33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Minimum sewer design slope
- For an 8-inch sanitary sewer, a common minimum slope is 0.4 percent, or about 1 foot of fall per 250 feet of pipe, to maintain self-cleansing velocity.
- Self-cleansing velocity
- A flow velocity of roughly 2 feet per second at average daily flow keeps solids moving. Below this, grit and organic solids settle and accumulate in the pipe.
- Manning's equation
- Q equals 1.486 divided by n, times area times hydraulic radius to the two-thirds power, times slope to the one-half power. It predicts gravity sewer capacity.
- Infiltration versus inflow
- Infiltration is groundwater entering through defective pipes, joints, and manholes. Inflow is direct stormwater entry through roof drains, yard drains, and cross-connections.
- Wet well short cycling
- Rapid pump start and stop cycles indicate excessive inflow, a leaking check valve allowing backflow, or a faulty level sensor. Check design volume per cycle.
- CIPP rehabilitation
- Cured-in-place pipe lining inserts a resin-saturated tube, inflates it against the host pipe, and cures it in place to seal cracks and restore structural strength.
- Root intrusion control
- Roots enter at joints and cracks seeking moisture. Mechanical cutting or chemical foaming removes them, but sealing or lining the entry point prevents rapid regrowth.
- Permit-required confined space
- A confined space containing a hazardous atmosphere, engulfment, entrapment, or other serious hazard. Entry requires a permit, atmospheric testing, and an attendant.
- Atmospheric testing order
- Test oxygen first, then flammables, then toxics. Acceptable entry is 19.5 to 23.5 percent oxygen, under 10 percent LEL, and hydrogen sulfide below exposure limits.
- Hydrogen sulfide hazard
- H2S is heavier than air and collects in wet wells and manholes. It deadens the sense of smell at higher concentrations, so odor is not a reliable warning.
- Methane flammability range
- Methane is flammable in air between about 5 and 15 percent by volume. The lower explosive limit is 5 percent, so readings near 10 percent LEL require evacuation.
- Oxygen enrichment risk
- Oxygen above 23.5 percent makes clothing and materials burn violently. Never ventilate a confined space with pure oxygen; use forced air instead.
- Confined space ventilation
- Run forced-air ventilation at least 15 to 20 minutes before entry and keep it running during occupancy. Retest the atmosphere after any interruption.
- Trench spoil placement
- Spoil piles, equipment, and materials must be kept at least 2 feet back from the trench edge to prevent collapse and falling objects onto workers.
- Lockout tagout
- Isolate and verify zero energy on pumps, blowers, and valves before maintenance. Automatic pump start and stored pressure can injure workers in wet wells.
- Grab versus composite sample
- A grab sample captures one moment in time. A composite sample, either time-proportioned or flow-proportioned, represents an average over the sampling period.
- BOD holding time
- BOD samples are typically held at 4 degrees Celsius and analyzed within 48 hours. COD holding time is commonly 24 hours; pH must be analyzed promptly.
- Parshall flume advantage
- A Parshall flume is self-cleaning because flow accelerates through the throat, so it is preferred over a weir where sediment and debris are present.
- Chain of custody
- A written record of sample ID, collector, time, location, preservation, and every transfer. It makes monitoring data legally defensible for regulatory reporting.
- SSO reporting content
- Overflow reports document location, volume, duration, receiving water, cause, and corrective action. Report within the timeframe set by the permit or state rule.
- Field meter calibration
- Calibrate pH and dissolved oxygen meters before use and after each batch, and log the calibration. Uncalibrated readings are not defensible in regulatory reports.
- Non-detect reporting
- Results below the method detection limit are reported as less than that value, never as zero. Record the detection limit and the analytical method used.
- Clean Water Act basis
- The federal Clean Water Act regulates point-source discharges through the NPDES permit program, usually administered by state agencies under delegated authority.
- CMOM program
- Capacity, management, operation, and maintenance programs are the framework regulators use to evaluate collection systems: capacity assurance, management, operations, maintenance, and reporting.
- Pretreatment program
- Under 40 CFR Part 403, local limits control industrial discharges that could pass through treatment untreated, interfere with treatment, or harm workers and sludge.
- Grease interceptor rule
- Food service establishments must install and maintain grease interceptors sized to fixture volume and pump them on a required schedule to prevent sewer blockages.
- Air gap backflow protection
- An air gap is the only fail-safe backflow prevention method because it provides a physical separation between the potable supply and any contaminated source.
- Record retention period
- Keep O&M records, monitoring data, and overflow reports for the period the permit specifies, commonly 3 years and longer during enforcement or litigation.
- Operator certification
- State-issued certification requires passing an exam and earning continuing education hours to renew. Certificate level may limit the system size an operator supervises.
- Hazard communication
- Employers must inform workers about hazardous chemicals through labels, safety data sheets, and training, including chlorine, sulfur dioxide, and treatment polymers.
- Public overflow notification
- When an overflow may affect public health or waters, the utility must notify the public and the regulatory agency and document the notice in its records.
- Prohibited discharge limits
- Local limits bar flammable, corrosive, and toxic wastes that pass through or interfere with treatment, and set numeric limits on metals, oil, and grease.
- Cross-connection control
- A cross-connection is any link between potable water and a contamination source. Backflow prevention devices or air gaps must protect every such link.