  57. Question 57Type II - high- or very high-pressure appliances, except small appliances and MVACs

    When recovering refrigerant from a system, which portion of the charge should be removed first?

    1. Compressor oil
    2. Non-condensable gases
    3. Liquid refrigerant Correct answer.
    4. Refrigerant vapor

    Explanation

    Recovering liquid first removes most of the charge quickly, because liquid recovery is far faster than vapor recovery. Vapor is removed after the liquid has been taken out, and oil is never drained as a recovery step.

  58. Question 58Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A recovery cylinder is found to contain a mixture of two different refrigerants. What must be done with it?

    1. Vent it slowly outdoors
    2. Add it to a cylinder of virgin refrigerant
    3. Send it to a reclaimer labeled as mixed refrigerant Correct answer.
    4. Use it in any system that uses one of the two refrigerants

    Explanation

    Mixed refrigerant cannot be separated in the field, so it must be sent to a reclamation facility and clearly labeled as a mixture. It may not be vented, blended with virgin refrigerant, or installed in equipment.

  59. Question 59Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Before opening a 1996 condensing unit that holds 80 pounds of R-22, the technician must evacuate it to at least:

    1. 20 inches of mercury vacuum
    2. 15 inches of mercury vacuum
    3. 10 inches of mercury vacuum Correct answer.
    4. 4 inches of mercury vacuum

    Explanation

    Appliances manufactured after November 15, 1993 with a charge under 200 pounds must be evacuated to 10 inches of mercury vacuum. The 15 inch level applies only when the appliance holds 200 pounds or more.

  60. Question 60Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A commercial refrigeration appliance holding 120 pounds of R-404A is found to be leaking. Under Section 608, the leak must be repaired within:

    1. 90 days
    2. 30 days Correct answer.
    3. 1 year
    4. 60 days

    Explanation

    Appliances with a charge of 50 pounds or more must be repaired within 30 days of discovering a leak, and the repair must be verified within 30 days after that. Appliances below the 50 pound threshold have no federal repair deadline.

  61. Question 61Type II - high- or very high-pressure appliances, except small appliances and MVACs

    The owner of a high-pressure appliance must keep records of refrigerant purchased and added when the appliance charge is at least:

    1. 50 pounds Correct answer.
    2. 15 pounds
    3. 5 pounds
    4. 200 pounds

    Explanation

    Section 608 requires owners and operators of appliances containing 50 pounds or more of refrigerant to keep records of refrigerant purchased and added, and to make those records available to EPA on request. Smaller appliances carry no such federal record-keeping duty.

  62. Question 62Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Passive (system-dependent) recovery equipment may be used on a high-pressure appliance only if the charge does not exceed:

    1. 200 pounds
    2. 50 pounds
    3. 5 pounds
    4. 15 pounds Correct answer.

    Explanation

    System-dependent recovery relies on the appliance's own compressor and internal pressure to move refrigerant, so the rules limit its use to appliances holding 15 pounds or less. Such appliances must also have an operating compressor.

  63. Question 63Type II - high- or very high-pressure appliances, except small appliances and MVACs

    When adding refrigerant to an operating system that has a receiver, the refrigerant should be charged as:

    1. Liquid into the suction service valve
    2. Vapor into the suction line
    3. Vapor into the discharge line
    4. Liquid into the liquid line Correct answer.

    Explanation

    A system with a receiver can accept liquid refrigerant through the liquid line while it operates, because the receiver buffers the charge and the metering device handles liquid. Liquid introduced at the suction service valve can slug and destroy the compressor.

  64. Question 64Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Refrigerant recovered from one customer's system may be installed in a different customer's equipment only after it has been:

    1. Stored for at least 30 days
    2. Tested with a halide torch
    3. Filtered through a suction line drier
    4. Reclaimed to ARI-700 standards Correct answer.

    Explanation

    Recovered refrigerant may go back into equipment owned by the same person, but moving it to another owner's equipment requires reclamation, which restores it to ARI-700 purity. Field filtering alone does not meet that requirement.

  65. Question 65Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which instrument shows the deep vacuum level reached during evacuation?

    1. A compound gauge
    2. An electronic leak detector
    3. A micron gauge Correct answer.
    4. A charging scale

    Explanation

    A micron gauge measures absolute pressure in the deep vacuum range where manifold gauges are useless. Reaching the target micron level and holding it proves the system is dry and free of leaks.

  66. Question 66Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Air that has been drawn into a high-pressure system will most likely cause:

    1. Lower suction superheat than normal
    2. Higher head pressure and higher current draw Correct answer.
    3. Lower head pressure than the system normally shows
    4. A condenser coil that runs colder than normal

    Explanation

    Air is non-condensable, so it collects in the condenser and occupies volume that refrigerant would otherwise use, raising head pressure and compressor current draw. It is removed by recovering the charge, evacuating, and recharging.

  67. Question 67Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Before starting a compressor after service, the technician must verify that:

    1. Both service valves are open Correct answer.
    2. The suction valve open and the discharge valve closed
    3. Both service valves front-seated
    4. The crankcase heater disconnected

    Explanation

    A compressor started with a closed discharge valve has nowhere to pump and can be damaged or ruptured. Both service valves must be open, and the crankcase heater should be energized ahead of startup.

  68. Question 68Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is required when recovering R-410A from a rooftop unit?

    1. A halide torch to confirm the refrigerant type
    2. The same equipment and hoses used for R-22
    3. Recovery equipment only if the charge exceeds 50 pounds
    4. Equipment and hoses rated for R-410A pressures Correct answer.

    Explanation

    R-410A operates at substantially higher pressures than R-22, so recovery machines, hoses, and gauges must be rated for it. Hoses and gauges intended only for R-22 can burst at R-410A pressures.

  69. Question 69Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is the main danger of leaving moisture in a refrigeration system?

    1. It lowers the compressor discharge temperature
    2. It improves lubricant circulation
    3. It forms acid and ices the metering device Correct answer.
    4. It raises the evaporator pressure

    Explanation

    Moisture reacts with refrigerant and oil to form acids that attack motor windings and bearings, and it can freeze at the metering device and block refrigerant flow. That is why systems are evacuated to a deep vacuum and fitted with filter driers.

  70. Question 70Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which method is best for pinpointing a small leak on an R-410A system?

    1. A halide torch
    2. Waiting for the system to lose its full charge
    3. Smelling for refrigerant odor
    4. An electronic leak detector Correct answer.

    Explanation

    Electronic leak detectors are sensitive to HFC refrigerants and can pinpoint small leaks. Halide torches depend on chlorine in the refrigerant, so they do not respond to HFCs such as R-410A.

  71. Question 71Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A recovery cylinder has a water capacity of 47.5 pounds and a tare weight of 22 pounds. What is the maximum total weight of the cylinder when it is properly filled with recovered refrigerant?

    1. 60 pounds Correct answer.
    2. 69.5 pounds
    3. 47.5 pounds
    4. 38 pounds

    Explanation

    A recovery cylinder may be filled to 80 percent of its water capacity: 0.80 times 47.5 equals 38 pounds of refrigerant. Adding the 22 pound tare weight gives a maximum scale reading of 60 pounds.

  72. Question 72Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Why must R-410A be charged into a system as a liquid?

    1. Because its cylinder contains a dip tube
    2. Because it is a blend that can fractionate Correct answer.
    3. Because liquid charging is faster than vapor charging
    4. Because the compressor will not accept vapor

    Explanation

    R-410A is a near-azeotropic blend whose components have slightly different volatilities. Withdrawing vapor can change the composition of what remains in the cylinder, so the blend must be charged as a liquid, usually into the liquid line.

  73. Question 73Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which appliance may be serviced by a technician holding only Type II certification?

    1. A centrifugal chiller using R-123
    2. A household refrigerator that is factory sealed
    3. A 25-ton packaged rooftop unit using R-410A Correct answer.
    4. An automobile air conditioner

    Explanation

    Type II certification covers high-pressure and very high-pressure appliances other than small appliances and motor vehicle air conditioners. Packaged rooftop units fall in that category, while household refrigerators are small appliances and R-123 chillers are low-pressure appliances.

  74. Question 74Type II - high- or very high-pressure appliances, except small appliances and MVACs

    After replacing a compressor that failed due to a burnout, what should the technician do?

    1. Install a suction line filter drier and check its pressure drop Correct answer.
    2. Add a second charge of refrigerant to dilute the acid
    3. Change only the liquid line drier, then put the system back in service
    4. Flush the system with water and then evacuate it thoroughly

    Explanation

    A burnout leaves acid and sludge throughout the system, so a suction line filter drier is installed to capture debris and its pressure drop is checked after a period of operation. The liquid line drier is also replaced, and the filter may need to be changed again.

  75. Question 75Type II - high- or very high-pressure appliances, except small appliances and MVACs

    An appliance using R-23 as its refrigerant requires:

    1. Evacuation only to 0 inches of mercury
    2. The same equipment used for R-134a systems
    3. Equipment rated for very high pressures Correct answer.
    4. No recovery because the charge is factory sealed

    Explanation

    R-23 is a very high-pressure refrigerant, so recovery machines, hoses, and cylinders must be rated for those pressures. Very high-pressure appliances fall under Type II certification and recovery is still required when they are opened.

  76. Question 76Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is the primary function of the filter-drier in a refrigeration system?

    1. Remove moisture and trap solid contaminants from the refrigerant Correct answer.
    2. Reduce the pressure of the liquid refrigerant before the metering device
    3. Store liquid refrigerant during periods of high load
    4. Separate oil from the refrigerant vapor leaving the evaporator

    Explanation

    A filter-drier contains a desiccant that absorbs moisture and a screen or core that traps solid particles, protecting the metering device and compressor from contamination. Moisture and debris are the two most common causes of repeat failures in a high-pressure system.

  77. Question 77Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which component prevents liquid refrigerant from entering the compressor on a system that may flood during operation?

    1. Suction line accumulator Correct answer.
    2. King valve
    3. Liquid line solenoid
    4. Receiver

    Explanation

    An accumulator is installed in the suction line to catch liquid refrigerant and allow it to boil off as vapor before it reaches the compressor. Liquid entering a compressor causes slugging and dilutes the lubricating oil.

  78. Question 78Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which personal protective equipment is essential when there is a risk of liquid refrigerant contacting the skin or eyes?

    1. Leather work gloves and a plastic hard hat
    2. Cotton work gloves and a cloth dust mask
    3. Refrigerant-rated gloves and a face shield Correct answer.
    4. Safety glasses and ordinary leather work shoes

    Explanation

    Liquid refrigerant boils at extremely low temperatures and can cause severe frostbite or eye damage on contact. Gloves that resist refrigerant and eye or face protection are required whenever lines or cylinders may release liquid.

  79. Question 79Type II - high- or very high-pressure appliances, except small appliances and MVACs

    How often must a DOT recovery cylinder be hydrostatically tested?

    1. Every 10 years
    2. Every 2 years
    3. Every 5 years Correct answer.
    4. Every year

    Explanation

    DOT regulations require recovery cylinders to be hydrostatically tested every five years to confirm the shell can still withstand the pressures it will see in service. A cylinder past its test date must not be filled.

  80. Question 80Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Why must a technician never use a disposable refrigerant cylinder to hold recovered refrigerant?

    1. It is not built to be refilled and may rupture Correct answer.
    2. It is too heavy to be weighed accurately on a scale
    3. It will absorb moisture from the air through the valve
    4. It cannot be connected to a gauge manifold set

    Explanation

    Disposable cylinders are manufactured and tested as one-way containers and are not designed for refilling. Filling one with recovered refrigerant can cause the shell to rupture or leak, and the refrigerant inside cannot be safely stored or transported.

  81. Question 81Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is the purpose of a crankcase heater on a compressor?

    1. To keep the oil warm so refrigerant cannot migrate Correct answer.
    2. To boil off moisture that has entered the crankcase
    3. To warm the suction vapor so the compressor can build capacity
    4. To raise the discharge pressure when the outdoor ambient is low

    Explanation

    During the off cycle, refrigerant can condense in the crankcase and dilute the oil. The crankcase heater keeps the oil warmer than the coldest part of the system so refrigerant stays out of the oil and does not cause slugging at startup.

  82. Question 82Type II - high- or very high-pressure appliances, except small appliances and MVACs

    On a manifold gauge set, the low-pressure (compound) gauge is connected to the:

    1. Receiver outlet valve
    2. Discharge service valve
    3. Liquid line service port
    4. Suction service valve Correct answer.

    Explanation

    The compound gauge reads pressures at or below atmospheric and is connected to the suction service valve so the technician can observe suction pressure. The high-pressure gauge connects to the discharge or liquid side of the system.

  83. Question 83Type II - high- or very high-pressure appliances, except small appliances and MVACs

    How should refrigerant cylinders be stored at a job site?

    1. Upright, secured, and away from heat sources Correct answer.
    2. Laid on their side to save space in the truck
    3. Inside the equipment room next to the compressor
    4. In direct sunlight to keep the cylinder pressure up

    Explanation

    Cylinders should be stored upright, blocked or strapped so they cannot tip, and kept away from flames, heat, and direct sun that would raise internal pressure. Heat also raises the risk of the relief device discharging refrigerant.

  84. Question 84Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A high-pressure appliance manufactured in 1991 holds 250 pounds of R-22. Before it is opened for repair, the technician must evacuate it to at least:

    1. 5 inches of mercury vacuum
    2. 10 inches of mercury vacuum Correct answer.
    3. 2 psig
    4. 0 psig

    Explanation

    Section 608 requires a 10 inch mercury vacuum before opening a high-pressure appliance that contains 200 pounds or more of refrigerant or was manufactured before November 15, 1993. Smaller appliances built after that date need only be reduced to 0 psig.

  85. Question 85Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Recovery equipment manufactured after November 15, 1993 must be capable of recovering what percentage of the refrigerant charge from a high-pressure appliance?

    1. 95 percent
    2. 80 percent
    3. 90 percent Correct answer.
    4. 100 percent

    Explanation

    EPA sets recovery efficiency at 80 percent for equipment built before November 15, 1993 and 90 percent for equipment built on or after that date. The certified technician must know the age of the recovery unit because it determines the required efficiency.

  86. Question 86Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which procedure is used to remove moisture and noncondensables from a system that has been open to the atmosphere?

    1. Triple evacuation, breaking the vacuum with dry nitrogen Correct answer.
    2. Purging the system with compressed air from the shop compressor
    3. A single long evacuation down to 1,000 microns
    4. Flushing the system with liquid refrigerant

    Explanation

    Triple evacuation breaks the vacuum with dry nitrogen several times so moisture trapped in the system is absorbed by the dry gas and carried out with each evacuation. This lets the system reach a deep, stable vacuum that a single pull-down cannot achieve.

  87. Question 87Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Bubbles in the liquid-line sight glass of a system operating at a steady load most likely indicate:

    1. The system is overcharged and liquid is backing into the condenser
    2. The evaporator is flooding with liquid refrigerant at part load
    3. Flash gas in the liquid line from a low charge or a restriction Correct answer.
    4. The crankcase heater has failed and the oil is cold

    Explanation

    A bubbling sight glass means liquid refrigerant is flashing to vapor before it reaches the metering device, usually because the charge is low or the liquid line is restricted. The cause must be found before adding refrigerant so an overcharge is not created.

  88. Question 88Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is the most accurate way to charge a critically charged packaged system?

    1. Weigh the refrigerant in according to the nameplate charge Correct answer.
    2. Charge until the sight glass is completely clear
    3. Charge until the suction line is sweating back to the compressor
    4. Charge until the head pressure matches the design value

    Explanation

    Critically charged systems have no receiver to absorb error, so the charge listed on the nameplate must be weighed in with a scale. Charging by sight glass or by feel leaves the system overcharged or undercharged.

  89. Question 89Type II - high- or very high-pressure appliances, except small appliances and MVACs

    On a system with a thermostatic expansion valve, subcooling measured at the condenser outlet is used to:

    1. Determine the airflow through the evaporator coil
    2. Set the superheat at the evaporator coil
    3. Confirm the system has the correct liquid charge Correct answer.
    4. Check whether the compressor valves are leaking

    Explanation

    A TXV holds evaporator superheat on its own, so charge is verified with subcooling at the condenser outlet compared with the manufacturer's target. Low subcooling suggests an undercharge and high subcooling suggests an overcharge or a liquid line restriction.

  90. Question 90Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which valve is used to isolate the receiver from the liquid line?

    1. King valve Correct answer.
    2. Suction service valve
    3. Hot gas bypass valve
    4. Relief valve

    Explanation

    The king valve is the manual valve at the receiver outlet. Closing it traps liquid in the receiver so the liquid line, filter-drier, or metering device can be serviced or the system pumped down.

  91. Question 91Type II - high- or very high-pressure appliances, except small appliances and MVACs

    What is the purpose of a pump-down cycle controlled by a low-pressure switch?

    1. To move refrigerant into the receiver before shutdown Correct answer.
    2. To remove noncondensables from the receiver during operation
    3. To raise suction pressure before the next startup
    4. To defrost the evaporator coil at the end of a cycle

    Explanation

    Pump-down closes the liquid line solenoid and lets the compressor run until the low-pressure switch stops it, which stores the refrigerant in the receiver. The evaporator and suction line are left nearly empty, keeping liquid out of the compressor during the off cycle.

  92. Question 92Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Under Section 608, after a leak on a 150-pound high-pressure appliance is repaired, the repair must be verified by:

    1. An oil sample analysis sent to a laboratory
    2. A follow-up leak test within 30 days of the repair Correct answer.
    3. A 24-hour standing vacuum decay test
    4. A hydrostatic pressure test of the whole system

    Explanation

    Appliances containing 50 or more pounds of refrigerant must have repairs verified, and the follow-up verification test must be performed within 30 days after the repair is completed. If the appliance still leaks, further repair and verification are required.

  93. Question 93Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Why should a system's own compressor never be used to evacuate the system?

    1. It will release refrigerant through the shaft seal
    2. It cannot pull a deep vacuum and may overheat or fail Correct answer.
    3. It will overcharge the recovery cylinder
    4. It removes oil from the crankcase too quickly

    Explanation

    A refrigeration compressor is not a vacuum pump and cannot reach the deep vacuum needed to boil off moisture. Running a compressor in a vacuum also reduces cooling of the motor windings and can destroy the compressor, so a dedicated vacuum pump is always used.

  94. Question 94Type II - high- or very high-pressure appliances, except small appliances and MVACs

    While recovering refrigerant, the recovery cylinder reaches 80 percent of its capacity and the appliance still holds refrigerant. What should the technician do?

    1. Switch to an empty recovery cylinder and continue Correct answer.
    2. Continue recovery and watch the cylinder pressure closely
    3. Cool the cylinder with ice so more refrigerant fits
    4. Vent the remaining refrigerant to the atmosphere

    Explanation

    Recovery cylinders must never be filled above 80 percent of their capacity by weight because liquid expansion with warming can overstress the shell. When the limit is reached, the technician changes to another cylinder and completes the recovery.

  95. Question 95Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Liquid refrigerant returning to a running compressor will most likely cause:

    1. A higher discharge temperature at the compressor
    2. An increase in oil pressure at the pump
    3. Mechanical damage from slugging and oil dilution Correct answer.
    4. A lower head pressure at the condenser

    Explanation

    Liquids are incompressible, so liquid reaching the cylinders can break valves, connecting rods, or other internal parts. Liquid also washes oil off the bearing surfaces and dilutes the oil, causing rapid wear.

  96. Question 96Type II - high- or very high-pressure appliances, except small appliances and MVACs

    A system with a TXV shows high discharge pressure, a clear sight glass, high subcooling, and normal evaporator superheat. The most likely cause is:

    1. The system is undercharged
    2. The system is overcharged Correct answer.
    3. The suction line filter is restricted
    4. The evaporator fan motor has failed

    Explanation

    High subcooling means liquid is backing up in the condenser, which is the signature of excess refrigerant when the sight glass is clear. Normal superheat shows that the TXV is still feeding the coil correctly, so the problem is on the high side.

  97. Question 97Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Frost forms immediately at the outlet of the TXV while the rest of the evaporator coil stays warm and superheat is high. The most likely cause is:

    1. An overcharge of refrigerant in the system
    2. A restriction at the TXV inlet screen Correct answer.
    3. A dirty condenser coil with high ambient air
    4. Worn compressor valves and low capacity

    Explanation

    A restriction produces a pressure drop and flashing at one point, chilling the metal there and forming frost while the coil downstream starves. High superheat with a warm coil confirms that refrigerant is not reaching the evaporator in the right quantity.

  98. Question 98Type II - high- or very high-pressure appliances, except small appliances and MVACs

    During evacuation, the technician valves off the pump at 500 microns. The gauge rises to about 1,500 microns and then holds steady. This most likely indicates:

    1. Noncondensables trapped in the receiver
    2. Moisture in the system Correct answer.
    3. A faulty micron gauge
    4. A leak in the system

    Explanation

    A vacuum that rises and then stabilizes at an elevated level points to moisture or off-gassing from the system, which requires more evacuation or a nitrogen sweep. A vacuum that keeps rising toward atmospheric pressure indicates a leak instead.

  99. Question 99Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Why is a recovery cylinder never filled above 80 percent of its capacity by weight?

    1. To prevent the refrigerant from fractionating in the cylinder
    2. The liquid expands as it warms and can rupture the cylinder Correct answer.
    3. Because the tare weight changes with temperature
    4. To leave room for the recovery hose connections

    Explanation

    Refrigerant liquid expands significantly as its temperature rises, and with no vapor space left the pressure can build beyond the cylinder's design limit. Leaving about 20 percent vapor space keeps hydrostatic pressure from overstressing or rupturing the shell.

  100. Question 100Type II - high- or very high-pressure appliances, except small appliances and MVACs

    Which practice best limits refrigerant released to the atmosphere during routine gauge connections on a high-pressure appliance?

    1. Purge the hoses into the air for a full minute before connecting
    2. Fill the service hoses with nitrogen before each connection
    3. Loosen the hose connections to bleed pressure before disconnecting
    4. Use low-loss fittings and hose shutoff valves Correct answer.

    Explanation

    Section 608 prohibits venting refrigerant, so the technician minimizes releases by using low-loss fittings, core depressors, and shutoff valves so hoses hold very little refrigerant. Purging hoses into the air is a deliberate release and is not permitted.

  101. Question 101Type III - low-pressure appliances

    Under EPA regulations, a low-pressure appliance is one that uses a refrigerant with a saturation pressure at 104°F of no more than:

    1. 75 psig
    2. 30 psig
    3. 15 psig Correct answer.
    4. 50 psig

    Explanation

    The regulatory dividing line between low-pressure and high-pressure appliances is a saturation pressure of 15 psig at 104°F. Equipment above that value is treated as high-pressure equipment for recovery, evacuation, and leak-repair purposes.

  102. Question 102Type III - low-pressure appliances

    Which refrigerant is commonly used in low-pressure centrifugal chillers?

    1. R-123 Correct answer.
    2. R-22
    3. R-410A
    4. R-404A

    Explanation

    R-123, like the CFC-11 it largely replaced, boils near or below room temperature at atmospheric pressure, so a chiller using it operates in a vacuum on the low side. R-22, R-410A, and R-404A are all high-pressure refrigerants and would not be used in a low-pressure machine.

  103. Question 103Type III - low-pressure appliances

    Because the low side of a low-pressure chiller normally operates below atmospheric pressure, a leak in that section will:

    1. Draw air and moisture into the system Correct answer.
    2. Release refrigerant rapidly into the room
    3. Raise the evaporator pressure above atmospheric
    4. Open the pressure relief valve

    Explanation

    A machine running below atmospheric pressure pulls inward through any breach, so air and water vapor enter the refrigerant circuit rather than refrigerant escaping. That is why low-pressure chillers accumulate non-condensables and moisture and why they are built with a purge unit.

  104. Question 104Type III - low-pressure appliances

    What is the function of the purge unit on a low-pressure chiller?

    1. To remove air and moisture from the system Correct answer.
    2. To add refrigerant to the chiller automatically
    3. To filter debris from the chilled water loop
    4. To raise evaporator pressure above atmospheric

    Explanation

    Air and water vapor migrate into a machine that runs in a vacuum and collect in the condenser, raising head pressure. The purge unit pulls those non-condensables out while limiting how much refrigerant escapes with them.

  105. Question 105Type III - low-pressure appliances

    Which gas should be used to pressurize a low-pressure appliance for leak testing?

    1. Compressed air
    2. Carbon dioxide
    3. Oxygen
    4. Dry nitrogen Correct answer.

    Explanation

    Dry nitrogen is inert, carries no moisture, and is used with a pressure regulator so the shell can be brought to a positive pressure safely. Air and oxygen can combine with refrigerant oil to form an explosive mixture and also introduce water into the system.

  106. Question 106Type III - low-pressure appliances

    Large low-pressure chillers that use R-11 or R-123 typically use which type of compressor?

    1. Centrifugal Correct answer.
    2. Reciprocating
    3. Scroll
    4. Rotary vane

    Explanation

    Low-pressure refrigerants have very large specific volumes, so a high-volume machine is needed to move a useful mass of vapor. Centrifugal compressors are the standard choice for these large chillers.

  107. Question 107Type III - low-pressure appliances

    When charging a low-pressure chiller, the refrigerant is normally admitted:

    1. As a liquid into the condenser
    2. As a liquid into the evaporator Correct answer.
    3. As a vapor into the suction line
    4. As a vapor into the receiver

    Explanation

    The evaporator holds the normal operating charge, so liquid refrigerant is throttled into the low side and flashes there. Charging vapor through the suction line would take far too long and risks liquid reaching the compressor.

  108. Question 108Type III - low-pressure appliances

    R-123 is classified as which type of refrigerant?

    1. CFC
    2. HCFC Correct answer.
    3. HFC
    4. HFO

    Explanation

    R-123 is a hydrochlorofluorocarbon, the HCFC that replaced CFC-11 in many low-pressure chillers. The hydrogen in its molecule makes it less stable in the atmosphere than a CFC, though it is still an ozone-depleting substance.

  109. Question 109Type III - low-pressure appliances

    Before opening a low-pressure appliance for repair, the refrigerant must be recovered until the system reaches:

    1. 25 mm Hg absolute Correct answer.
    2. 0 psig
    3. 4 inches of mercury vacuum
    4. 10 inches of mercury vacuum

    Explanation

    The evacuation requirement for low-pressure appliances is 25 mm Hg absolute, a deep vacuum far below atmospheric. The 0 psig, 4-inch, and 10-inch levels apply to high-pressure appliances of various sizes and refrigerant types.

  110. Question 110Type III - low-pressure appliances

    After reassembling a low-pressure chiller, which test best confirms the system is leak-free before charging?

    1. Pressurize with refrigerant and use a halide torch
    2. Evacuate to a deep vacuum and watch for a rise Correct answer.
    3. Operate the purge unit and observe its output
    4. Run the chiller and check the sight glass

    Explanation

    A standing vacuum test isolates an evacuated system and monitors it with a micron gauge; if the pressure climbs steadily, air is entering and a leak exists. Because the machine normally runs in a vacuum, the test closely mimics the real leak direction.

  111. Question 111Type III - low-pressure appliances

    A low-pressure chiller runs with abnormally high condenser pressure, and its purge unit cycles far more often than usual. The most likely cause is:

    1. An overcharge of refrigerant
    2. Air has entered the system Correct answer.
    3. A restricted liquid line drier
    4. Low chilled water flow

    Explanation

    Non-condensable gases such as air collect in the condenser, raise the condensing pressure, and force the purge unit to run frequently. High head pressure combined with excessive purging is the classic signature of air in a low-pressure machine.

  112. Question 112Type III - low-pressure appliances

    Which practice speeds up recovery of refrigerant from a low-pressure chiller?

    1. Pressurize the chiller with nitrogen to push out the refrigerant
    2. Warm the chiller water and cool the recovery cylinder Correct answer.
    3. Pack ice around the chiller barrel
    4. Use the chiller's compressor to pull a deeper vacuum

    Explanation

    Recovery rate depends on the pressure difference between the appliance and the cylinder. Adding heat to the chiller raises the refrigerant's vapor pressure while chilling the cylinder lowers it, so the refrigerant moves faster; cylinders are never heated with a flame.

  113. Question 113Type III - low-pressure appliances

    Which practice is prohibited when removing refrigerant from a low-pressure appliance?

    1. Using the chiller's compressor as a recovery device Correct answer.
    2. Using a recovery machine rated for the refrigerant
    3. Weighing the recovery cylinder during the procedure
    4. Recovering into a DOT-approved cylinder

    Explanation

    Recovery must be performed with certified recovery equipment designed for the refrigerant. A system compressor is not a recovery device; drawing the charge through it can damage the machine and release refrigerant.

  114. Question 114Type III - low-pressure appliances

    A pressure relief valve on a low-pressure chiller is typically set to open at approximately:

    1. 15 psig Correct answer.
    2. 50 psig
    3. 300 psig
    4. 150 psig

    Explanation

    Low-pressure shells are built for very low working pressures, so their relief devices are set near 15 psig. If a relief valve or rupture disc releases, the entire charge can escape, so the cause of the overpressure must be found and corrected.

  115. Question 115Type III - low-pressure appliances

    Moisture that enters a low-pressure chiller is harmful mainly because it can:

    1. Reduce the condenser water flow rate
    2. Form acids and freeze at the metering device Correct answer.
    3. Raise the evaporator pressure above atmospheric
    4. Turn the refrigerant into a non-condensable gas

    Explanation

    Water reacts with refrigerant and oil to form acids that attack metals and motor windings, and it can freeze at the expansion device and block flow. That is why these machines require thorough dehydration, working filter driers, and a functioning purge unit.

  116. Question 116Type III - low-pressure appliances

    When an owner is notified that a low-pressure appliance has exceeded the applicable leak rate, the repairs must normally be completed within:

    1. 60 days
    2. 30 days Correct answer.
    3. 14 days
    4. 7 days

    Explanation

    The regulation requires repair within 30 days of discovering a leak that exceeds the threshold, followed by an initial and a follow-up verification test. Additional time requires an approved retrofit or replacement plan.

  117. Question 117Type III - low-pressure appliances

    Before recovering refrigerant from a chiller of unknown service history, the technician should:

    1. Assume it is the refrigerant named on the nameplate
    2. Test the refrigerant with a refrigerant identifier Correct answer.
    3. Add a small amount of virgin refrigerant to dilute any mix
    4. Vent a small sample to check its odor

    Explanation

    Mixed or contaminated refrigerant cannot be reclaimed and must be handled separately, so it has to be identified before recovery begins. Using an identifier protects both the recovered refrigerant and the equipment it will eventually be returned to.

  118. Question 118Type III - low-pressure appliances

    A low-pressure chiller operating with a low refrigerant charge will most likely show:

    1. High evaporator pressure and reduced capacity
    2. Normal pressures with a full sight glass
    3. Low evaporator pressure and reduced capacity Correct answer.
    4. High condenser pressure with frequent purging

    Explanation

    With less refrigerant the evaporator is starved, so suction pressure falls and the machine cannot deliver its rated capacity, causing the leaving chilled water temperature to rise. High head pressure with frequent purging instead points to air in the machine.

  119. Question 119Type III - low-pressure appliances

    A recovery cylinder must never be filled beyond 80 percent of its capacity because:

    1. The refrigerant will be contaminated above that level
    2. The recovery machine cannot pull vapor from a full cylinder
    3. The cylinder valve seal will fail above that level
    4. Liquid expansion could rupture the cylinder Correct answer.

    Explanation

    Cylinders are filled by weight and must retain a vapor space so liquid can expand as it warms without hydraulically over-pressurizing the shell. Overfilling can rupture the cylinder and injure the technician.

  120. Question 120Type III - low-pressure appliances

    An idle R-123 chiller in an 80°F machine room shows 5 psig on its gauge. What does this indicate?

    1. Non-condensable gases are in the chiller Correct answer.
    2. The purge unit is operating correctly
    3. The chiller is overcharged with refrigerant
    4. The gauge is reading normally for R-123 at that temperature

    Explanation

    R-123 boils at about 82°F, so at 80°F its saturation pressure is slightly below atmospheric rather than 5 psig. A positive pressure that the refrigerant alone cannot produce means air or another non-condensable has been drawn in through a leak.

  121. Question 121Type III - low-pressure appliances

    Why must a low-pressure chiller be pressurized before an electronic leak detector is used?

    1. Refrigerant cannot vaporize in a vacuum
    2. Pressurizing changes the refrigerant into a different chemical compound
    3. Electronic detectors do not work below zero psig
    4. A leak under vacuum pulls air in, not refrigerant out Correct answer.

    Explanation

    In normal operation the shell is below atmospheric pressure, so a breach admits air rather than releasing refrigerant for a detector to sense. Pressurizing with nitrogen reverses the flow so escaping refrigerant can be detected at the leak site.

  122. Question 122Type III - low-pressure appliances

    A technician evaluates a purge unit's efficiency by comparing the:

    1. Chilled water temperature drop to the purge rate
    2. Purge run time to compressor run time
    3. Condenser water flow to the purge run time
    4. Refrigerant lost to the air removed Correct answer.

    Explanation

    Purge efficiency is expressed as the mass of refrigerant emitted per mass of air purged, so a lower ratio means less refrigerant is lost for the same air removal. A purge unit that loses excessive refrigerant per unit of air needs service or replacement.

  123. Question 123Type III - low-pressure appliances

    Why must the chilled water pump be running while a large charge of liquid refrigerant is added to an idle chiller's evaporator?

    1. To keep the water from freezing in the tubes Correct answer.
    2. To speed the refrigerant through the purge unit
    3. To keep the recovery cylinder from overheating
    4. To prevent the relief valve from opening

    Explanation

    Adding liquid refrigerant drives evaporator pressure and temperature down sharply. If water sits motionless in the tubes while its temperature drops below freezing, the tubes can split, so flow through the evaporator must be maintained during charging.

  124. Question 124Type III - low-pressure appliances

    The purge unit on a low-pressure chiller removes non-condensables from:

    1. The top of the condenser Correct answer.
    2. The liquid line
    3. The bottom of the evaporator
    4. The compressor discharge line

    Explanation

    Air and other non-condensables do not liquefy at condensing temperatures, so they rise and gather at the highest point of the condenser shell where the purge connection is located. Purging from that point removes them with the least refrigerant loss.

  125. Question 125Type III - low-pressure appliances

    How should oil be removed from the sump of an R-123 chiller?

    1. Pumped out through a service valve Correct answer.
    2. Drained by gravity into an open bucket
    3. Left in the sump until the machine is at atmospheric pressure
    4. Blown out with compressed air

    Explanation

    The oil sump of a low-pressure machine is at a vacuum, so simply opening a drain would pull air and moisture into the circuit. Oil is transferred with a pump or oil-handling system connected to a service valve, and refrigerant dissolved in the oil must be recovered before the oil is disposed of.

  126. Question 126Type III - low-pressure appliances

    A Type III appliance is defined as one that uses a refrigerant with a boiling point that is:

    1. Above 50°F at atmospheric pressure Correct answer.
    2. Above 200°F at atmospheric pressure
    3. Exactly 0°F at atmospheric pressure
    4. Below 32°F at atmospheric pressure

    Explanation

    EPA defines a low-pressure appliance by the refrigerant's boiling point, which must be above 50°F at atmospheric pressure. Such refrigerants have low saturation pressures and often operate in a vacuum. This is the basis for Type III certification.

  127. Question 127Type III - low-pressure appliances

    Which refrigerant is most commonly used in low-pressure centrifugal chillers?

    1. R-134a
    2. R-410A
    3. R-404A
    4. R-123 Correct answer.

    Explanation

    R-123 is the usual low-pressure refrigerant in modern centrifugal chillers, and R-11 was used in older machines. R-410A, R-134a, and R-404A are higher-pressure refrigerants covered under other certification types.

  128. Question 128Type III - low-pressure appliances

    A low-pressure chiller operating at normal chilled-water temperatures has an evaporator pressure that is:

    1. Exactly 0 psig
    2. About 150 psig
    3. Below atmospheric pressure Correct answer.
    4. About 25 psig

    Explanation

    Low-pressure refrigerants such as R-123 have saturation pressures below atmospheric at normal evaporator temperatures. That is why these machines run in a vacuum and why air can be drawn in.

  129. Question 129Type III - low-pressure appliances

    Why do air and moisture tend to enter an operating low-pressure chiller?

    1. The compressor seal is always open
    2. The purge unit draws in outdoor air
    3. The refrigerant forms acids with air
    4. The system is under vacuum Correct answer.

    Explanation

    Because the inside of a low-pressure chiller is below atmospheric pressure, any opening draws air and moisture inward. This is why leak detection and purge operation are critical on these machines.

  130. Question 130Type III - low-pressure appliances

    The refrigerant charge in a low-pressure chiller is normally determined by:

    1. Suction pressure alone
    2. Sight glass bubbles
    3. Compressor current draw
    4. Weight Correct answer.

    Explanation

    Low-pressure chillers are charged by weight because pressure and sight-glass indications are unreliable at low pressures. The manufacturer's charge weight is the accurate basis.

  131. Question 131Type III - low-pressure appliances

    Which gas is used to pressurize a low-pressure chiller for leak testing?

    1. Compressed room air
    2. Dry nitrogen Correct answer.
    3. Oxygen
    4. Acetylene

    Explanation

    Dry nitrogen is used because it is inert, does not add moisture, and will not support combustion. Oxygen and acetylene are dangerous, and room air introduces moisture.

  132. Question 132Type III - low-pressure appliances

    Because R-123 vapor is heavier than air, a leak in a machine room tends to:

    1. Settle near the floor Correct answer.
    2. Rise to the ceiling
    3. Form a flammable cloud at the ceiling
    4. Dissipate instantly

    Explanation

    R-123 vapor is denser than air, so it accumulates in low areas such as pits and floor drains. Proper ventilation and monitoring are required before entering those spaces.

  133. Question 133Type III - low-pressure appliances

    A recovery machine used on low-pressure appliances must be capable of:

    1. Operating without a condenser
    2. Pulling a deep vacuum Correct answer.
    3. Producing high discharge pressure
    4. Heating the refrigerant

    Explanation

    Recovery from a low-pressure appliance requires a machine able to pull a deep vacuum because the refrigerant's saturation pressure is low. Standard high-pressure recovery equipment may not reach the required level.

  134. Question 134Type III - low-pressure appliances

    Refrigerant must be recovered from a low-pressure appliance until the system reaches:

    1. 25 mm Hg absolute Correct answer.
    2. 10 inches of mercury vacuum
    3. 0 psig
    4. 25 psig

    Explanation

    EPA requires low-pressure appliances to be evacuated to 25 mm Hg absolute during recovery. This is a deeper vacuum than the levels required for high-pressure appliances.

  135. Question 135Type III - low-pressure appliances

    For a low-pressure comfort-cooling chiller, the EPA leak rate threshold is:

    1. 5 percent
    2. 50 percent
    3. 35 percent
    4. 15 percent Correct answer.

    Explanation

    The leak rate threshold for comfort-cooling appliances is 15 percent per year. Commercial refrigeration and industrial process refrigeration use a 35 percent threshold.

  136. Question 136Type III - low-pressure appliances

    When pressurizing a low-pressure chiller with nitrogen, the technician should:

    1. Fill until the disc opens
    2. Use a regulator and gauge Correct answer.
    3. Use full cylinder pressure directly
    4. Add oxygen for sensitivity

    Explanation

    Nitrogen is supplied at high cylinder pressure, so a regulator is required to avoid overpressurizing and damaging the chiller. The test pressure should not exceed the low-side design pressure.

  137. Question 137Type III - low-pressure appliances

    The most accurate instrument for monitoring evacuation of a low-pressure chiller is a:

    1. Pressure transducer
    2. Micron gauge Correct answer.
    3. Manifold gauge set
    4. Compound gauge

    Explanation

    A micron gauge measures absolute pressure in the deep-vacuum range where standard gauges are inaccurate. It is the required instrument for confirming evacuation.

  138. Question 138Type III - low-pressure appliances

    A purge unit minimizes refrigerant loss by:

    1. Storing the air in the receiver
    2. Condensing the air into a liquid
    3. Burning the non-condensable gases
    4. Separating air from refrigerant Correct answer.

    Explanation

    A purge unit separates non-condensable gases from refrigerant vapor so that mainly air is vented. This limits the amount of refrigerant lost during purging.

  139. Question 139Type III - low-pressure appliances

    A large low-pressure centrifugal chiller's capacity is often controlled by:

    1. Inlet guide vanes Correct answer.
    2. A hot gas bypass valve
    3. The purge unit
    4. The condenser water valve

    Explanation

    Centrifugal chillers commonly use inlet guide vanes to modulate compressor capacity. The purge unit and condenser water valve serve other functions.

  140. Question 140Type III - low-pressure appliances

    R-123 was introduced primarily as a replacement for which refrigerant?

    1. R-11 Correct answer.
    2. R-22
    3. R-502
    4. R-12

    Explanation

    R-123 was developed as a lower-ozone-depletion replacement for R-11 in centrifugal chillers. It is not a drop-in for R-12, R-22, or R-502 systems.

  141. Question 141Type III - low-pressure appliances

    Before recovering refrigerant, a recovery cylinder should be:

    1. Filled to 90 percent
    2. Filled with nitrogen
    3. Warmed to 100°F
    4. Evacuated and weighed Correct answer.

    Explanation

    A recovery cylinder must be evacuated so it does not contaminate the refrigerant, and weighed so the 80 percent fill limit can be respected. Nitrogen or heating is not appropriate preparation.

  142. Question 142Type III - low-pressure appliances

    A tube leak in the evaporator of a low-pressure chiller is serious mainly because:

    1. The purge unit will stop
    2. Water can enter the refrigerant Correct answer.
    3. Refrigerant will vent rapidly
    4. The compressor will overspeed

    Explanation

    The evaporator operates below atmospheric pressure, so a tube leak allows water to enter the refrigerant circuit. Water causes acid formation, sludge, and freeze-up.

  143. Question 143Type III - low-pressure appliances

    After a leak is repaired on a low-pressure appliance, the repair must be verified by:

    1. A purge count
    2. An initial verification test Correct answer.
    3. A capacity test
    4. An oil analysis

    Explanation

    EPA requires an initial verification test after a leak repair to confirm the repair was successful. Follow-up verification may also be required depending on the appliance.

  144. Question 144Type III - low-pressure appliances

    Recovered R-123 that will be used in another owner's appliance must be:

    1. Reclaimed Correct answer.
    2. Vented
    3. Mixed with R-11
    4. Recycled on site

    Explanation

    Refrigerant sold or transferred to another owner must be reclaimed to AHRI Standard 700. On-site recycling is only acceptable for reuse in equipment under the same ownership.

  145. Question 145Type III - low-pressure appliances

    The leaving chilled water from a low-pressure chiller is typically:

    1. 70°F to 75°F
    2. 40°F to 45°F Correct answer.
    3. 25°F to 30°F
    4. 55°F to 60°F

    Explanation

    Low-pressure chillers are designed to produce chilled water in the 40°F to 45°F range. Lower temperatures risk freezing the water in the evaporator tubes.

  146. Question 146Type III - low-pressure appliances

    A chiller with a 1,000-pound charge loses 200 pounds over 12 months. What is the annual leak rate?

    1. 200 percent
    2. 20 percent Correct answer.
    3. 10 percent
    4. 2 percent

    Explanation

    Annual leak rate is the refrigerant added over a year divided by the full charge, times 100. Here, 200 ÷ 1,000 × 100 = 20 percent.

  147. Question 147Type III - low-pressure appliances

    R-123 has which ASHRAE safety group classification?

    1. B3
    2. B1 Correct answer.
    3. A2L
    4. A1

    Explanation

    R-123 is classified B1, meaning it has higher toxicity and no flame propagation. This is why machine-room monitoring and ventilation are important.

  148. Question 148Type III - low-pressure appliances

    A chiller has a saturated evaporator temperature of 35°F and leaves 45°F chilled water. What is the approach?

    1. 35°F
    2. 80°F
    3. 10°F Correct answer.
    4. 45°F

    Explanation

    Approach is the difference between leaving chilled water and saturated evaporator temperature. Here, 45°F minus 35°F equals 10°F.

  149. Question 149Type III - low-pressure appliances

    Why must liquid R-123 often be pushed out of a chiller with vapor or a pump?

    1. The system may be under vacuum Correct answer.
    2. It is too cold to flow
    3. It reacts with recovery cylinders
    4. It cannot be recovered as a liquid

    Explanation

    At normal room temperature, R-123's saturation pressure can be below atmospheric, so it will not flow out under its own pressure. It must be pumped or pushed with vapor.

  150. Question 150Type III - low-pressure appliances

    After evacuation, a micron gauge reading rises steadily after the pump is isolated. This indicates:

    1. A leak or residual moisture Correct answer.
    2. The gauge is out of calibration
    3. The vacuum pump is oversized
    4. The system is dry and tight

    Explanation

    A vacuum that holds steady indicates a tight, dry system. A rising reading means air or moisture is entering the system or being released from it.

  151. Question 151Universal - all types of equipment

    Under Section 608 of the Clean Air Act, which practice is prohibited when servicing stationary refrigeration equipment?

    1. Returning used refrigerant to a reclamation facility
    2. Recycling refrigerant on site using certified equipment
    3. Venting refrigerant to the atmosphere Correct answer.
    4. Recovering refrigerant into a DOT-approved recovery cylinder

    Explanation

    Section 608 prohibits knowingly venting ozone-depleting refrigerants and their HFC substitutes into the atmosphere. Refrigerant removed from an appliance must be recovered and then recycled, reclaimed, or destroyed.

  152. Question 152Universal - all types of equipment

    A recovery cylinder should never be filled beyond what percentage of its capacity by weight?

    1. 90 percent
    2. 80 percent Correct answer.
    3. 100 percent
    4. 60 percent

    Explanation

    Recovery cylinders are limited to 80 percent fill so that liquid refrigerant has room to expand as its temperature rises. An overfilled cylinder can become liquid-full and rupture from hydrostatic pressure.

  153. Question 153Universal - all types of equipment

    Which of the following refrigerants is classified as an HFC?

    1. R-123
    2. R-22
    3. R-134a Correct answer.
    4. R-12

    Explanation

    R-134a contains only hydrogen, fluorine, and carbon, with no chlorine, so it is a hydrofluorocarbon. R-22 and R-123 are HCFCs, and R-12 is a fully halogenated CFC.

  154. Question 154Universal - all types of equipment

    Which characteristic distinguishes polyolester (POE) oil from mineral oil in a refrigeration system?

    1. It absorbs moisture from the air Correct answer.
    2. It mixes only with CFC refrigerants
    3. It is not affected by moisture
    4. It is used only with R-22

    Explanation

    POE oil is hygroscopic, meaning it readily takes on moisture when exposed to air. It must be kept in sealed containers and systems using it must be evacuated thoroughly to remove water.

  155. Question 155Universal - all types of equipment

    Which gas should be used to pressurize a system for leak testing?

    1. Acetylene
    2. Oxygen
    3. Compressed air
    4. Dry nitrogen Correct answer.

    Explanation

    Dry nitrogen is inert, nonflammable, and adds no moisture to the system. Oxygen and acetylene can form explosive mixtures with oil, and compressed air carries moisture and contaminants into the piping.

  156. Question 156Universal - all types of equipment

    Technicians who service, maintain, or dispose of appliances containing regulated refrigerants must hold:

    1. A state plumbing license
    2. An EPA Section 608 certification Correct answer.
    3. A manufacturer's warranty card
    4. A DOT hazmat endorsement

    Explanation

    Section 608 requires certification through an EPA-approved testing program for anyone who services, maintains, repairs, or disposes of appliances containing regulated refrigerants. The certification type must match the equipment being worked on.

  157. Question 157Universal - all types of equipment

    Why is chlorodifluoromethane (R-22) being phased out of new equipment?

    1. It is flammable at room temperature
    2. It operates at pressures too high for standard equipment
    3. It contains chlorine and depletes stratospheric ozone Correct answer.
    4. It has an unusually high global warming potential

    Explanation

    R-22 is an HCFC, and the chlorine in its molecule destroys stratospheric ozone. Production and import of HCFCs are being phased out under the Montreal Protocol and the Clean Air Act.

  158. Question 158Universal - all types of equipment

    Which personal protective equipment is most important when handling liquid refrigerant?

    1. Eye/face protection and insulating gloves Correct answer.
    2. A hard hat and steel-toed boots with hearing protection
    3. A dust mask and leather work gloves with ear plugs
    4. A respirator with a full-body apron and shoe covers

    Explanation

    Liquid refrigerant boils at extremely low temperatures and can cause frostbite and permanent eye damage on contact. Safety glasses or a face shield plus insulating gloves are the essential protection.

  159. Question 159Universal - all types of equipment

    When recovering refrigerant from an appliance containing 200 pounds or more of an HCFC refrigerant, the system must be evacuated to:

    1. 15 inches of mercury vacuum Correct answer.
    2. 0 psig
    3. 500 microns
    4. 4 inches of mercury vacuum

    Explanation

    The EPA evacuation table requires a 15 inch Hg vacuum for CFC and HCFC appliances holding 200 pounds or more. Smaller systems require 10 inches Hg, and small appliances require 4 inches Hg.

  160. Question 160Universal - all types of equipment

    While brazing a new suction line, dry nitrogen should flow through the tubing to:

    1. Prevent oxidation and scale inside the tubing Correct answer.
    2. Cool the joint so the fittings can be handled sooner
    3. Speed up the flow of solder into the joint
    4. Increase the pressure so leaks show up

    Explanation

    Heat drives oxygen to combine with copper and form oxide scale on the inside of the tubing. A slow nitrogen purge displaces the air so the interior stays clean, preventing scale from clogging driers and metering devices.

  161. Question 161Universal - all types of equipment

    System-dependent (passive) recovery of refrigerant from a small appliance is accomplished by:

    1. The pressure of the refrigerant alone
    2. The appliance's own compressor Correct answer.
    3. A vacuum pump on the recovery cylinder
    4. A separate recovery machine

    Explanation

    In system-dependent recovery, the appliance's own compressor moves refrigerant into a recovery cylinder that has been evacuated and often chilled. No separate recovery machine or vacuum pump is used to move the charge.

  162. Question 162Universal - all types of equipment

    Superheat at the evaporator outlet is found by:

    1. Subtracting the suction line temperature from the condensing temperature
    2. Subtracting the liquid line temperature from the ambient temperature
    3. Adding the suction line temperature to the liquid line temperature
    4. Suction line temperature minus evaporator saturation temperature Correct answer.

    Explanation

    Superheat is the difference between the actual suction vapor temperature and the saturation temperature that corresponds to the suction pressure. It confirms refrigerant is fully boiled to vapor before reaching the compressor.

  163. Question 163Universal - all types of equipment

    Subcooling at the condenser outlet is found by:

    1. Subtracting the liquid line temperature from the condensing temperature Correct answer.
    2. Subtracting the suction saturation temperature from the suction line temperature
    3. Subtracting the return air temperature from the supply air temperature
    4. Adding the liquid line temperature to the suction line temperature

    Explanation

    Subcooling compares the measured liquid line temperature to the condensing temperature obtained from the head pressure. It shows how much liquid is stacked in the condenser and is used to verify charge on thermostatic expansion valve systems.

  164. Question 164Universal - all types of equipment

    An appliance containing 50 or more pounds of refrigerant that leaks above the allowable rate must be repaired within how many days of discovering the leak?

    1. 30 days Correct answer.
    2. 120 days
    3. 90 days
    4. 10 days

    Explanation

    EPA regulations require repair within 30 days of discovering a leak above the allowable rate on appliances holding 50 or more pounds. An extension to 120 days is available only in limited circumstances, such as unavailable parts with a documented retrofit or retirement plan.

  165. Question 165Universal - all types of equipment

    Which method is the most accurate way to charge a new system that has a nameplate charge?

    1. Adding refrigerant until the sight glass is clear
    2. Weighing in the charge using a scale and the data plate amount Correct answer.
    3. Charging until the high-side gauge reads exactly 200 psig
    4. Charging until the suction line feels cold

    Explanation

    Weighing the refrigerant on a scale against the data plate charge is the only method independent of load, ambient temperature, and airflow. Gauge readings and sight glass observations are all affected by operating conditions.

  166. Question 166Universal - all types of equipment

    A properly dehydrated system should hold a standing vacuum of approximately:

    1. 10 inches of mercury
    2. 500 microns or lower Correct answer.
    3. 1,000 microns
    4. 5,000 microns

    Explanation

    A vacuum that holds at 500 microns or lower after the pump is isolated indicates that moisture and non-condensables have been removed. A rising vacuum during the standing test signals a leak or residual moisture.

  167. Question 167Universal - all types of equipment

    When adding refrigerant as a liquid to an evacuated system, it should be introduced:

    1. As a liquid into the suction line with the cylinder inverted
    2. Rapidly, as a liquid, into the suction service port
    3. Slowly, as a liquid, into the liquid line Correct answer.
    4. As a vapor into the liquid line with the system off

    Explanation

    Liquid refrigerant is metered into the high side, such as the liquid line or receiver, where it cannot reach the compressor as a slug of liquid. Feeding liquid into the suction line risks hydraulic damage to the compressor valves.

  168. Question 168Universal - all types of equipment

    Zeotropic blends such as R-407C must be charged:

    1. As a vapor to prevent fractionation
    2. As a liquid to prevent fractionation Correct answer.
    3. Only through the suction line
    4. Only after warming the cylinder above 100 degrees F

    Explanation

    Zeotropic blends contain components with different boiling points, so drawing vapor off the cylinder changes the mixture ratio. Liquid must be removed so the charge matches the labeled composition.

  169. Question 169Universal - all types of equipment

    Which statement about disposable refrigerant cylinders is correct?

    1. They must never be refilled Correct answer.
    2. They may be refilled by a certified technician
    3. They are legal for storing recovered refrigerant
    4. They can be refilled if the valve is replaced

    Explanation

    Disposable cylinders are DOT non-refillable containers designed for a single trip from the manufacturer. Federal rules prohibit refilling them, and they may not be used to store recovered refrigerant.

  170. Question 170Universal - all types of equipment

    Before connecting a recovery machine to a recovery cylinder, the technician should:

    1. Open the cylinder valve and leave it open to the air
    2. Heat the cylinder to increase its capacity
    3. Confirm the cylinder is DOT-approved and within its test date Correct answer.
    4. Fill the cylinder with water to keep it cool

    Explanation

    Recovery cylinders must be DOT-approved for refrigerant service, within their hydrostatic test interval, and free of air or non-condensables. Air left in the cylinder contaminates the recovered refrigerant and raises pressure.

  171. Question 171Universal - all types of equipment

    After a hermetic compressor burnout, the correct cleanup procedure is to:

    1. Replace the compressor only, since burnout residue clears itself
    2. Flush the system with water and blow it out with compressed air
    3. Replace the filter driers, change the oil, and correct the cause Correct answer.
    4. Install a suction filter only and reuse the old liquid drier

    Explanation

    A burnout leaves acid and sludge distributed throughout the system, so cleanup requires correcting the original cause and installing suction and usually liquid line filter driers. The oil and driers are then replaced again after a short run, and an acid test confirms the system is clean.

  172. Question 172Universal - all types of equipment

    Triple evacuation is performed to:

    1. Remove only non-condensable gases from the system, leaving moisture behind
    2. Leak test the system once the vacuum is deep
    3. Increase the system pressure before charging
    4. Remove moisture by sweeping with dry nitrogen between evacuations Correct answer.

    Explanation

    Each nitrogen sweep absorbs moisture clinging to the system walls, and the following evacuation carries it out. Repeating the cycle is the standard method when a deep vacuum will not hold after a major repair.

  173. Question 173Universal - all types of equipment

    A customer asks about replacing R-22 with R-410A in an existing R-22 system. The technician should explain that:

    1. It works if a larger suction line filter drier is installed
    2. Only the metering device needs to be changed
    3. It runs at much higher pressures and needs a different oil Correct answer.
    4. It works if the charge is reduced by 20 percent

    Explanation

    R-410A operates at roughly 50 to 60 percent higher pressures and requires polyolester oil and components rated for those pressures. It is not a drop-in replacement, so the compressor, coil, and line set ratings must be evaluated.

  174. Question 174Universal - all types of equipment

    A system shows low superheat at the evaporator outlet with a cold, sweating suction line back to the compressor. This most likely indicates:

    1. A restricted liquid line filter drier
    2. A failed condenser fan motor
    3. Overfeeding by the metering device Correct answer.
    4. An undercharge of refrigerant

    Explanation

    Low superheat with liquid returning to the compressor means too much refrigerant is entering the evaporator, as with an overfeeding valve, oversized orifice, or overcharge. Undercharge and restrictions produce the opposite symptom of high superheat.

  175. Question 175Universal - all types of equipment

    R-410A is composed of:

    1. 23 percent R-32, 25 percent R-125, and 52 percent R-134a
    2. 50 percent R-32 and 50 percent R-125 Correct answer.
    3. 60 percent R-22 and 40 percent R-152a
    4. 48.8 percent R-22 and 51.2 percent R-115

    Explanation

    R-410A is a near-azeotropic HFC blend of equal parts R-32 and R-125. Because the components are close in volatility, it has very little temperature glide and is charged as a liquid.

  176. Question 176Universal - all types of equipment

    Which action is prohibited by Section 608 of the Clean Air Act?

    1. Pressure testing with dry nitrogen
    2. Venting refrigerant to the atmosphere Correct answer.
    3. Recovering refrigerant before opening a system
    4. Recycling refrigerant for the same owner's equipment

    Explanation

    Section 608 prohibits knowingly venting ozone-depleting refrigerants and their HFC substitutes to the atmosphere. Refrigerant must be recovered before a system is opened or an appliance is discarded; only de minimis releases during good-faith recovery are allowed.

  177. Question 177Universal - all types of equipment

    A recovery cylinder should be filled with refrigerant to no more than what percentage of its capacity?

    1. 80 percent Correct answer.
    2. 100 percent
    3. 60 percent
    4. 95 percent

    Explanation

    Recovery cylinders must never be filled above 80 percent of capacity by weight, which leaves room for liquid expansion as the cylinder warms. The cylinder is filled while sitting on a scale so the weight can be monitored.

  178. Question 178Universal - all types of equipment

    Which gas must never be used to pressure test a refrigerant system?

    1. Carbon dioxide
    2. Dry nitrogen
    3. Oxygen Correct answer.
    4. Helium

    Explanation

    Oxygen combines with refrigerant oil under pressure and can ignite or detonate, so it is never used for leak testing or purging. Dry nitrogen is the standard inert gas for pressure testing a system.

  179. Question 179Universal - all types of equipment

    What is the maximum temperature to which a refrigerant cylinder should ever be heated?

    1. 250°F
    2. 125°F Correct answer.
    3. 200°F
    4. 150°F

    Explanation

    Cylinders should not be heated above 125°F because pressure rises rapidly with temperature and can exceed the cylinder's relief setting. Warm water or a warm room is acceptable, but open flame or steam is never used.

  180. Question 180Universal - all types of equipment

    Why must recovered refrigerant never be mixed with a different refrigerant in the same cylinder?

    1. The cylinder's pressure rating would be exceeded
    2. The recovery machine would run too hot
    3. The mixture can no longer be reclaimed Correct answer.
    4. The refrigerant would become flammable

    Explanation

    A reclaimer cannot separate different refrigerants or oils, so a mixed cylinder usually cannot be reclaimed to specification and must be destroyed. Each recovery cylinder must hold a single refrigerant and be labeled accordingly.

  181. Question 181Universal - all types of equipment

    Before a household refrigerator is disposed of, the technician must:

    1. Cut the suction line and let it bleed off
    2. Recover the refrigerant first Correct answer.
    3. Drain the compressor oil into the sewer
    4. Vent the charge to relieve system pressure

    Explanation

    Section 608 requires that refrigerant be recovered from appliances before final disposal, and disposal facilities must verify that recovery occurred. Releasing the charge to relieve pressure is illegal venting.

  182. Question 182Universal - all types of equipment

    A recovery machine should not be used to:

    1. Recover liquid refrigerant using the liquid port
    2. Evacuate a system to a deep vacuum before charging Correct answer.
    3. Remove vapor from a system at positive pressure
    4. Transfer refrigerant from a system into a recovery cylinder

    Explanation

    A recovery machine moves refrigerant but cannot pull the deep vacuum needed for dehydration, and running it that way can overheat or damage it. A dedicated vacuum pump is used to evacuate a system before charging.

  183. Question 183Universal - all types of equipment

    A technician holding only a Type I certification may service:

    1. Low-pressure chillers using R-123
    2. Any high-pressure appliance containing 50 pounds or more
    3. Small appliances of 5 pounds or less Correct answer.
    4. Any appliance regardless of charge size

    Explanation

    Type I certification covers small appliances containing 5 pounds or less of refrigerant, such as window units and household refrigerators. Larger high-pressure equipment requires Type II and low-pressure equipment requires Type III.

  184. Question 184Universal - all types of equipment

    An appliance containing 50 or more pounds of refrigerant used in commercial refrigeration must be repaired if its leak rate exceeds:

    1. 5 percent per year
    2. 35 percent per year Correct answer.
    3. 20 percent per year
    4. 15 percent per year

    Explanation

    The leak rate trigger is 35 percent per year for commercial refrigeration and industrial process refrigeration, while comfort cooling carries a 15 percent trigger. Exceeding the threshold starts the required repair timeline.

  185. Question 185Universal - all types of equipment

    When recovering refrigerant from a small appliance whose compressor is operating, the recovery equipment must remove at least:

    1. 50 percent of the charge
    2. 95 percent of the charge
    3. 80 percent of the charge Correct answer.
    4. 70 percent of the charge

    Explanation

    Recovery equipment used on small appliances must achieve 80 percent of the charge when the compressor is working, or 90 percent when it is not. The requirement applies whether the equipment is self-contained or system-dependent.

  186. Question 186Universal - all types of equipment

    Which of the following is classified as a low-pressure appliance under EPA rules?

    1. A rooftop unit using R-410A
    2. A centrifugal chiller using R-123 Correct answer.
    3. A walk-in freezer using R-404A
    4. A residential split system using R-22

    Explanation

    Low-pressure appliances operate with the evaporator below atmospheric pressure, as do centrifugal chillers using R-11 or R-123. R-22, R-410A and R-404A systems are all high-pressure appliances.

  187. Question 187Universal - all types of equipment

    To restore recovered refrigerant to the purity of virgin refrigerant, it must be:

    1. Reclaimed to AHRI Standard 700 Correct answer.
    2. Passed through a filter-drier
    3. Recycled on site
    4. Re-evacuated

    Explanation

    Reclaiming is the only process that returns refrigerant to virgin specifications, and it is performed off site by an EPA-certified reclaimer to AHRI 700. On-site recycling only removes oil, acid and particulates.

  188. Question 188Universal - all types of equipment

    Air that has entered a sealed refrigeration system will most likely cause:

    1. A lower than normal condensing temperature
    2. Higher than normal discharge pressure Correct answer.
    3. Lower than normal discharge pressure
    4. Frost on the suction line

    Explanation

    Non-condensables such as air do not condense in the condenser, so they take up space and raise discharge pressure while reducing capacity. The symptom pattern is high head pressure with otherwise normal superheat and subcooling.

  189. Question 189Universal - all types of equipment

    Which practice improves both the speed and the depth of a system evacuation?

    1. Connecting the pump through the gauge manifold
    2. Using the system compressor as a vacuum pump
    3. Charging a little refrigerant to raise pressure
    4. Removing valve cores and using large hoses Correct answer.

    Explanation

    Every restriction, including Schrader cores, small hoses and manifold passages, limits flow and slows evacuation. Removing the cores and connecting large-diameter hoses with a micron gauge at the system allows a deep vacuum to be reached.

  190. Question 190Universal - all types of equipment

    When retrofitting an R-22 system to an HFC blend, the technician should plan to:

    1. Change to POE oil and a new drier Correct answer.
    2. Increase the system charge by 50 percent
    3. Keep the existing mineral oil in all cases
    4. Reuse the existing filter-drier without change

    Explanation

    HFC refrigerants are not miscible with mineral oil, so the lubricant must be changed to POE or another approved oil and the filter-drier replaced to capture moisture and acid. Residual mineral oil should be flushed out as well.

  191. Question 191Universal - all types of equipment

    An electronic leak detector is preferred over a halide torch for HFC refrigerants because halide torches:

    1. Detect only HFC refrigerants
    2. Respond mainly to chlorine Correct answer.
    3. Cannot be used indoors
    4. Respond only to nitrogen

    Explanation

    A halide torch changes flame color in the presence of chlorine, so it works for CFCs and HCFCs but is unreliable for HFCs such as R-410A. Electronic detectors and soap bubbles work across the common refrigerant families.

  192. Question 192Universal - all types of equipment

    DOT recovery cylinders must be hydrostatically tested and requalified every:

    1. 10 years
    2. 5 years Correct answer.
    3. 15 years
    4. 2 years

    Explanation

    Recovery cylinders must be requalified by hydrostatic test every 5 years and marked with the test date. A cylinder that is damaged or past its requalification date must be taken out of service.

  193. Question 193Universal - all types of equipment

    When transporting refrigerant cylinders in a service vehicle, the technician should:

    1. Secure them upright with valve caps installed Correct answer.
    2. Lay them on their side to save space
    3. Store them in the passenger area for monitoring
    4. Remove the valve caps so pressure can vent

    Explanation

    Cylinders should ride upright and secured so liquid stays away from the valve and relief device, with valve caps protecting the valve from damage. They must not be carried in the passenger compartment where a leak could displace oxygen.

  194. Question 194Universal - all types of equipment

    On a low-pressure centrifugal chiller, the purge unit is used to:

    1. Raise the pressure above atmospheric for leak testing
    2. Remove air and moisture that enter the machine Correct answer.
    3. Add refrigerant vapor to the evaporator
    4. Circulate chilled water through the tubes

    Explanation

    Low-pressure machines run below atmospheric pressure, so air and moisture leak inward and collect in the condenser. The purge unit removes these non-condensables so condensing pressure and efficiency stay correct.

  195. Question 195Universal - all types of equipment

    An appliance containing 200 pounds of HFC-134a must be evacuated to what level before it is opened?

    1. 15 inches of mercury
    2. 10 inches of mercury Correct answer.
    3. 0 inches of mercury
    4. 4 inches of mercury

    Explanation

    EPA evacuation levels depend on refrigerant type and charge size. Appliances of 200 pounds or more using refrigerants other than HCFC-22 must reach 10 inches of mercury, while HCFC-22 appliances of that size must reach 15 inches.

  196. Question 196Universal - all types of equipment

    A commercial refrigeration appliance holds 120 pounds of R-404A and lost 45 pounds over the past 12 months. What is the leak rate and what does it require?

    1. 37.5 percent, which requires repair Correct answer.
    2. 37.5 percent, which is within the allowable rate
    3. 45 percent, which is above the comfort-cooling limit
    4. 27 percent, which requires repair

    Explanation

    Leak rate is the refrigerant lost in 12 months divided by the appliance charge, so 45 ÷ 120 = 37.5 percent. That exceeds the 35 percent limit for commercial refrigeration, so a repair is required.

  197. Question 197Universal - all types of equipment

    After a required leak repair is completed on an appliance containing 50 or more pounds of refrigerant, a follow-up verification test must be performed:

    1. Within 6 months of the repair
    2. Only if the owner requests it
    3. Within 30 days of the repair Correct answer.
    4. Within 24 hours of the repair

    Explanation

    The regulations require a follow-up verification test to confirm the repair, completed within 30 days after the repair is finished. If the appliance still leaks, further repair, retrofit or retirement is required.

  198. Question 198Universal - all types of equipment

    Refrigerant that has been recovered and recycled on site may legally be:

    1. Sold to another customer as new refrigerant
    2. Placed in a disposable cylinder for resale
    3. Put back into the same owner's equipment Correct answer.
    4. Used in any appliance of the same refrigerant type

    Explanation

    Recycled refrigerant may only be charged back into equipment owned by the same person, or sent to a certified reclaimer. It may not be sold or represented as new refrigerant, and disposable cylinders may not be refilled.

  199. Question 199Universal - all types of equipment

    When recovering a flammable refrigerant such as R-290, the technician must:

    1. Vent the refrigerant outdoors in small amounts
    2. Use flammable-rated recovery equipment Correct answer.
    3. Use the same recovery machine used for HFCs
    4. Use a standard vacuum pump to speed recovery

    Explanation

    Flammable refrigerants require recovery machines and components rated for flammable service, and all ignition sources must be eliminated. Standard HFC recovery equipment is not approved for these refrigerants.

  200. Question 200Universal - all types of equipment

    Before a low-pressure chiller using R-123 is opened for service, it must be evacuated to:

    1. 500 microns
    2. 25 mm Hg absolute Correct answer.
    3. 0 psig
    4. 10 inches of mercury vacuum

    Explanation

    EPA sets the recovery level for low-pressure appliances at 25 mm Hg absolute, measured with an absolute pressure gauge. Because these machines operate below atmospheric pressure, ordinary gauge-vacuum readings do not apply.

EPA 608 Universal flashcards

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Type I appliance threshold
Type I certification covers small appliances containing 5 pounds or less of refrigerant, such as household refrigerators, window air conditioners, dehumidifiers, and vending machines, but not motor vehicle air conditioners.
Small appliance recovery: 90 percent
When the compressor of a small appliance is operating, the technician must recover at least 90 percent of the refrigerant charge before opening, servicing, or disposing of the appliance.
Small appliance recovery: 80 percent
If a small appliance's compressor is not functioning, at least 80 percent of the refrigerant charge must be recovered before the appliance is opened or discarded.
System-dependent recovery device
A recovery device that relies on the appliance's own compressor, gravity, or applied heat to move refrigerant; it may be used on small appliances only while the compressor operates.
Leak repair rule scope
The mandatory 30-day leak repair and verification requirements apply only to appliances containing 50 or more pounds of refrigerant, so small appliances are exempt from those rules.
Recycling versus reclaiming
Recycling cleans refrigerant on site for reuse, often in the same appliance; reclaiming reprocesses refrigerant to AHRI 700 purity at a certified facility and is required before the refrigerant changes ownership.
Line-piercing service valve
Many small appliances are factory-sealed with no service ports, so technicians install a line-piercing valve to recover refrigerant, then leak-check the access point after service.
Type II appliance examples
Type II certification covers high-pressure and very-high-pressure equipment other than small appliances and motor vehicle air conditioners, for example R-22, R-134a, R-404A, and R-410A systems.
Post-1993 evacuation level
High-pressure appliances manufactured after November 15, 1993 must be evacuated to 10 inches of mercury vacuum before being opened for service or disposal.
Pre-1993 R-22 evacuation
For high-pressure appliances built before November 15, 1993 that contain HCFC-22, technicians must evacuate to 0 inches of mercury vacuum, meaning atmospheric pressure.
Pre-1993 other refrigerant evacuation
High-pressure appliances manufactured before November 15, 1993 that use refrigerants other than HCFC-22 must be evacuated to 4 inches of mercury vacuum before opening.
R-410A pressure class
R-410A is a near-azeotropic blend of R-32 and R-125 that operates at pressures roughly 50 to 70 percent higher than R-22, so only R-410A-rated gauges, hoses, and recovery equipment may be used.
Eighty percent cylinder limit
A recovery cylinder must never be filled beyond 80 percent of its capacity by weight, because liquid refrigerant expands as it warms and an overfilled cylinder can rupture.
Nitrogen leak testing
Dry nitrogen is the approved pressurizing gas for leak testing; oxygen, compressed air, and acetylene must never be used because they can cause fire, explosion, or oil breakdown.
Fifty-pound leak repair rule
Appliances holding 50 or more pounds of refrigerant must have leaks repaired within 30 days of discovery, followed by an initial verification test and a follow-up verification test.
Micron gauge dehydration
A vacuum pump and micron gauge dehydrate an opened high-pressure system; pulling to about 500 microns and holding a stable vacuum shows the system is dry and leak-free.
Type III appliances
Type III certification covers low-pressure appliances such as centrifugal chillers using CFC-11 or HCFC-123, refrigerants that boil below atmospheric pressure so the machine operates in a vacuum.
Low-pressure evacuation level
Low-pressure appliances must be evacuated to 25 millimeters of mercury absolute, about 29.6 inches of mercury vacuum, before opening; the same level applies to pre-1993 and post-1993 equipment.
Air and moisture ingress
Because low-pressure systems run below atmospheric pressure, any leak or open line pulls air and moisture in, which raises condensing pressure and forms acids that damage the system.
Low-pressure rupture disc
Low-pressure chillers are protected by a rupture disc, usually set near 15 psig, instead of a reseating relief valve; the system must never be pressurized above that setpoint.
Purge unit function
A purge unit removes air and other non-condensables that collect in a low-pressure chiller's condenser, restoring efficiency; excessive purging wastes refrigerant and signals a leak.
Freeze-up from moisture
Moisture carried into a low-pressure chiller can freeze at the evaporator and restrict refrigerant flow, so the system uses filter-driers and is never left open to the atmosphere.
R-11 versus R-123
CFC-11 has an ozone depletion potential of 1.0, while HCFC-123 is a lower-ODP replacement; both are low-pressure refrigerants that must be recovered and never vented.
Low-pressure recovery sequence
Recovering a low-pressure chiller usually means removing liquid first, then vapor with a recovery machine able to pull from a vacuum; cooling the recovery cylinder speeds the transfer.
Venting prohibition
Since July 1, 1992, knowingly venting ozone-depleting refrigerant to the atmosphere during service, maintenance, repair, or disposal has been prohibited; recovered refrigerant must be recycled, reclaimed, or destroyed.
Ozone depletion potential values
CFC-11 and CFC-12 have an ozone depletion potential of 1.0, HCFC-22 is about 0.05, and HFCs such as R-134a and R-410A have a value of zero.
Final disposal responsibility
Refrigerant must be recovered before an appliance is scrapped, and the last person in the disposal chain must verify that recovery and keep the documentation for three years.
Section 609 versus 608
Motor vehicle air conditioners are governed by Section 609 and require a separate certification; Section 608 covers stationary refrigeration and air-conditioning equipment only.
Never braze charged lines
Heating a line that still contains refrigerant can decompose halogenated refrigerant into toxic, corrosive gas; recover the charge and purge with dry nitrogen before brazing.
No mixed refrigerants
Never mix different refrigerants in one recovery cylinder; the mixture cannot be reclaimed to specification and must be destroyed, and each cylinder must be labeled with its refrigerant.
Cylinder requalification
DOT recovery cylinders must be pressure-tested and requalified on a set schedule, and cylinders that are damaged, corroded, or past their test date must not be filled.
De minimis release
Small releases that occur during good-faith attempts to recover refrigerant, such as residual vapor left in hoses, are de minimis and are not violations of the venting prohibition.

EPA 608 Universal study guide

Type I - Small Appliances

What Type I covers

Type I applies to small appliances: equipment that is fully manufactured, charged, and hermetically sealed in a factory with five pounds or less of refrigerant. Household refrigerators and freezers, window and PTAC air conditioners, dehumidifiers, under-counter ice machines, water coolers, and vending machines are the classic examples. The five-pound figure is the factory nameplate charge, not a gauge reading taken today. Motor-vehicle air conditioners are excluded (that is Section 609), and any appliance holding more than five pounds falls to Type II or Type III.

Numbers to know

  • Recovery efficiency: 90% of the charge when the compressor is operating, 80% when it is not, using equipment certified to AHRI 740.
  • System-dependent (passive) recovery devices are permitted only on small appliances, and only while the appliance compressor is running. If the compressor is dead, use a self-contained recovery machine.
  • Never fill a recovery cylinder past 80% of its capacity by weight. Use a scale every time.

Traps the exam sets

  • Micron answers. Deep-vacuum evacuation targets are not the Type I rule; small appliances are governed by recovery efficiency, so do not pick 500 microns on a Type I question.
  • It is only five pounds, so I can vent it. Venting is prohibited; refrigerant must be recovered even from a scrap refrigerator.
  • Scope creep. Type I does not authorize work on a rooftop unit or a chiller.
  • Refrigerant mixing. Never blend two refrigerants into one recovery cylinder.

Rule of thumb: five pounds or less and factory-sealed means Type I; if the question asks for a percentage, remember 80 off, 90 running.

Type II - High-Pressure and Very High-Pressure Appliances

Scope

Type II covers high-pressure and very high-pressure appliances other than small appliances and MVACs: split systems, packaged rooftop units, positive-pressure chillers, and anything using R-22, R-134a, R-407C, R-410A, R-32, or R-744. Very high pressure means a saturated pressure above roughly 220 psig at 104°F, or a critical temperature below 104°F. R-410A qualifies, so use only hoses, manifolds, recovery machines, and cylinders rated for it - an R-22 gauge set must never be used on an R-410A system.

Evacuation levels before opening

  • Manufactured before November 15, 1993: 15 inches of mercury vacuum (380,000 microns).
  • Manufactured on or after that date, charge under 200 lb: 0 psig.
  • Manufactured on or after that date, charge 200 lb or more: 10 inches of mercury vacuum (254,000 microns).

Leak repair and records

Appliances holding 50 lb or more that leak above the applicable rate must be repaired within 30 days of discovery, extended to 120 days with a documented repair plan, then verified by test and documented. Chronic leakers must be retrofitted or retired.

Traps

Charging a zeotropic blend such as R-407C as a vapor - it fractionates, so charge liquid. Mixing refrigerants in one cylinder. Pressure-testing with oxygen or shop air instead of dry nitrogen. Assuming 0 psig means the system is clean - the required level still must be reached before the circuit is opened.

Worked example: a 2005 rooftop unit holding 12 lb of R-410A is evacuated to 0 psig, because it was built after 1993 and holds under 200 lb; an identical unit built in 1990 would go to 15 inches of mercury vacuum, about 380,000 microns.

Type III - Low-Pressure Appliances

What makes an appliance low-pressure

Low-pressure appliances use refrigerants whose evaporator pressure sits below atmospheric, so the machine runs in a vacuum and air and moisture leak in rather than refrigerant leaking out. R-11, R-113, and R-123 centrifugal chillers are the standard examples. Because the shell is not built for positive pressure, a low-pressure chiller typically has a rupture disc set near 15 psig rather than a spring-loaded relief valve, and the vessel must never be pressurized with air or above its design pressure.

Air and moisture

A purge unit removes non-condensables and water that enter through seals and gaskets. Excess air raises condensing pressure and destroys efficiency, which is why high condensing pressure on a chiller points to a failing purge. Moisture can freeze inside the evaporator tubes. Never add heat with a torch to speed recovery; use warm water or a heat blanket and keep tube water above freezing.

Evacuation and recovery

The required evacuation level for low-pressure appliances is 25 mm Hg absolute, about 25,400 microns. It is absolute pressure, not inches of vacuum. A standard high-pressure recovery machine cannot pull a chiller below atmospheric, so a liquid pump or a machine rated for low-pressure refrigerant is used, often in a push-pull arrangement.

Charging and traps

Charge R-11 or R-123 as a liquid into the evaporator so water in the tubes does not freeze. Expect the exam to test units: 25 mm Hg absolute versus 25 inches of vacuum is the favorite distractor. Leak testing is done with a standing vacuum test or dry nitrogen plus a trace of refrigerant - never with oxygen or compressed air.

Universal - All Equipment Types

The universal idea

The Universal exam is the core section plus Type I, II, and III sections, and you must reach 70% on each. In practice, the Universal credential means you classify the appliance first, then apply that type rules. The most common way candidates lose points is applying small-appliance numbers to a 200-pound system.

The classification decision

Ask three questions: what is the factory charge, is it hermetically sealed, and does it run below atmospheric pressure?

  • Five pounds or less and hermetic: Type I. Recover 90% with the compressor running, 80% with it off.
  • Positive pressure, any size, not hermetic and not MVAC: Type II. Evacuate to 0 psig (post-1993, under 200 lb), 10 in Hg vacuum (200 lb and up, post-1993), or 15 in Hg vacuum (pre-1993).
  • Vacuum-side chiller using R-11 or R-123: Type III. Evacuate to 25 mm Hg absolute.

Rules that apply everywhere

Venting refrigerant is prohibited. Recover into DOT-approved cylinders filled to no more than 80% by weight, using a scale. Never mix refrigerants. Never pressure-test with oxygen or shop air. Appliances holding 50 lb or more must have leaks repaired and verified, with records kept. Recover refrigerant before any appliance is scrapped.

Traps

  • Section 608 certification does not expire; it is not renewed annually and there is no recertification exam.
  • A Type II technician cannot legally service a small appliance, and Section 608 never authorizes MVAC work - that is Section 609.
  • Purchasing refrigerant requires certification, and small cans are restricted.
  • Refrigerant must be removed before the appliance leaves the site for disposal.

EPA 608 Universal cheat sheet

Quick reference

Type I - Small Appliances

  • Type I covers appliances charged at the factory with 5 lb or less of refrigerant: household refrigerators and freezers, window air conditioners, dehumidifiers, water coolers, vending machines. MVACs are excluded.

  • Recovery target when the appliance compressor is operational: at least 90% of the refrigerant charge.

  • Recovery target when the appliance compressor is not operational: at least 80% of the refrigerant charge.

  • A system-dependent (passive) recovery device may be used only on a small appliance whose own compressor runs; it uses that compressor, applied heat, or gravity to move refrigerant.

  • If the compressor will not run, a self-contained (active) recovery machine must be used to meet the 80% standard.

  • Leak-repair obligations (30-day repair, verification tests, chronic-leak reporting) apply to appliances holding 50 lb or more and therefore do not apply to small appliances.

  • Refrigerant recovered from a small appliance may be recycled on site and reused in equipment owned by the same owner; refrigerant changing ownership must be reclaimed to AHRI 700 purity.

  • Recovery equipment used on small appliances must be certified to the EPA-referenced standard (ARI/AHRI 740) for Type I equipment.

  • Sealed small systems without service ports are accessed with a line-piercing valve; the access point must be leak-checked before charging.

Quick reference

Type II - High- and Very-High-Pressure Appliances

  • Type II covers high-pressure and very-high-pressure equipment other than small appliances and MVACs, e.g. R-22, R-134a, R-404A, R-407C, R-410A, R-502 systems.

  • Evacuation level for appliances built after November 15, 1993: 10 inches of mercury vacuum.

  • Evacuation level for pre-November 15, 1993 appliances using HCFC-22: 0 inches of mercury vacuum (atmospheric).

  • Evacuation level for pre-November 15, 1993 appliances using other high-pressure refrigerants: 4 inches of mercury vacuum.

  • R-410A is a near-azeotropic R-32/R-125 blend running roughly 50–70% above R-22 pressures; only R-410A-rated gauges, hoses, and recovery equipment may be used, and it is charged as a liquid.

  • A recovery cylinder must never be filled above 80% of its capacity by weight; liquid expansion at higher temperature can rupture the cylinder.

  • Leak testing uses dry nitrogen, soap bubbles, or an electronic detector on the system charge; oxygen, compressed air, and acetylene are prohibited because of fire and explosion risk.

  • Appliances holding 50 lb or more must have leaks repaired within 30 days of discovery, then pass an initial verification test and a follow-up verification test.

  • Opened systems are dehydrated with a vacuum pump and micron gauge (about 500 microns, held stable); the system compressor is never used as a vacuum pump.

Quick reference

Type III - Low-Pressure Appliances

  • Type III covers low-pressure appliances such as centrifugal chillers using CFC-11 or HCFC-123, refrigerants that boil below atmospheric pressure.

  • Required evacuation level is 25 mm of mercury absolute (about 29.6 inches of mercury vacuum), the same for pre-1993 and post-1993 equipment.

  • Because the machine runs in a vacuum, every leak or opened line draws air and moisture inward; air raises condensing (head) pressure and moisture forms acids.

  • Low-pressure chillers are protected by a rupture disc, typically set near 15 psig, rather than a reseating relief valve; never pressurize above the disc rating, and replace a burst disc before charging.

  • A purge unit removes air and other non-condensables from the condenser; excessive purging wastes refrigerant and usually indicates a leak on the low side.

  • Moisture entering a low-pressure chiller can freeze at the evaporator and block flow; keep the system closed, use filter-driers, and leak-test with dry nitrogen plus trace refrigerant, soap bubbles, or an electronic detector.

  • Recovery is done liquid-first, then vapor, using a machine capable of pulling from a vacuum; cooling the recovery cylinder speeds transfer of low-pressure vapor.

  • CFC-11 has an ODP of 1.0 while HCFC-123 is a lower-ODP replacement refrigerant; both are low-pressure and both must be recovered, never vented.

Quick reference

Universal - All Equipment Types

  • Section 608 certifications: Type I small appliances, Type II high-pressure, Type III low-pressure, Universal (all three).

  • Venting refrigerant to the atmosphere during service, maintenance, repair, or disposal has been prohibited since July 1, 1992; recovered refrigerant must be recycled, reclaimed, or destroyed.

  • Ozone depletion potential: CFC-11 and CFC-12 = 1.0, HCFC-22 = 0.05, HFCs such as R-134a and R-410A = 0.

  • Refrigerant must be recovered before an appliance is scrapped; the last person in the disposal chain verifies recovery and keeps the documentation for three years.

  • Motor vehicle air conditioners fall under Section 609 and require separate certification; Section 608 covers stationary refrigeration and air-conditioning.

  • Never braze or torch a line that still holds refrigerant: decomposition produces toxic, corrosive gas. Recover the charge and purge with dry nitrogen first.

  • Never mix refrigerants in a recovery cylinder; mixed refrigerant cannot be reclaimed to specification and cylinders must be labeled with the refrigerant they contain.

  • Recovery cylinders must be DOT-approved, requalified on schedule, and free of damage or corrosion; do not fill an out-of-test cylinder.

  • Releases that occur during good-faith recovery attempts (for example residual hose vapor) are de minimis and are not venting violations.

EPA 608 Universal key terms

Ozone Depletion Potential (ODP)

A number comparing a refrigerant's ability to destroy stratospheric ozone to CFC-11, which is set at 1.0. Higher values indicate greater ozone harm.

Related: Chlorofluorocarbon (CFC), Hydrofluorocarbon (HFC), Global Warming Potential (GWP)
Global Warming Potential (GWP)

A number comparing a refrigerant's heat-trapping effect in the atmosphere to carbon dioxide over a chosen time period. Higher values mean a stronger contribution to climate change.

Related: Ozone Depletion Potential (ODP), Hydrofluorocarbon (HFC), A2L refrigerant
Chlorofluorocarbon (CFC)

A refrigerant class containing chlorine, fluorine, and carbon that strongly depletes stratospheric ozone. CFCs are banned from production and use in most applications.

Related: Ozone Depletion Potential (ODP), Hydrofluorocarbon (HFC)
Hydrofluorocarbon (HFC)

A refrigerant class containing hydrogen, fluorine, and carbon but no chlorine. HFCs do not deplete ozone but are potent greenhouse gases, such as R-134a and R-410A.

Related: Global Warming Potential (GWP), Ozone Depletion Potential (ODP), A2L refrigerant
Zeotropic blend

A refrigerant mixture whose components have different boiling points, producing a temperature glide during phase change. It must be charged as liquid to maintain the intended composition.

Related: Temperature glide, Fractionation, Liquid charging
Temperature glide

The difference between the bubble point and dew point temperatures of a zeotropic refrigerant blend at a given pressure. It affects charging and system performance.

Related: Zeotropic blend, Fractionation, Liquid charging
Fractionation

The separation of components in a zeotropic blend when it leaks or boils, because components vaporize at different rates. This changes the remaining refrigerant's composition and performance.

Related: Zeotropic blend, Temperature glide, Liquid charging
Recovery

Removing refrigerant from an appliance and storing it in an external container without intentionally processing it. Recovery is required before opening a system or disposing of equipment.

Related: Recycling, Reclaiming, Recovery cylinder
Recycling

Cleaning recovered refrigerant by removing oil, moisture, and non-condensables so it can be reused, typically in the same appliance or another appliance owned by the same person.

Related: Recovery, Reclaiming, Non-condensable gases
Reclaiming

Reprocessing used refrigerant to meet the purity specifications of new product, which requires an EPA-certified reclaimer. Reclaimed refrigerant can be sold and used in any appliance.

Related: Recovery, Recycling, Recovery cylinder
De minimis release

A refrigerant release small enough that EPA does not require recovery under the venting prohibition. It generally applies only to very small amounts released during service or repair.

Related: Knowing release, Venting prohibition, Recovery
Knowing release

Intentionally or knowingly venting refrigerant to the atmosphere, which is prohibited for ozone-depleting refrigerants and their substitutes. Proper recovery is required instead.

Related: De minimis release, Venting prohibition, Recovery
Recovery cylinder

A refillable, DOT-approved cylinder used to hold recovered refrigerant. It must never be filled above 80% of capacity and must be labeled with the refrigerant type.

Related: 80% fill rule, Recovery, Reclaiming
80% fill rule

A safety requirement that recovery cylinders be filled to no more than 80% of their capacity by weight, leaving room for liquid expansion and preventing dangerous overpressure.

Related: Recovery cylinder, Liquid charging
Deep vacuum

A vacuum level low enough, typically below 500 microns, to remove moisture and non-condensable gases from a refrigeration system before charging.

Related: Micron, Triple evacuation, Non-condensable gases
Micron

A unit of vacuum equal to one-thousandth of a millimeter of mercury. Micron gauges measure deep vacuum during evacuation to verify moisture and non-condensables are removed.

Related: Deep vacuum, Triple evacuation
Triple evacuation

An evacuation method that alternately pulls a vacuum and breaks it with dry nitrogen, repeated three times, to remove moisture and non-condensables from a system.

Related: Deep vacuum, Nitrogen purge, Micron
Nitrogen purge

Using dry nitrogen to sweep air and moisture from tubing or to displace oxygen during brazing, preventing oxidation inside the system.

Related: Triple evacuation, Non-condensable gases
Non-condensable gases

Gases such as air or nitrogen that do not condense at normal system pressures and temperatures. They raise condensing pressure and must be removed by evacuation or purging.

Related: Nitrogen purge, Deep vacuum, Purge unit
Liquid charging

Adding refrigerant to a system as a liquid, often into the liquid line or receiver. It is required for zeotropic blends to prevent fractionation.

Related: Vapor charging, Zeotropic blend, Fractionation
Vapor charging

Adding refrigerant to the low-pressure side as a vapor. It is slower than liquid charging and is used for single-component refrigerants to avoid liquid slugging the compressor.

Related: Liquid charging, Fractionation
A2L refrigerant

A refrigerant safety classification for mildly flammable fluids under ASHRAE Standard 34. A2L refrigerants require special handling and leak detection because of flammability.

Related: Global Warming Potential (GWP), Hydrofluorocarbon (HFC)
Venting prohibition

EPA's rule that prohibits knowingly venting ozone-depleting refrigerants and their substitutes during service, maintenance, repair, or disposal. Refrigerant must be recovered instead.

Related: Knowing release, De minimis release, Recovery
Small appliance

EPA's category for household refrigerators, freezers, room air conditioners, dehumidifiers, and similar units with small refrigerant charges, typically five pounds or less.

Related: System-dependent recovery equipment, Self-contained recovery equipment, Recovery efficiency
System-dependent recovery equipment

Recovery equipment that relies on the appliance's own compressor to move refrigerant into a recovery container. It is commonly used for small appliances and cannot recover all refrigerant.

Related: Self-contained recovery equipment, Small appliance, Recovery efficiency
Self-contained recovery equipment

Recovery equipment with its own compressor that does not depend on the appliance's compressor. It can recover refrigerant faster and to lower levels than system-dependent equipment.

Related: System-dependent recovery equipment, Recovery efficiency, Small appliance
Recovery efficiency

The percentage of refrigerant removed from an appliance compared with the amount originally in it. EPA sets minimum recovery efficiency requirements that vary by appliance type and equipment.

Related: System-dependent recovery equipment, Self-contained recovery equipment, Small appliance
High-pressure appliance

EPA's equipment category for systems using refrigerants such as R-22, R-410A, and R-134a that operate at relatively high pressures. Type II certification covers these appliances.

Related: Very high-pressure appliance, R-410A, Superheat
Very high-pressure appliance

A Type II appliance that uses a refrigerant operating at pressures higher than R-22, such as R-410A. It requires gauges, hoses, and recovery equipment rated for the higher pressure.

Related: High-pressure appliance, R-410A, Recovery
Superheat

The difference between the actual temperature of refrigerant vapor and its saturation temperature at the same pressure. It is used to check charge in systems with a fixed orifice.

Related: Subcooling, Saturation temperature, Fixed orifice
Subcooling

The difference between the saturation temperature of liquid refrigerant and its actual liquid temperature at the same pressure. It is used to check charge in systems with a thermostatic expansion valve.

Related: Superheat, Saturation temperature, Thermostatic expansion valve (TXV)
Saturation temperature

The temperature at which a refrigerant changes between liquid and vapor at a given pressure. It is found on a pressure-temperature chart and is used to calculate superheat and subcooling.

Related: Superheat, Subcooling
Thermostatic expansion valve (TXV)

A metering device that controls refrigerant flow into the evaporator to maintain a set superheat. Systems with a TXV are typically charged by measuring subcooling.

Related: Subcooling, Superheat, Fixed orifice
Fixed orifice

A metering device with a fixed opening that does not adjust to load changes. Systems using a fixed orifice are typically charged by measuring superheat.

Related: Superheat, Thermostatic expansion valve (TXV), Saturation temperature
R-410A

A high-pressure HFC blend used in residential and commercial air conditioning. It requires POE oil and pressure-rated equipment because it operates at higher pressures than R-22.

Related: Very high-pressure appliance, Hydrofluorocarbon (HFC), High-pressure appliance
Low-pressure appliance

EPA's category for systems that use low-pressure refrigerants such as R-11 or R-123, typically centrifugal chillers whose evaporators operate in a vacuum.

Related: Chiller, Purge unit, R-123
Chiller

A machine that cools water or another fluid for building cooling. Large centrifugal chillers often use low-pressure refrigerants and require special recovery and purge procedures.

Related: Low-pressure appliance, Centrifugal compressor, Purge unit
Purge unit

A device on low-pressure chillers that removes air and other non-condensable gases from the refrigerant. It helps maintain efficiency and prevents excessive condensing pressure.

Related: Non-condensable gases, Low-pressure appliance, Chiller
Centrifugal compressor

A high-volume compressor used in large chillers that raises refrigerant pressure using a spinning impeller. It can operate with low-pressure refrigerants and may create a vacuum in the evaporator.

Related: Chiller, Low-pressure appliance, R-123
R-123

A low-pressure HCFC refrigerant used mainly in centrifugal chillers. It has a low ozone depletion potential but is being phased out.

Related: Low-pressure appliance, Chiller, Centrifugal compressor

EPA 608 Universal study plan

8 weeks · About 7 hours per week

Week 1

Type II - high- or very high-pressure appliances, except small appliances and MVACs

  • Identify the operating pressure range, cylinder valve type, and liquid/vapor charging rule for R-410A, R-32, R-134a, R-404A, and R-22

  • Apply the 80% cylinder fill rule to compute the maximum safe fill weight of two sample recovery cylinders

  • Distinguish recovery, recycling, and reclaiming, and name the equipment each one requires

  • Sequence the evacuation procedure for a high-pressure system from recovery through micron-level standing vacuum test

  • State the leak-detection method approved for each refrigerant class and explain why a halide torch is unacceptable for HFCs

Your checkpoint

Score at least 80% on a self-written 20-question Type II quiz covering refrigerant ID, fill rule, and evacuation.

Week 2

Type II - high- or very high-pressure appliances, except small appliances and MVACs & Type I - small appliances

  • Compute the EPA-required recovery vacuum (0 psig, 10 in Hg, or 20 in Hg) from a given system charge and component type

  • Compare Type I small-appliance recovery targets with Type II targets for the same charge weight

  • Diagram the four common leak-detection techniques and rank them by sensitivity

  • List three SNAP-acceptable refrigerant substitutes for small appliances and state one use restriction on each

  • Explain why R-410A requires different gauges and manifold ratings than R-22

Your checkpoint

One-page reference sheet mapping system charge and equipment type to the required recovery vacuum level, with no errors on a self-check.

Week 3

Type III - low-pressure appliances

  • Describe how a low-pressure chiller operates below atmospheric pressure and why air and moisture enter the system

  • Explain the function of the purge unit and identify what it removes from the system

  • Explain why moisture in a low-pressure system forms acids and how that damages the compressor and motor windings

  • State the EPA-required evacuation level for low-pressure appliances and compare it with the Type II levels learned in week 2

  • Identify the role of the rupture disc and relief devices on low-pressure equipment and why they differ from high-pressure relief valves

Your checkpoint

A labeled diagram of a low-pressure chiller refrigerant loop with purge unit, rupture disc, and charging points annotated from memory.

Week 4

Type I - small appliances & Universal - all types of equipment

  • Map the Section 608 core rules: ozone-depletion science, CFC and HCFC phase-out dates, and the venting prohibition

  • Apply the sales-restriction rules to determine who may buy refrigerant and what certification is required

  • Solve five scenario questions that mix small-appliance and universal content

  • Review and correct every missed item from weeks 1 through 3 and log the reason for each miss

Your checkpoint

Timed 25-question mixed practice section (Type I plus core) completed at 80% or better.

Week 5

Universal - all types of equipment

  • Apply the leak-repair requirements, including repair deadlines and the exemption conditions, to four scenario questions

  • Identify the records a technician must keep for refrigerant purchases, recovery, and disposal

  • Explain safe handling practices for nitrogen pressurization, brazing, and flammable refrigerants

  • Differentiate the certification type required for each class of equipment and for the Universal certification

Your checkpoint

A written compliance checklist covering leak repair, recordkeeping, and safe handling, verified against your study notes.

Week 6

Universal - all types of equipment & Type III - low-pressure appliances

  • Integrate recovery, evacuation, and charging decisions across high-pressure, low-pressure, and small-appliance systems in one decision tree

  • Resolve ten mixed questions where the equipment type is not stated outright and must be inferred from refrigerant and pressure clues

  • Re-explain the three most-missed concepts from weeks 1 to 5 without notes

Your checkpoint

Completed decision tree plus a 30-question mixed Domain 3 and 4 set scored at 85% or better.

Week 7

Type I - small appliances & Type II - high- or very high-pressure appliances, except small appliances and MVACs & Type III - low-pressure appliances & Universal - all types of equipment

  • Take two full-length practice exams under timed conditions and record per-domain scores

  • Rank your four domain scores and drill the two weakest domains until each reaches 85%

  • Convert every missed question into a one-line rule you can recite

Your checkpoint

Scorecard showing all four domains at 85% or higher on the second full-length practice exam.

Week 8

Type I - small appliances & Type II - high- or very high-pressure appliances, except small appliances and MVACs & Type III - low-pressure appliances & Universal - all types of equipment

  • Recite from memory the recovery vacuum levels, fill rule, and phase-out dates without reference material

  • Complete a final timed practice exam and review only the items missed

  • Simulate exam-day pacing by answering 25 questions in the allotted time per section

Your checkpoint

Final full-length practice exam passed with every section above the EPA passing threshold and a written list of the three facts to re-check the morning of the test.

Milestones

Week 2: Type II and Type I fundamentals: 80% or better on a 20-question self-quiz, and the recovery-vacuum reference sheet finished with zero self-check errors.

Week 4: First timed mixed section (Type I plus core) completed at 80% or better with all week 1 to 3 misses logged and corrected.

Week 6: Cross-domain decision tree finished and a 30-question mixed Domain 3 and 4 set scored at 85% or better.

Week 8: Two full-length practice exams complete; all four domains at 85% or higher on the final attempt and one line of remediation written for every missed item.

EPA 608 Universal exam day

Your checklist

Government-issued photo ID

Bring a valid, unexpired ID with a photo and signature. The name must match your registration exactly. Confirm with your certifying program which ID forms it accepts before test day.

Registration confirmation

Bring your appointment confirmation, registration number, or confirmation email - printed or accessible on your phone before you enter the testing area (phones are put away during the exam).

Payment or proof of payment

Some providers collect the exam fee at the site. Confirm with the provider whether payment is due in advance or on test day, and bring an accepted payment method if needed.

Provider contact information

Have the certifying program's phone number and the testing location's address or proctoring support number saved in case of delay, cancellation, or technical problems.

Route and arrival plan

Know the testing center location, parking situation, and traffic patterns. Plan to arrive well before your appointment time; confirm the provider's recommended arrival window.

Remote-testing setup (if testing online)

If you are taking the exam online, confirm with the provider the required webcam, microphone, browser, and internet speed, and plan to run any system check the day before. Requirements vary by provider.

Quiet, private room (remote only)

Online proctoring typically requires a private room with a clear desk and no interruptions. Confirm the provider's room and desk rules in advance.

Confirm what aids are permitted

Section 608 exams are generally closed-book with no notes or reference materials. Confirm with your provider whether any aid (for example, a basic calculator or scratch paper) is allowed - assume none until told otherwise.

Light meal and water beforehand

Eat and hydrate before check-in. Rules on drinks and snacks during the exam vary, so confirm with the provider rather than bringing them into the testing room.

Rest and a realistic study cutoff

Plan to stop heavy studying the night before. Fatigue hurts recall more than one extra hour of review helps.

Plan the day

72 hours before

Reconfirm your appointment date, time, and location (or online session details) with the certifying program. Verify your ID is valid and the name matches your registration.

72 hours before

Do focused review of the four exam areas - Core (regulations, refrigerant safety, environmental impact), Type I (small appliances), Type II (high-pressure systems), and Type III (low-pressure systems). For Universal you must pass all four.

72 hours before

Practice recalling key regulatory concepts and safety procedures from memory, since the exam is closed-book. Confirm the passing standard and number of questions with your provider, as these are set by the certifying program.

72 hours before

If testing online, run the provider's system check and test your webcam, microphone, and internet connection.

24 hours before

Do a light review only - skim your own summary notes, key definitions, and safety rules. Avoid learning new material.

24 hours before

Lay out your ID, confirmation, payment method, and directions or login information. Confirm your transportation or, for remote testing, that your room will be quiet and clear.

24 hours before

Get a full night's sleep. Set two alarms.

Morning of

Eat a normal meal and arrive at the testing center early - confirm the provider's recommended arrival time. For remote testing, log in early and clear your desk.

At check-in

Present your ID and confirmation, follow the proctor's instructions, and store all personal items, including your phone, where directed.

During the test

Read each question completely and watch for absolutes and 'except' wording. Answer every question - confirm with your provider whether unanswered questions are scored as incorrect.

During the test

If you are unsure, mark the question and return to it if the platform allows. Keep an eye on the clock and leave time to review flagged items.

After the test

Follow the provider's process for receiving your score and, if you pass, your certification card or certificate. Confirm turnaround time and how to obtain a replacement.

Rules to check

  • The exam is closed-book. Do not bring or use notes, reference materials, textbooks, or a phone in the testing area unless the provider explicitly permits an item - confirm any allowances with the provider in advance.

  • Your photo ID must match the name on your registration. If your name has changed or your ID is expired, contact the provider before test day; you may be turned away.

  • Follow all proctor instructions, including desk clearance, room scans for remote testing, and prohibitions on talking or leaving the view of the camera. Suspected misconduct can void your exam.

  • Breaks are set by the certifying program and proctoring platform. Confirm the break policy when you register, and plan to remain seated unless the proctor authorizes a break.

  • Scoring is per section. For Universal certification you typically must meet the passing score on Core, Type I, Type II, and Type III. Confirm the exact passing score and question count with your provider, since these are set by the certifying program.

  • Retake rules, waiting periods, and fees vary by provider. If you do not pass a section, contact the certifying program directly to learn your options rather than assuming a policy.

  • Testing accommodations must be requested in advance through the provider. Do not assume they can be arranged on the day of the exam.

EPA 608 Universal FAQ

How many EPA 608 Universal practice questions are available?

The practice set has 200 EPA 608 Universal questions. Each one includes the choices, the correct answer, and an explanation, and the set is free to read with no signup.

How many EPA 608 Universal flashcards are available?

The flashcard set has 32 EPA 608 Universal cards. Each card shows the term and its definition.

Which topics does the EPA 608 Universal study material cover?

The EPA 608 Universal study material has 4 sections, including Type I - Small Appliances, Type II - High-Pressure and Very High-Pressure Appliances, and Type III - Low-Pressure Appliances.

What format facts does the catalog list for the EPA 608 Universal exam?

The catalog lists these item types: open-book core test (cannot be used to obtain Universal certification), proctored core test (required to attain Universal certification), and written examination administered by an EPA-approved certifying organization for the EPA 608 Universal exam.